Honeywell NOTIFIER FW-MM Installation And Maintenance Instructions Download Page 2

  

I56-4067-005 

  

 

©2021 Notifier. 7/27/2021 

MOUNTING

The FW-MM(A) mounts directly to an SMB500(-WH) electrical box. (See 
Figure 4.) To avoid interference with the wireless network metal elec-
trical boxes are NOT recommended. Non-metal surface mounted elec-
trical boxes (SMB500/SMB500-WH) are available from Notifier. If not 
using an SMB500(-WH), the minimum mounting opening dimensions for the 
FW-MM(A) are 4 in. X 3¾ in. x 1½ in. deep. 

NOTE: Do not attach the module to temporary structures such that the place-
ment could be altered.

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. This module is intended for power limited wiring only. FW-MM(A) 
must be within 3 feet of monitored device when using field wiring or 20 feet 
in non-metallic conduit. In Canada, wiring methods shall be in accordance 
with CSA C22.1 Safety Standard for Electrical Installations, Canadian Electri-
cal Code, Part 1, Section 32.

1.   Install module wiring in accor-

dance with the job drawings 
and appropriate wiring dia-
grams.

2.   Set the address on the module 

per job drawings.

3.   

Secure module to electrical 
box (supplied by installer), as 
shown in Figure 3.

C1096-00

C1097-00

FIGURE 4. MODULE MOUNTING

FIGURE 3. BATTERY COMPARTMENT

BATTERY
COMPARTMENT
DOOR

BATTERY
COMPARTMENT

C2002-00

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
WARNING: Do not make changes to the equipment. Changes or modifications not expressly approved by the manufacturer could void the user’s authority to operate the equipment.

FCC STATEMENT

IC STATEMENT

This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any 
interference, including interference that may cause undesired operation of the device.

RAPPORT D’IC

Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes: (1) l’appareil ne doit pas produire de 
brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.

INSTITUTO FEDERAL DE TELECOMUNICACIONES

This device utilizes the Honeywell915 rev A radio module and complies with IFETEL standard(s). IFT: RCPHOSW14-1983

Use of these products in combination with non-Honeywell products in a wireless mesh 
network, or to access, monitor or control devices in a wireless mesh nework via the inter-
net or another external wide area network, may require a separate license from Sipco, LLC. 

For more information, contact Sipco, LLC or Ipco, LLC at 8215 Roswell Rd., Building 900, 
Suite 950, Atlanta, GA 30350, or at www.sipocollc.com or www.intusiq.com.

LICENSING STATEMENT

FIGURE 5. TYPICAL MONITORING CONFIGURATION

               

WIRELESS 

MONITOR MODULE

ONLY ONE UL/ULC LISTED CONTACT 

CLOSURE MAY BE USED

POWER LIMITED

3.1 VDC MAX

3.9K EOL 

RESISTOR 

A2143-10

INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER’S 

INSTALLATION INSTRUCTIONS. WIRELESS MONITOR MODULE MUST BE 

WITHIN 3 FEET (1M) OF MONITORED DEVICE WHEN USING FIELD WIRING 

OR 20 FEET (6.1M) IN NON-METALLIC CONDUIT.

 

C1099GC-00

Notifier

®

 and SWIFT ® are registered trademarks of Honeywell International, Inc.