Section 3 Configuration
3.1 Configuration Web Page
Configuration of the NFN-GW-EM-3 is via a web page running on the NFN-GW-EM-3. Supported web browsers are listed in
.
The following information applies to IP settings:
• Each NFN-GW-EM-3 is shipped with a default IP address of 192.168.1.2 and a default node number of 240.
• The computer used to configure the NFN-GW-EM-3 must be able to establish an IP connection to the gateway. Consult with a
network administrator if unsure how to make this connection.
• Connecting more than one NFN-GW-EM-3 prior to reconfiguring the IP address will result in an IP address conflict.
Refer to
Appendix A, "Gateway Settings"
for instructions on resetting and reviewing the IP settings of the NFN-GW-EM-3.
3.2 Configuring the NFN-GW-EM-3
3.2.1 Logging into the Web Page
Log into the NFN-GW-EM-3 as follows:
1.
Start the web browser.
2.
Navigate to the IP address of the
gateway
(default http://192.168.1.2)
.
3.
If a security warning appears, select the option to continue anyway. Refer to
for more information.
4.
Log into the web page:
a. If the password has already been established, enter the password and click
OK
.
b. If any of the following conditions is true, go to Step 5:
•
A new gateway from the factory.
•
An upgrade of a gateway from a previous version for which the password has not been set (i.e. still using
the default password).
•
After a factory reset of the gateway.
5.
To set a new password:
a. Enter the default password, 00000000 (eight zeros) and click
OK
. The Set Device Password dialog box
appears.
b. Reenter the default password.
c. Enter a new password.
d. Reenter the new password to confirm.
e. Click
OK
.