Configuration and Programming
Programming the ACPS-610
Figure 3.8 PK-PPS: Synchronization
Synchronization
Select the protocol for synchronized outputs. Select
U
SE
E
XTERNAL
S
YNC
(UZC)
, when the
power supply will be connected (via TB1) to an external sync source.The external sync source
must be an FACP or power supply manufactured by the same manufacturer as the ACPS-610.
This is a non-supervised connection. This option will not be available if the UZC is already
configured to accept a coded signal (See “Coding Type” on page 33).
If no external sync is selected or there is a loss of signal, the ACPS-610 will generate an
internal sync pattern based upon the selection from the
I
NTERNAL
/B
ACKUP
S
YNC
dropdown
menu.
Silenceable
Select this option to silence all synchronized NACs when signal silence is activated. Use this
option with Gentex, System Sensor and Wheelock synchronized devices.
If any output address is configured as “non-silenceable” at the panel, the horns will mute, but
the strobes will remain active when silenced. If any output address is configured as
“silencable” at the panel, both horns and strobes will become inactive when silenced.
Making outputs silenceable adds an additional SLC address (see Section 3.1.1 on page 26).
This extra address is specifically for Signal Silence only. The Signal Silence SLC address
should be configured in the panel as a “silenceable output”, activated by CBE.
PK
-P
PS_
Syn
c
.j
pg
!
CAUTION: All Synchronized power supplies must have the same protocol!
FOR SYNCHRONIZED MASTER/SLAVE OPERATION: when a synchronized signal is supplied to
the UZC connections of TB1, the same protocol must also be programmed at the slave ACPS-610
as programmed at the master ACPS-610. This will ensure operation of all synchronized outputs of
the slave ACPS-610 should signal loss occur of the synchronization input (UZC connections) at TB1.