38
ACPS-610/E Manual —
P/N 53018:A1 07/31/2007
Configuration and Programming
Two Stage Alert/Evacuation (Canada Only)
The sequence of operations is as follows.
•
A general alarm activates FCM L1M1 (Type code APND).
•
L1M2, which has been programmed via CBE for OR(L1M1), activates (Type code FORC).
•
L1M3 (Type code NONA) physically monitors L1M2 contacts. L1M3 activates.
•
Software Zone Z200 (RZON) is programmed to activate after a 5 minute delay with the
equation Z200 = DEL(00.05.00(L1M3)). Z200 will clear (or never activate) if L1M1 is
acknowledged or if the system is reset before the 5 minute timer expires.
•
Software Zone Z201 (RZON) is programmed to activate after a 0 delay when Z200 activates.
Z201 will only clear from a system reset.
•
Alert Software Zone Z1 will activate when the Z1 equation is satisfied. ALERT = OR(Z1). A
CBE (Control-by-event) in this equation refers to any local CBE that is programmed into this
point. It could be a CBE that programs four cross-zoned detectors, for example.
•
EVAC Software Zone Z2 will activate when the Z2 equation is satisfied. EVAC = OR(Z2,
Z201). The CBE in this equation refers to any local CBE that is programmed into this point. It
could be a CBE that programs four or more cross-zoned detectors, for example.
Refer to the programming section of the FACP manual for more information on programming.