SCS Series Manual —
P/N 15712:L 7/18/16
61
Configuration
The SCS⁄SCE
Toggle Switch Operation for FSCS Mode
FSCS ON/AUTO/OFF (OPEN/AUTO/CLOSED) Toggle Switch Operation
Each ON/AUTO/OFF toggle switch will function according to Table 3.6 for non-alarm conditions and Table 3.7 for alarm conditions. Plac-
ing a toggle switch in the ON or OFF position will activate/deactivate the control points as shown. Once this has occurred, further control-
by-event processing at the FACP is inhibited.
NOTE:
The AUTO position column in the table indicates the control module (CM) condition when the control panel is in a normal, non-
alarm condition.
SWITCH
GROUP TYPE
FSCS NON-DEDICATED SYSTEM TOGGLE SWITCH POSITION
ON
AUTO
OFF
1
Deactivates CON
OFF⁄CL
CM
Deactivates CON
OFF⁄CL
CM
Activates CON
OFF⁄CL
CM
2
Deactivates CON
OFF⁄CL
CM
Deactivates CON
OFF⁄CL
CM
Activates CON
OFF⁄CL
CM
3
Deactivates CON
OFF⁄CL
CM
Deactivates CON
OFF⁄CL
CM
Activates CON
OFF⁄CL
CM
4
Activates CON
ON⁄OP
CM
Deactivates CON
ON⁄OP
CM
Deactivates CON
ON⁄OP
CM
5
Activates CON
ON⁄OP
CM
Deactivates CON
ON⁄OP
CM
Deactivates CON
ON⁄OP
CM
6
Activates CON
ON⁄OP
CM
Deactivates CON
ON⁄OP
CM
Deactivates CON
ON⁄OP
CM
7
Activates CON
ON⁄OP
CM
Deactivates CON
OFF⁄CL
CM
Deactivates CON
ON⁄OP
CM
Deactivates CON
OFF⁄CL
CM
Deactivates CON
ON⁄OP
CM
Activates CON
OFF⁄CL
CM
8
Activates CON
ON⁄OP
CM
Deactivates CON
OFF⁄CL
CM
Deactivates CON
ON⁄OP
CM
Deactivates CON
OFF⁄CL
CM
Deactivates CON
ON⁄OP
CM
Activates CON
OFF⁄CL
CM
9
Activates CON
ON⁄OP
CM
Deactivates CON
OFF⁄CL
CM
Deactivates CON
ON⁄OP
CM
Deactivates CON
OFF⁄CL
CM
Deactivates CON
ON⁄OP
CM
Activates CON
OFF⁄CL
CM
SWITCH
GROUP TYPE
FSCS DEDICATED SYSTEM TOGGLE SWITCH POSITION
ON
AUTO
OFF
1-9
see above
depends on CBE after Reset (see
Automatic Control in Dedicated
System Operation section)
see above
Table 3.6 FSCS Toggle Switch Functions (Non-Alarm Condition)
Table 3.7 FSCS Toggle Switch Functions (Alarm Condition)
SWITCH
GROUP TYPE
FSCS NON-DEDICATED SYSTEM TOGGLE SWITCH POSITION
ON
AUTO
OFF
1
Deactivates CON
OFF⁄CL
CM
depends on CBE after Reset
Activates CON
OFF⁄CL
CM
2
Deactivates CON
OFF⁄CL
CM
depends on CBE after Reset
Activates CON
OFF⁄CL
CM
3
Deactivates CON
OFF⁄CL
CM
depends on CBE after Reset
Activates CON
OFF⁄CL
CM
4
Activates CON
ON⁄OP
CM
depends on CBE after Reset
Deactivates CON
ON⁄OP
CM
5
Activates CON
ON⁄OP
CM
depends on CBE after Reset
Deactivates CON
ON⁄OP
CM
6
Activates CON
ON⁄OP
CM
depends on CBE after Reset
Deactivates CON
ON⁄OP
CM
7
Activates CON
ON⁄OP
CM
Deactivates CON
OFF⁄CL
CM
depends on CBE after Reset
Deactivates CON
ON⁄OP
CM
Activates CON
OFF⁄CL
CM