FROM PANEL OR
(+)
(-)
TO NEXT
(+)
(-)
DEVICE
(+)
(-)
(-)
(+)
3.9K EOL
RESISTOR
MODULE POLARITIES ARE
SHOWN IN ALARM
32 VDC MAX.
IS RECOMMENDED
BRANCH CIRCUITS
BREAK ALL WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
DO NOT LOOP WIRE AROUND TERMINALS.
(-)
(+)
TWISTED PAIR
SIGNAL LINE CIRCUIT (SLC)
PREVIOUS DEVICE
(-)
(+)
TELEPHONE CONSOLE
24 VOLTS DC POWER LIMITED
Relay Contact Rating:
24 VDC, 3 Amperes Maximum
TELEPHONE CONSOLE MUST
PROVIDE ITS OWN
WIRING SUPERVISION
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
FROM PANEL OR
(+)
(-)
TO NEXT
(+)
(-)
DEVICE
(+)
(-)
(-)
(+)
3.9K EOL
RESISTOR
MODULE POLARITIES ARE
SHOWN IN ALARM
CONNECT MODULES TO LISTED COMPATIBLE
32 VDC MAX.
IS RECOMMENDED
BRANCH CIRCUITS
BREAK ALL WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
DO NOT LOOP WIRE AROUND TERMINALS.
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
TWISTED PAIR
NOTIFIER CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
PREVIOUS DEVICE
(-)
(+)
(-)
(+)
TELEPHONE CONSOLE
24 VOLTS DC POWER LIMITED
Relay Contact Rating:
24 VDC, 3 Amperes Maximum
TELEPHONE CONSOLE MUST
PROVIDE ITS OWN
WIRING SUPERVISION
NO-460-017
2
I56-3533-000
©2008 Notifier
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
Figure 3. Typical circuit configuration, NFpA Style y:
Figure 4. Typical fault tolerant circuit configuration, NFpA Style Z: