RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
53
Master Programming Level
Programming
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and indi-
cate the selection next to the Type option.
Output Circuit Map
Output Mapping (per input zone) allows the programmer/operator to assign the Output Circuits that
will be activated when a particular Input Zone or cross-zoned releasing group goes active. Pressing
1
for
Output Circuit Map
while viewing Edit Input Zone Screen #3 will display screens which show
the Output Circuits programmed to activate when the selected Input Zone (or cross-zoned releasing
group) is activated. Output Map Screen #1 displays the Output Type Codes and programming for
Output Circuits 1 through 3 and Output Map Screen #2 displays the Output Type Code and pro-
gramming for Output Circuit 4.
As an example, if Template 1 has been selected as the FACP Configuration [refer to“FACP
CONFIG (Application Templates)” on page 51], selecting the Output Circuit Map for Input Zone 1
will display the following screens:
The screens indicate that when Input Zone 1 is activated:
Output Circuit #1 default programmed as
Alarm NAC
will activate (Yes)
N/A
N/A
Waterflow
Fire
Waterflow NS (nonsilenceable)
Fire, nonsilenceable
Combo
Fire/Supervisory
Combo w/AutoResettable Superv
2
Fire/Supervisory, nonlatching
2-Wire Smoke
Fire Alarm
2-Wire Heat
Fire Alarm
N/A
Linear Heat
Fire Alarm
N/A
N/A
Fire
Fire Alarm
Low Pressure
Supervisory, latching
Low Pressure AutoResettable2
Supervisory, nonlatching
High Pressure
Supervisory
High Pressure AutoResettable2
Supervisory, nonlatching
Disable Release
3
Supervisory, nonlatching (disables Release Circuits)
Supervisory
Supervisory, latching
Supervisory AutoResettable2
Supervisory, nonlatching
N/A
2nd-Shot Water Switch
4
Fire Alarm, nonlatching
1 Activation of a Manual Release Switch will override Predischarge Delay, resulting
in an immediate water release.
2
AutoResettable
means that a device with this type code, when activated, will
automatically reset when the corresponding condition is cleared.
3
Disable Release
allows the installer to disable the releasing solenoids during
system testing. Disable Release will only work when the system is
not
in alarm.
4 The
2nd-Shot Water Switch
provides the option of performing another immediate
water release manually. Refer to “2nd-Shot Water Switch” on page 81.
Table 3.1 Zone Types
INPUT ZONE #
1=OUTPUT CIRCUIT MAP
2=FREEZE SUPV.
Edit Input Zone Screen #3
OUTPUT MAP ZONE 1
1=ALARM NAC YES
2=WATERFLOW NAC NO
3=RELEASE 1 YES
Output Map Screen#1
OUTPUT MAP ZONE 1
4=SUPV BELL NAC N/A
Output Zone Screen#2