RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
103
Template 4: Dual Hazard - Split Release
FACP Configuration Templates
B.4 Template 4: Dual Hazard - Split Release
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).
Input Zone Types:
•
Zone 1 = 2-wire smoke
•
Zone 2 = Fire
•
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay Timer 10 set to
secs.)
•
Zone 4 = Supervisory
•
Zone 5 = Manual Release
•
Zone 6 = Pull Station
Output Circuit Types:
•
Output 1 = Alarm NAC, silenceable, coded for steady on
•
Output 2 = Supervisory Bell NAC, silenceable, coded for steady on
•
Output 3 = Release Solenoid 1 (unsupervised for shorts)
•
Output 4 = Release Solenoid 2 (unsupervised for shorts)
Timers
•
Soak Timer 1 - set for 10 minutes
•
Soak Timer 2 - set for 10 minutes
•
Waterflow Delay Timer - set for 10 seconds
•
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of Input Zone 1 (2-Wire Smoke) will operate Release Solenoid 1 Output #3 and
Alarm NAC Output #1. Activation of Input Zone 2 (Fire) will operate Release Solenoid 2 Out-
put #4 and Alarm NAC Output #1. Activation of Input 5 (Manual Release)
or
Input 6 (Manual
Pull Station) will operate Solenoid 1 Output #3
and
Solenoid 2 (Output #4)
and
Alarm NAC
Output #1. Release Solenoid 1 will turn off water release following time-out of the 10 minute
Soak Timer 1 and Release Solenoid 2 will turn off water release following time-out of the 10
minute Soak Timer 2
•
Activation of Input Zone 3 (Waterflow) will operate the Alarm NAC Output #1. There is a 10
second FACP initiated delay in activation since Waterflow Delay Timer is set to 10 seconds
•
Activation of Input Zone 4 (Supervisory) will operate the Supervisory Bell NAC Output #2
Template 4: DUAL HAZARD - SPLIT RELEASE
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE SMOKE
FIRE
WATERFLOW
SUPV.
MANUAL
RELEASE
PULL
STATION
#1 ALARM NAC
X
X
X
X
X
#2 SUPV BELL NAC
X
#3 RELEASE SOLENOID 1
X
X
X
#4 RELEASE SOLENOID 2
X
X
X