General 

The NFS-320SYS intelligent Fire Alarm Control Panel is part of the
ONYX

®

 Series of Fire Alarm Controls from NOTIFIER.

As a stand-alone small-to-large system, or as a large network, the
ONYX Series of products meet virtually every application require-
ment.

The modular design of the ONYX Series makes system planning
easier. The panel can be configured with just a few devices for small
building applications, or networked with many devices to protect a
large campus or a high-rise office block. Simply add additional
peripheral equipment to suit the application. Wireless fire protection
can be added with the SWIFT wireless gateway and devices.

NOTE: 

Unless called out with a version-specific “E” at the end of the part

number, “NFS-320SYS” refers to models NFS-320SYS and NFS-
320SYSE; similarly, “CPU-320SYS” refers to models CPU-320SYS and
CPU-320SYSE. 

ONYX® Series panels integrate with the Connected Life Safety Ser-
vices (CLSS) platform through the CLSS Gateway, providing
connectivity to central station, cloud, and mobile applications. 

(See

HON-62034.) 

This cloud-based functionality provides reliable pro-

tection and remote monitoring of the system, reduced manual data
entry, and reporting. 

Features

Certified for seismic applications when used with the appropriate
seismic mounting kit. 

Approved for Marine applications when used with listed compati-
ble equipment. 

See DN-60688.

One isolated intelligent Signaling Line Circuit (SLC) Class A, B,
or X.

Wireless fire protection using SWIFT Smart Wireless Integrated
Fire Technology. 

See DN-60820.

Up to 159 detectors and 159 modules per SLC; 318 devices max-
imum. 

Detectors can be any mix of photo, thermal, or multi-sensor;
wireless detectors are available for use with the FWSG(A). 

Modules include addressable pull stations, normally open con-
tact devices, two-wire smoke detectors, notification, or relay;
wireless modules are available for use with the FWSG(A). 

Standard 80-character display.

Network options:

High-speed network for up to 200 nodes (N16e/x, NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM,
ONYXWorks, NFS-3030, NFS-640, and NCA. 

Standard network for up to 103 nodes (N16e/x, NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM,
ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-
300/400, AFP-1010, and AM2020. Up to 54 nodes when DVC-
EM is used in network paging. 

6.0 A power supply with four Class A/B built-in Notification Appli-
ance Circuits (NAC). Selectable System Sensor, Wheelock, or
Gentex strobe synchronization.

Built-in Alarm, Trouble, Security, and Supervisory relays.

VeriFire

®

 Tools online or offline programming utility. Upload/

Download, save, store, check, compare, and simulate panel data-
bases. Upgrade panel firmware.

Autoprogramming and Walk Test reports.

Multiple central station communication options:

Standard UDACT

Internet

Internet/GSM

80-character remote annunciators (up to 32).

EIA-485 annunciators, including custom graphics.

Printer interface (80-column and 40-column printers).

History file with 800-event capacity in nonvolatile memory, plus
separate 200-event alarm-only file.

Alarm Verification selection per point, with automatic counter.

Presignal/Positive Alarm Sequence (PAS).

Silence inhibit and Auto Silence timer options.

NAC coding functions: 

March time. 

Temporal. 

California two-stage coding. 

Canadian two-stage. 

Strobe synchronization.

Optional cloud connectivity for remote off site monitoring through
CLSS (

see HON-62034)

Monitor multiple buildings through one off-campus central station,
and report through the CLSS Gateway

Optional remote programing through CLSS

Field-programmable on panel or on PC with VeriFire

®

 Tools pro-

gram check, compare, simulate.

Full QWERTY keypad.

Battery charger supports 18 – 200 AH batteries.

Non-alarm points for lower priority functions.

Remote ACK/Signal Silence/System Reset/Drill via monitor mod-
ules.

Automatic time control functions, with holiday exceptions.

Extensive, built-in transient protection.

Powerful Boolean logic equations.

Summary of Contents for Notifier NFS-320SYS

Page 1: ...detectors notification or relay wireless modules are available for use with the FWSG A Standard 80 character display Network options High speed network for up to 200 nodes N16e x NFS2 3030 NFS2 640 NFS 320 C NFS 320SYS NCD NCA 2 DVC EM ONYXWorks NFS 3030 NFS 640 and NCA Standard network for up to 103 nodes N16e x NFS2 3030 NFS2 640 NFS 320 C NFS 320SYS NCD NCA 2 DVC EM ONYXWorks NCS NFS 3030 NFS 6...

Page 2: ...overlapping net work coverage RELEASING FEATURES Ten independent hazards Sophisticated cross zone three options Delay timer and Discharge timers adjustable Abort four options Low pressure CO2 listed VOICE FEATURES Integrates with FirstCommand Series See DN 60772 Telephone applications require NFC FFT HIGH EFFICIENCY OFFLINE SWITCHING 3 0 A POWER SUPPLY 6 0 A IN ALARM 120 VAC NFS 320 NFS 320C 240 V...

Page 3: ...ls 1 Low Chamber value 2 Maintenance Alert indicative of dust accumulation that is near but below the allowed limit 3 Maintenance Urgent indicative of dust accumulation above the allowed limit Sensitivity Adjust Nine sensitivity levels are provided for alarm detection These levels can be set manually or can change automat ically between day and night Nine levels of pre alarm sensitivity can also b...

Page 4: ...h speed Network Commu nications Modules Wire single mode fiber multi mode fiber and media conversion models are available See DN 60454 NCD As part of a standalone NFS 320SYS system the NCD can serve as Primary Display for the panel to provide control and status capabilities on displayless nodes On network systems the NCD connects to and requires a standard Network Communication Mod ule or High Spe...

Page 5: ...gent 135 F fixed thermal sensor FlashScan and CLIP Must be mounted to one of the bases listed below ULC FST 951A IV FST 951R White low profile intelligent rate of rise thermal sensor FlashScan only Must be mounted to one of the bases listed below ULC FST 951A FSP 951R IV Ivory low profile intelligent photoelectric sensor remote test capable FlashScan only ULC FSP 95RA IV for use with DNRA FSV 951 ...

Page 6: ... MB for systems using 100 AH batteries For a full list of required and optional equipment see DN 60688 NFS LBB Battery Box required for batteries larger than 26 AH NFS LBBR Same as above but red SEISKIT 320 B26 Seismic mounting kit Required for seismic certi fied applications with NFS 320 and BB 26 Includes battery bracket for two 26 AH batteries SEISKIT BB25 Seismic mounting kit for the BB 25 Inc...

Page 7: ... the useful life of the system s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity Therefore it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 27 C 60 80 F AGENCY LISTINGS AND APPROVALS The listings and approvals below apply to the basic NFS 32SYS control pane...

Reviews: