Honeywell NOTIFIER NZM-100 Installation And Maintenance Instructions Download Page 1

BEFORE INSTALLING

This information is included as a quick reference installation guide. Refer to 
the control panel installation manual for detailed system information. If the 
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

The NZM-100 Interface Module is intended for use in addressable two-wire 
systems, where the individual address of each module is selected using the 
built-in rotary switches. This module allows addressable panels to interface 
and monitor two-wire conventional smoke detectors. It transmits the status 
(normal, open, or alarm) of one full zone of conventional detectors back to 
the control panel. All two-wire detectors being monitored must be UL compat-
ible with this module. The NZM-100 has a panel controlled LED indicator and 
can be used to replace an M302 module in existing systems.

COMPATIBILITY REQUIREMENTS

To ensure proper operation, these modules shall be connected to listed com-
patible system control panels only.

FIGURE 1. CONTROLS AND INDICATORS

C0909-01

SPECIFICATIONS

Normal Operating Voltage: 

15 to 32 VDC

Maximum Current Draw: 

5.1 mA (LED on)

Average Operating Current: 

270 µA (LED flashing)

EOL Resistance: 

3.9K ohms

Maximum IDC Resistance: 

25 Ohms

External Supply Voltage (between Terminals T10 and T11)
 

Regulated DC Voltage: 

24 VDC power limited

 

Ripple Voltage: 

0.1 Volts RMS maximum

 

Alarm Current: 

90 mA per module

 

Standby Current:  

13 mA Maximum @24 VDC

Temperature Range: 

32˚F to 120˚F (0˚C to 49˚C)

Humidity: 

10% to 93% Non-condensing

Dimensions: 

4.5˝ H × 4˝ W × 1.25˝ D (Mounts to a 4˝ square by 2.125˝ deep box.)

Accessories: 

SMB500 Electrical Box

  

I56-3505-003 

 

 7/1/2022

NZM-100 Interface Module

I56-35

05-00
3

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203.484.7161

INSTALLATION AND MAINTENANCE INSTRUCTIONS

MOUNTING

The NZM-100 mounts directly to 4-inch square electrical boxes. (See 
Figure 2A.) The box must have a minimum depth of 2.125˝. Surface mounted 
electrical boxes (SMB500) are available.

FIGURE 2A. MODULE 

FIGURE 2B 

MOUNTING

ISOLATED

QUADRANT

C1044-00

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and 
regulations. This module is intended for power-limited wiring only.
1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.  Set the address on the module per job drawings.
3.   Secure module to electrical box (supplied by installer), as shown in 

Figure 2A.

Reviews: