Honeywell NOTIFIER NZM-100 Installation And Maintenance Instructions Download Page 2

FIGURE 3. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS, NFPA CLASS B

(+)

(–)

(+)

(–)

(+)

(–)

+

+

LISTED BATTERY-BACKUP SWITCHED 

REGUALTED DC POWER SUPPLY

POWER TO THE INTERFACE MODULE 

MUST BE EXTERNALLY SWITCED TO 

RESET THE DETECTORS. A NC-100R 

RELAY CONTROL MODULE CAN BE USED 

TO SWITCH POWER FROM A STANDARD 

POWER SUPPLY - SEE FIGURE 5.

OPTIONAL BRANCH CIRCUIT

TO NEXT INTERFACE MODULE. 

MODULE SUPERVISES 

SUPPLY VOLTAGE AND 

DETECTOR LOOP.

(+)

(–)

DO NOT MIX FIRE ALARM INITIAT-

ING, SUPERVISORY, OR SECURITY 

DEVICES ON THE SAME MODULE.

TO NEXT

DEVICE

INTERFACE 

MODULE

SIGNAL LINE CIRCUIT (SLC) 

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

CONNECT MODULES TO 

LISTED COMPATIBLE 

CONTROL PANELS ONLY.

FROM PANEL 

OR PREVIOUS 

DEVICE

3.9K EOL 

RESISTOR 

(INCLUDED 

A2143-10) 

DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. DETECTORS MUST 

BE UL LISTED COMPATIBLE WITH MODULE. INSTALL DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS.

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT 

ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

TERMINAL WIRING MUST BE 

POWER LIMITED.

C0992-00

FIGURE 4. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS, NFPA CLASS A

(+)

(–)

(+)

(–)

(+)

(–)

+

+

(+)

(–)

LISTED BATTERY-

BACKUP SWITCHED 

REGUALTED DC 

POWER SUPPLY

POWER TO THE INTERFACE 

MODULE MUST BE EXTERNALLY 

SWITCED TO RESET THE 

DETECTORS. A NC-100R RELAY 

CONTROL MODULE CAN BE 

USED TO SWITCH POWER FROM 

A STANDARD POWER

SUPPLY - SEE FIGURE 5.

OPTIONAL BRANCH CIRCUIT

TO NEXT INTERFACE MODULE. 

MODULE SUPERVISES SUPPLY 

VOLTAGE AND DETECTOR LOOP.

DO NOT MIX FIRE ALARM INITIATING, 

SUPERVISORY, OR SECURITY 

DEVICES ON THE SAME MODULE.

3.9K EOL RESISTOR REQUIRED 

AT TERMINALS 8 & 9 

(INCLUDED) A2143-10

DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. DETECTORS 

MUST BE UL LISTED COMPATIBLE WITH MODULE. INSTALL DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS.

INTERFACE 

MODULE

TO NEXT

DEVICE

SIGNAL LINE CIRCUIT (SLC) 

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

CONNECT MODULES TO LISTED 

COMPATIBLE CONTROL PANELS ONLY.

FROM PANEL 

OR PREVIOUS 

DEVICE

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT 

ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

TERMINAL WIRING MUST 

BE POWER LIMITED.

C0991-00

FIGURE 5. RELAY CONTROL MODULE USED TO DISCONNECT A POWER SUPPLY*

(+)

(–)

(+)

(–)

(+) 
(–)

(+)

(–)

(+)

(–)

SIGNAL LINE CIRCUIT (SLC) 

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

CONNECT MODULES TO LISTED 

COMPATIBLE CONTROL PANELS ONLY.

FROM PANEL OR 

PREVIOUS DEVICE

RELAY CONTROL  

MODULE

TO NEXT

DEVICE

POWER LIMITED DC 

POWER SUPPLY, 

LISTED FOR FIRE 

PROTECTION WITH 

BATTERY BACKUP

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT 

ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

C0923-02

FIGURE 6. INTERFACE TWO-WIRE INTRINSICALLY SAFE CONVENTIONAL DETECTORS, NFPA CLASS B

(+)

(–)

(+)

(–)

(+)

(–)

LISTED BATTERY-BACKUP SWITCHED 

REGUALTED DC POWER SUPPLY

POWER TO THE INTERFACE MODULE MUST BE 

EXTERNALLY SWITCED TO RESET THE 

DETECTORS. A NC-100R RELAY CONTROL 

MODULE CAN BE USED TO SWITCH POWER FROM 

A STANDARD POWER SUPPLY - SEE FIGURE 5.

OPTIONAL BRANCH CIRCUIT

TO NEXT INTERFACE MODULE. 

MODULE SUPERVISES SUPPLY 

VOLTAGE AND DETECTOR LOOP.

(+)

(–)

DO NOT MIX FIRE ALARM INITIATING, 

SUPERVISORY, OR SECURITY 

DEVICES ON THE SAME MODULE.

TO NEXT

DEVICE

INTERFACE 

MODULE

SIGNAL LINE CIRCUIT (SLC) 

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

CONNECT MODULES TO LISTED 

COMPATIBLE CONTROL PANELS ONLY.

FROM PANEL 

OR PREVIOUS 

DEVICE

3.9K EOL 

RESISTOR 

(INCLUDED 

A2143-10)

DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. DETECTORS MUST 

BE UL LISTED COMPATIBLE WITH MODULE. INSTALL DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS.

*NOTE: ANY FAULT IN THE POWER SUPPLY 

IS LIMITED TO THAT ZONE AND DOES NOT 

RESULT IN A FAULT IN A SEPARATE ZONE.

+

+

TERMINAL WIRING MUST 

BE POWER LIMITED.

MTL3043 

ISOLATOR

C0993-00

  

I56-3505-003 

 

 

©2022 Notifier. 7/1/2022