BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the appropriate control panel installation manual for detailed system informa-
tion. If the modules will be installed in an existing operational system, inform
the operator and local authority that the system will be temporarily out of ser-
vice. Disconnect the power to the control panel before installing the modules.
This system contains static sensitive components. Always ground yourself
with a proper wrist strap before handling any circuits so that static charges are
removed from the body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
SPECIFICATIONS
Normal Operating Voltage:
15-32 VDC
Stand-By Current:
2.3 mA @ 24 V
Alarm Current:
40 mA (assumes all six LEDs solid on)
Temperature Range:
32°F to 120°F (0°C to 49°C)
Humidity:
10 to 93% Non-condensing
Dimensions:
6.8˝H x 5.8˝W x 1.25˝D
Accessories:
CH-6 Chassis;
BB-25 Cabinet;
;
BB-XP
Cabinet; CAB-4 Series Cabinets; CAB-3 Series Cabinets
Wire Gauge:
12-18 AWG
Maximum IDC Wiring Resistance: 25 Ohms
External Power Supply Voltage:
Regulated 24 VDC
Ripple Voltage:
0.1 volts RMS maximum
IDC (supervised and power limited)
DC Voltage:
18-28 volts power limited
Frequency:
DC
Alarm Current:
90mA per circuit
Standby Current 6 circuits:
42mA Maximum @18 VDC
56mA Maximum @24 VDC
66mA Maximum @28 VDC
NZM-100-6 Six Zone Interface Module
DET.
DETECTOR
MODEL COMP. ID
MANUFACTURER
BASE MODEL
MAX DET.
1151
A
SYSTEM SENSOR
B110LP,B401
20
1451
A
SYSTEM SENSOR
B401, B401B
20
1451DH
A
SYSTEM SENSOR
DH400
20
2151
A
SYSTEM SENSOR
B110LP, B401
20
2451
A
SYSTEM SENSOR
DH400, B401B,B401
20
2451TH
A
SYSTEM SENSOR
B401, B401B
20
5451
A
SYSTEM SENSOR
B401
20
1100
A
SYSTEM SENSOR
N/A
20
1400
A
SYSTEM SENSOR
N/A
20
** 2100AT
A
SYSTEM SENSOR
N/A
20
2100B
A
SYSTEM SENSOR
N/A
20
2100D
A
SYSTEM SENSOR
N/A
20
2100S
A
SYSTEM SENSOR
N/A
20
2100TB
A
SYSTEM SENSOR
N/A
20
2100TD
A
SYSTEM SENSOR
N/A
20
2100TS
A
SYSTEM SENSOR
N/A
20
2300B
A
SYSTEM SENSOR
N/A
20
2300TB
A
SYSTEM SENSOR
N/A
20
2400
A
SYSTEM SENSOR
N/A
20
2400TH
A
SYSTEM SENSOR
N/A
20
* 2W-B
A
SYSTEM SENSOR
N/A
20
* 2W-TB
A
SYSTEM SENSOR
N/A
20
DH100LP
A
SYSTEM SENSOR
N/A
20
* Class B Only
** No Accessory will be supported by 2100AT
COMPATIBLE TWO-WIRE SYSTEM SENSOR SMOKE DETECTORS FOR USE WITH NZM-100-6 WITH ZONE A IDENTIFIER
GENERAL DESCRIPTION
The NZM-100-6 Six Zone Interface Module is intended for use in an intelli-
gent alarm system. Each module provides an interface between the intelligent
alarm system and a conventional alarm system loop. A common SLC input is
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently
from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module
from 01 to 154. The remaining modules are automatically assigned to the next
five higher addresses. Provisions are included for disabling a maximum of two