RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
45
ANN-BUS Devices
Installation
The LEDs are wired as illustrated in Figure 2.22. Note that the illustration depicts only connectors
P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).
2.7.6 N-ANN-LED Annunciator Module
The N-ANN-LED annunciator modules provide LED annunciation of general system faults and
input zones when used with a compatible FACP. The N-ANN-LED module provides alarm (red),
trouble (yellow) and supervisory (yellow) indication for up to ten input zones.
Canadian Applications: The N-ANN-LED is supplied standard with the Canadian version of the
FACP. It is mounted to the dress panel included with this model.
Specifications
•
Max. ANN-BUS Voltage: 24 VDC
•
Max. Current:
Alarm: 68 mA
Standby: 28 mA
•
Operating Temperature: 32
o
F to 120
o
F (0
o
C to 49
o
C)
•
For indoor use in a dry location only
Mounting/Installation
Install the N-ANN-LED Module as described in the documentation supplied with the annunciator.
Figure 2.22 N-ANN-I/O LED Wiring