Honeywell Notifier NZM-100-6 Installation And Maintenance Instructions Manual Download Page 3

Step 2: 

 Carefully swing the upper edge of the board back towards the back 
of the chassis until it touches the two standoffs.

Step 3: 

 Align two 4-40 screws with the two standoffs and tighten.

Step 4:    Address and wire the modules according to the instructions in this 

manual.

The steps in Figures 6a and 6b describe and illustrate module installation 
when the rear chassis position and the position in front of it will be filled.  
Front position installation is possible only if the rear position is filled with 
another module.

FIGURE 6A. INSTALLATION OF NZM-100-6 MODULE IN A REAR 

CHASSIS POSITION, METHOD TWO

 

1

  

C0225-00

Step 1: 

 Insert the bottom edge of the NZM-100-6 module down into a rear 
slot of the chassis.

Step 2: 

 Carefully swing the upper edge of the board towards the back of the 
chassis until it touches the short standoff attached to the chassis.

Step 3: 

 Align the long standoff with the short standoff and tighten.

FIGURE 6B. INSTALLATION OF NZM-100-6 MODULE IN FRONT CHASSIS 

POSITION

 

2

3

1

C0226-00

Step 1: 

 Insert the bottom edge of the NZM-100-6 module down into a front 
slot of the chassis.

Step 2: 

 Carefully swing the upper edge of the board towards the back of 
the chassis until it touches the 1.25˝ (32 mm) standoffs installed on 
the rear module.

Step 3: 

 Align two 4-40 screws with the two standoffs and tighten.

Step 4: 

 Address and wire the modules according to the instructions in this 
manual.

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and 
regulations.
1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.   All wiring to the NZM-100-6 is done via terminal blocks. In order to prop-

erly make electrical connections strip approximately 0.25˝ of insulation 
from the end of wire, sliding the bare end of the wire under the clamping 
plate screw.  

3.   Set the address on the modules per the job drawing. Use the rotary code 

switches to set the address of the first module (between 01 and 154).

In Class B operation, the remaining modules are automatically assigned to the 
next five higher addresses. For example, if the base address switch is set to 28, 
the next five  modules will be addressed to 29, 30, 31, 32 and 33.

FIGURE 7.

 

TENS

0

7 8

6

5

4

3

2

1

9

10

11

12

13

14

15

 C0227-00

The module is shipped in Class B position, remove shunts for Class A. When 
operating in Class A, alternate modules are paired together (+0/+1, +2/+3, 
+4/+5), resulting in a total of three modules. For example, if the base ad-
dress switch is set to 28, then 30 and 32 will be automatically assigned to the 
modules while 29, 31 and 33 are available to be used for other modules on the 
SLC. For Class A and B operation, DO NOT set the lowest address above 154, 
as the other modules will be assigned to nonexistent addresses.

NOTE: Some panels support extended addressing. In order to set the module 
above address 99 on compatible systems, carefully remove the stop on the 
upper rotary switch (see Figure 7). If the panel does not support extended ad-
dressing, do not set the lowest address above 94.

4.    A shunt is provided to disable a maximum of two unused modules in 

Class B operation and Class A operation. Modules are disabled from the 
highest address and work downward.  If two modules are disabled, the 
lowest four addresses will be functional, while the highest two will be 
disabled. For example, in Class B operation, if the shunt for Address Dis-
able is placed on “two” and the base switch is set to 28, the modules will 
be assigned to 28, 29, 30 and 31 while disabling the highest two positions.

NOTE: Place unused shunts on single pin to store on board for   future use.
NOTE: Power must not be applied to the unit when changing functionality of 
the shunts.

WIRING NOTES

•   Power-limited circuits must employ type FPL, FPLR, or FPLP cable as 

required by Article 760 of the NEC.

•   All wiring must be in accordance with the NEC, NFPA 72 and all other 

applicable codes and standards. All external power supplies must be 

power limited with battery back-up. All external power supplies and 

detectors must be UL listed for fire protection signaling applications.

PROGRAMMING

Connect the module to listed-compatible control panels only. Refer to panel 
installation documentation to confirm compatibility. 

The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.  

  3 

I56-2990-004 

 

 

  7/1/2022

Summary of Contents for Notifier NZM-100-6

Page 1: ...1151 A SYSTEM SENSOR B110LP B401 20 1451 A SYSTEM SENSOR B401 B401B 20 1451DH A SYSTEM SENSOR DH400 20 2151 A SYSTEM SENSOR B110LP B401 20 2451 A SYSTEM SENSOR DH400 B401B B401 20 2451TH A SYSTEM SENSOR B401 B401B 20 5451 A SYSTEM SENSOR B401 20 1100 A SYSTEM SENSOR N A 20 1400 A SYSTEM SENSOR N A 20 2100AT A SYSTEM SENSOR N A 20 2100B A SYSTEM SENSOR N A 20 2100D A SYSTEM SENSOR N A 20 2100S A SY...

Page 2: ...fset below the rear NZM 100 6 module positions so that all of the status indicators are visible C0235 00 Cabinets A BB 25 CAB 3 or CAB 4 Series cabinet will house the CH 6 chassis with up to six NZM 100 6 modules installed on it Refer to cabinet installation docu ments for dimensions The BB XP cabinet houses one or two NZM 100 6 modules on the internal chassis that is part of the cabinet Refer to ...

Page 3: ... if the base address switch is set to 28 the next five modules will be addressed to 29 30 31 32 and 33 FIGURE 7 TENS 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 C0227 00 The module is shipped in Class B position remove shunts for Class A When operating in Class A alternate modules are paired together 0 1 2 3 4 5 resulting in a total of three modules For example if the base ad dress switch is set to 28 t...

Page 4: ...lect Class A remove the two shunts from the A B select positions 2 To use a common power supply between multiple NZM 100 6 modules connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent NZM 100 6 module 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS TO NEXT DEVICE STATUS INDICATORS IN OUT 0 1 2 3 4 5 IDC ADDRESS IDC ADDRESS IDC ADDRESS SLC FROM PANEL OR PREVIOUS DEVICE CONNECT MODULES TO L...

Page 5: ...NAL SUPPLY EXTERNAL POWER SUPPLY PCB 1 PCB 2 VIEW A A 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 FIGURE 10 EXAMPLE OF MULTIPLE BOARDS SHARING SAME EXTERNAL SUPPLY Refer to figures 8 and 9 for typical wiring Make certain lip on long power supply jumper engages retaining tab on T5 or T6 as shown in Vie...

Page 6: ...mined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV techni...

Reviews: