RS485 Serial connection 

 

The connection of LDC6000N with the control panel use serial line RS485. 

 

RS-485 line must be installed in “MULTI-POINT” configuration (daisy chain).  

 

Each peripheral must be programmed with an address between 1 

 16. (refer to TAB.1). 

 

 

“Multi-Point” configuration (Daisy Chain)  

 

Connect two wires to the RS485  

control panel terminal block 
(

LIN+

 and 

LIN-

 ) to the 

corresponding terminals of the 
first device on the line. 

Continue wiring from the first 

device to the next, and so on. 

Install EOL (120-150

,0.5W) on 

the terminal block on both 
control panel and last device of 
the line. 

Maximum length between control 

panel and last device 1,5 km. 

Use shielded cable with 

appropriate section type 
Belden 9574 or 9575

 

 
 
 

 

 

AM-2000 

13

EOL= 120 

12

EOL= 120 

23

22

LCD-6000N 

 

 

GND

+24V

LCD-6000N 

 

 
 
 

 

 

AM-4000 

17

EOL= 120 

16 

11

EOL= 120 

31

30

LCD-6000N 

1

2

 

 

GND

+24V

LCD-6000N 

 

 
 
 

 

 

AM-6000 

09

EOL= 120 

08

EOL= 120 

LCD-6000N

 

 

5

GND

+24V

CN

CN

LCD-6000N 

 

Typical wiring RS485 with 24Vdc power supply in common 

(Control panel user output voltage 24Vdc) 

 
 
 
 
 
 
 
 
 
 

Summary of Contents for Notifier LCD6000N

Page 1: ...LCD6000N LCD Remote panel Installation manual ...

Page 2: ...t panel controls 4 User interface description 5 Normal condition 5 Events from zone in alarm condition 6 Events from zone in fault condition 7 PROGRAMMING MENU 8 Address 8 Password 9 Buzzer volume 9 LED Test 9 LCD Test 9 RS485 Serial connection 10 Shield cable and earth connection 11 Topographic LCD6000N board 12 CN1 Terminal block 13 Environmental features 13 Power supply 13 ...

Page 3: ...d even happen at the worst time That s why it s essential to use only material that is indicated by NOTIFIER as compatible with its control panels In case of doubt check with NOTIFIER technical assistance This system and all its solid state components can be damaged by induced electrostatic discharges handle the boards picking them on borders and avoid to touch electronic components A good groundi...

Page 4: ...s time date and personalized messages from the AM Series control panel Using the function keys of the LCD6000N repeater can be successfully performed the following functions Buzzer tacitation Output tacitation Reset alarm and Lamp Test It also allows viewing of the events list on the control panel divided by Alarms Fault System fault Technical features Microprocessor based system LCD graphic 320 x...

Page 5: ...ntrol panel close to heat sources radiators heaters etc The panel is designed to be wall mounted through 4 self blocking nogs stone walls or self tapping screws pre built panels etc Screws diameter must be 5mm max We advice not to install the panel near heating sources radiators etc Fixing screws 5mm max Fix the incoming cable with a tie Plug in the cable into CN1 Front panel fixing screws ...

Page 6: ...ion This requires the level 2 password To access the level 2 password press key the entry window will be shown With arrow keys select first number than press to confirm Repeat this step to enter the entire password BUZZER TACITATION this key silence LCD6000N and control panel buzzer and enable the operator to RESET RESET by pressing this key you can cancel the memory of current alarms or fault poi...

Page 7: ... present In the presence of points or zone not included an exclamation is displayed In alarm condition the symbol Flame is displayed In fault condition the symbol Triangle is displayed Note The alarm state prevails in the event that the panel is alarm and fault condition simultaneously Date Time Counter areas in alarm Counter system fault Counter zone excluded Serial connection RS485 status In cas...

Page 8: ...ay the devices in a given area scroll through the list of zones until the selected zone is in the viewing area Use key to access the list of points in alarm of the selected zone With arrow keys it is possible to scroll the list of the devices in alarm Counter zone in alarm Date and time of the first event zone alarm First zone alarm Programmed text for the zone Last alarm zone Programmed text for ...

Page 9: ...e to scroll the list fault zone If there are several fault zone to display the faulty devices in a given area scroll through the list of zones until the selected zone is in the viewing area Use key to access the list of fault points of the selected zone With arrow keys it is possible to scroll the list of the devices in fault Fault zone Programmed text zone Faulty device D detector M module Progra...

Page 10: ...word level 3A press for a wile then the entering windows will displayed With arrow keys select first number than press to confirm Repeat this step to enter the entire password The following menu will displayed Where Address Select Address voice to assign peripheral number to LCD6000N Use arrow key to select device number and press list key to confirm 16 available device address for LCD6000N Use ar...

Page 11: ...2 3A LEVEL PASSWORD Press key for a wile to get 3A LEVEL password than entering window for the password entry will displayed With arrow keys select first number than press to confirm Repeat this step to enter the entire password Default password is 44444 Buzzer volume Selecting Buzzer volume with the arrow keys to scroll the list than list key to confirm it is possible to set buzzer volume for ala...

Page 12: ...minals of the first device on the line Continue wiring from the first device to the next and so on Install EOL 120 150 0 5W on the terminal block on both control panel and last device of the line Maximum length between control panel and last device 1 5 km Use shielded cable with appropriate section type Belden 9574 or 9575 AM 2000 13 EOL 120 12 7 EOL 120 23 22 LCD 6000N 1 2 3 4 5 GND 24V LCD 6000N...

Page 13: ...sis Typical wiring of the last device RS485 shield and earth wiring Connect two wires to the RS485 control panel terminal block LIN and LIN to the corresponding terminals of the first device on the line Continue wiring from the first device to the next and so on Install EOL 120 150 0 5W on the terminal block on both control panel and last device of the line Maximum length between control panel and...

Page 14: ...ALIA Doc M 183 1 LCD6000N ENG Rev A 2 LCD6000N_manu Topographic LDC6000N board Cables specifications Up to 1 200 mt 18 AWG Belden 9574 type Up to 1 500 mt 16 AWG Belden 9575 type 1 2 3 4 5 CN1 Terminal block CNT terminal block for front keypad Buzzer ...

Page 15: ...IN RS 485 Serial line 2 GND Power input 1 24Vdc TO BE USED IN CASE OF POWER NOT COMMON WITH THE CONTROL PANEL ENVIRONMENTAL FEATURES Operative temperature 5 C 40 C Humidity 10 93 without condensate Stock temperature 10 C 50 C Weight 0 54Kg Power supply Voltage range 10 30Vdc Current in normal condition without fault or alarms with display off 30mA Current in alarm condition with fault or alarms wi...

Page 16: ... M Tel Fax 055 289177 00118 Roma Via Del Casale Santarelli 51 Tel 06 7988021 Fax 06 79880250 E mail notifier roma notifier it 80143 Napoli Palazzo Prof Studi Centro Direzionale Isola E2 Scala B Piano 5 Tel 081 19493111 Fax 081 7879159 E mail notifier napoli notifier it 70125 Bari Via Delia Costituente 29 Tel 080 6180700 Fax 080 5648114 E mail notifier bari notifier it 95128 Catania Viale Alcide De...

Reviews: