FTM-1 Firephone Control Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS
BEFORE INSTALLINg
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
gENERAL DESCRIpTION
Firephone Control Modules are intended for use in intelligent, two-wire
systems, where the individual address of each module is selected using the
built-in rotary switches. This module is used to connect a remote firefighter
telephone to a centralized telephone console. A ringing sound is provided
at each off-hook handset until it is connected to the console. Wiring to indi-
vidual telephone jacks and handsets is supervised, and status is reported to
the panel as NORMAL, TROUBLE, or TELEPHONE. This module has two pairs
of output termination points available for fault-tolerant wiring, and includes a
panel-controlled LED indicator.
COMpATIBILITy REqUIREMENTS
To ensure proper operation, this module shall be connected to compatible
Notifier system control panels only (list available from Notifier).
MOUNTINg
This module mounts directly to 4
″
square electrical boxes (see Figure 2A).
The box must have a minimum depth of 2
1
/
8
″
. Flush mounted electrical boxes
(SMB500) are available.
WIRINg
NOTE: All wiring must conform to applicable local codes, ordinances and
regulations.
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams (Figures 3-4).
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in
Figure 2.
Figure 1. Controls and Indicators:
Figure 2. Module mounting:
C1059-00
SpECIFICATIONS
Normal Operating Voltage:
15 to 32 VDC
Maximum Current Draw:
7.5 mA (LED on)
Average Operating Current:
2.4mA (LED flashing)
SLC Wiring Resistance:
40 Ohms
Supervisory Wiring Resistance:
50 Ohms
Handset Offhook Resistance:
400 to 1500 Ohms
External Supply Voltage
Regulated 24VDC
(between Terminals T10 and T11)
Temperature Range:
32˚F to 120˚F (0˚C to 49˚C)
Humidity:
10% to 93% Noncondensing
Dimensions:
4.5
”
H × 4.275
”
W × 1.4
”
D (Mounts to a 4
”
square by 21/8
”
deep box.)
Accessories:
SMB500 Electrical Box; CB500 Barrier
C1070-02
I56-3533-000
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161