 Page 2 of 7 — DN-60637:N • 9/15/2022

          

F

LASH

S

CAN

®

 I

NTELLIGENT

 F

EATURES

Polls up to 318 devices in less than two seconds.

Activates up to 159 outputs in less than five seconds.

Multicolor LEDs blink device address during Walk Test.

Fully digital, high-precision protocol (U.S. Patent 5,539,389).

Manual sensitivity adjustment — up to nine levels.

Pre-alarm ONYX intelligent sensing — up to nine levels.

Day/Night automatic sensitivity adjustment.

Sensitivity levels:

– Photo  –

 0.5 to 2.35%/foot obscuration.

– High-Sensitivity Photoelectric (VIEW

®

) – 

Open Air Protection

(0.5% - 2.0%/ft. obscuration), Special Applications (0.02%-
0.5%/ft. obscuration

)

– Multi-Criteria Detector 

– Open Air Protection (2.52-3.89%/ft.

obscuration), Special Applications (1.13-2.52%/ft. obscuration)

Drift compensation (U.S. Patent 5,764,142).

Degraded mode: In the unlikely event that the CPU-320SYS
microprocessor fails, FlashScan detectors revert to degraded
operation and can activate the control panel’s NAC circuits and
alarm relay. Each of the four built-in panel circuits includes a Dis-
able/Enable switch for this feature.

Multi-detector algorithm involves nearby detectors in alarm deci-
sion (U.S. Patent 5,627,515).

Automatic detector sensitivity testing (NFPA-72 compliant).

Maintenance alert (two levels).

Self-optimizing pre-alarm.  

SWIFT W

IRELESS

 

Self-healing mesh wireless protocol.

Each SWIFT Gateway supports up to 49 SWIFT devices. 

Up to 4 wireless gateways can be installed with overlapping net-
work coverage. 

R

ELEASING

 F

EATURES

Ten independent hazards.

Sophisticated cross-zone (three options).

Delay timer and Discharge timers (adjustable).

Abort (four options).

Low-pressure CO

2

 listed.

V

OICE

 F

EATURES

Integrates with FirstCommand Series. 

See DN-60772.

Telephone applications require NFC-FFT.

H

IGH

-E

FFICIENCY

 O

FFLINE

 S

WITCHING

 

3.0 A P

OWER

 S

UPPLY

 (6.0 A 

IN

 A

LARM

)

120 VAC (NFS-320/NFS-320C); 240 VAC (NFS-320E).

Displays battery current/voltage on panel (with display).

FSV-951 S

ERIES

  V

IEW

®

 (V

ERY

  I

NTELLIGENT

  E

ARLY

  W

ARNING

)

H

IGH

-S

ENSITIVITY

 S

MOKE

 D

ETECTOR

       

Advanced ONYX intelligent sensing algorithms differentiate
between smoke and non-smoke signals.

Addressable operation pinpoints the fire location.

Ivory models (-IV) support CLIP mode as well as FlashScan.

ULC listed models available; “A” models are ULC Listed.

-R is retrofit, backwards compatible for use with older panels.

FCO-951/-IV A

DVANCED

 M

ULTI

-C

RITERIA

 F

IRE

/CO D

ETECTOR

Detects all four major elements of a fire (smoke, heat, CO, and
flame).

135°F (57.2°C) fixed-temperature heat detector.

Transmits an alarm signal due to heat.

Separate signal for life-safety CO detection.

Sample
System
Options

NFS-320SYSdia1-2022.wmf

SLC Intelligent Loop 1

DEVICES

FPTI-951

FSP-951 
FST-951

FCO-951

…etc.

NBG-12LX

FMM-1

IDC

FDU-80

Up to 32 remote displays

EIA-485

EIA-485

EIA-232

2048 annunciator/control points

Optional 318-point UDACT

Dual phone 
lines to 
Central 
Station

ACM/AEM-24AT 

LED Annunciator

LDM-32 

Custom Graphics

ACM-8R 

Relay Control 

FCM-1 

NAC

 

FRM-1 

Relay Contact

KDM-R2 

display 

OR

NFS-320SYS

“C” cabinet size shown

LCD2-80

PRN Series Printer

FWSG(A) 

XP6/10 I/O Modules

Summary of Contents for Notifier NFS-320SYS

Page 1: ...detectors notification or relay wireless modules are available for use with the FWSG A Standard 80 character display Network options High speed network for up to 200 nodes N16e x NFS2 3030 NFS2 640 NFS 320 C NFS 320SYS NCD NCA 2 DVC EM ONYXWorks NFS 3030 NFS 640 and NCA Standard network for up to 103 nodes N16e x NFS2 3030 NFS2 640 NFS 320 C NFS 320SYS NCD NCA 2 DVC EM ONYXWorks NCS NFS 3030 NFS 6...

Page 2: ...overlapping net work coverage RELEASING FEATURES Ten independent hazards Sophisticated cross zone three options Delay timer and Discharge timers adjustable Abort four options Low pressure CO2 listed VOICE FEATURES Integrates with FirstCommand Series See DN 60772 Telephone applications require NFC FFT HIGH EFFICIENCY OFFLINE SWITCHING 3 0 A POWER SUPPLY 6 0 A IN ALARM 120 VAC NFS 320 NFS 320C 240 V...

Page 3: ...ls 1 Low Chamber value 2 Maintenance Alert indicative of dust accumulation that is near but below the allowed limit 3 Maintenance Urgent indicative of dust accumulation above the allowed limit Sensitivity Adjust Nine sensitivity levels are provided for alarm detection These levels can be set manually or can change automat ically between day and night Nine levels of pre alarm sensitivity can also b...

Page 4: ...h speed Network Commu nications Modules Wire single mode fiber multi mode fiber and media conversion models are available See DN 60454 NCD As part of a standalone NFS 320SYS system the NCD can serve as Primary Display for the panel to provide control and status capabilities on displayless nodes On network systems the NCD connects to and requires a standard Network Communication Mod ule or High Spe...

Page 5: ...gent 135 F fixed thermal sensor FlashScan and CLIP Must be mounted to one of the bases listed below ULC FST 951A IV FST 951R White low profile intelligent rate of rise thermal sensor FlashScan only Must be mounted to one of the bases listed below ULC FST 951A FSP 951R IV Ivory low profile intelligent photoelectric sensor remote test capable FlashScan only ULC FSP 95RA IV for use with DNRA FSV 951 ...

Page 6: ... MB for systems using 100 AH batteries For a full list of required and optional equipment see DN 60688 NFS LBB Battery Box required for batteries larger than 26 AH NFS LBBR Same as above but red SEISKIT 320 B26 Seismic mounting kit Required for seismic certi fied applications with NFS 320 and BB 26 Includes battery bracket for two 26 AH batteries SEISKIT BB25 Seismic mounting kit for the BB 25 Inc...

Page 7: ... the useful life of the system s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity Therefore it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 27 C 60 80 F AGENCY LISTINGS AND APPROVALS The listings and approvals below apply to the basic NFS 32SYS control pane...

Reviews: