54
Notifier FirstCommand Series Manual —
P/N LS10001-001NF-E:H 1/8/2018
Programming
Main Menu - User Programming
NAC Options
NAC Type
The NAC circuit can be programmed to activate for specific applications. Select
Mass Notification
to turn on the NAC cir-
cuit only for a mass notification event,
Fire Evacuation
to turn on the NAC circuit only for a fire evacuation event,
Both
to turn on the
NAC circuit for both mass notification and fire evacuation events, or
Follow Input
to have the NAC follow the input from an external
source (connections to TB18). To use
Both,
the Unit Operation must be set to Combination. Refer to “Unit Operation” on page 53.
NAC Protocol
The programmer can select the notification appliance coding or strobe synchronization by selecting the corresponding
drop-down box. Select
System Sensor
for System Sensor synchronization,
Wheelock
, for Wheelock synchronization,
Gentex
for Gentex
synchronization, or
Steady
, for a continuous output with no coding.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit. Following
is a list of the strobes that have been tested with the NFC and the maximum number that can be connected to each NAC. Make sure that
the NAC maximum current is not exceeded.
Aux Power
Selects whether this power is
Constant
or
Resettable
use from TB17.
Speaker Volume Control NAC
If the Cooper Wheelock SP-SVC module is installed on TB23 of the main control board, allowing man-
ual volume setting for telephone paging and background music for a specific speaker or speaker zone, select
Enabled
.
Console Control
Console Priority
Priority can be assigned to the operator consoles so that the primary operator interface can always override the func-
tions at the local operator consoles or remote microphones. Select
POC->LOC->RM
for console priority. Selecting
Equal
for priority
allows users with access to the system on a a “first come, first served” basis.
Device Control Timeout
Enter the maximum amount of time (
30-300
seconds) that one of the devices (Primary Operator Console,
Local Operator Console, Remote Page Unit, or Remote Microphone) can remain in manual control of the NFC system.
Paging Timeout
Enter the maximum amount of time (
30-300
seconds) that the microphone’s PTT switch can be held.
Strobe Manufacturer
Maximum Number of Strobes
System Sensor
31
Wheelock
34
Gentex
26
Table 3.1 Maximum Number of Strobes by Manufacturer
Figure 3.4 NAC Options
n
a
c
o
p
ti
o
n
s
2
.j
p
g
Figure 3.5 Console Control
c
o
n
s
o
le
c
o
n
tr
o
l2
.j
p
g
Summary of Contents for Notifier FirstCommand Series
Page 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...
Page 86: ...Cut along dotted line ...
Page 88: ...Cut along dotted line ...
Page 92: ...92 Notes ...
Page 94: ...Cut along dotted line ...
Page 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...