SPECIFICATION DATA
68-3084-02
PC3F2699IUF00 Hydronic
Circulating 3 Speed Pump
APPLICATION
The PC3F in-line, wet rotor circulator with universal flange is
designed for applications in closed-loop hydronic heating and
cooling systems, as well as in solar-powered systems. The
pump is non-submersible and for use in dry, frost-free, well-
ventilated installations.
SPECIFICATIONS
Rate of flow:
up to 34 gpm (128.7 lpm)
Pressure head:
up to 31 ft (9 m)
Voltage:
/-10% 60hz
Amperage:
See “Speed switching” on page 2.
Max. Pressure:
145 psi (at room temperature);
50 psi (at 200°F [93°C])
Temperature Range:
Ambient temperature: 32°F to 104°F (0°C to 40°C)
Media temperature: 14°F to 230°F (-10°F to 110°C) [to 200°F
(93°C) with optional check valve installed]
Storage Temperature:
-40°F to 100°F (-40° to 66°C)
Standards:
Insulation Class F
Temperature Class FT 95
Fig. 1. Pump dimensions in in. (mm).
Shipping weight:
9.5 lbs (4.32 Kg)
L1
L2
L3
L4
L5
6.5 (165.5) 6.1 (155) 6.5 (165.5) 7.75 (197) 3.2 (80.2)
M32832A
L2
L4
L3
L1
L5