NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
105
Abort Switches
Releasing Applications
Each Cross Zone option and the conditions required to activate releasing zone ZR01 are shown in
the table below, according to the example in Figure B.8.
B.3.6 Using Type Codes for Releasing Zones
The control panel provides a set of Type Codes designed for releasing applications for inputs and
outputs. This section details how to program each of these Type Codes.
Type Codes designed for releasing zone
inputs
(SLC monitor modules).
Type Codes designed for releasing zone
outputs
(SLC control modules).
Cross Zone Selection
(Cross=)
Condition(s) Required to Activate the Releasing zone
Cross=
No
An alarm from any initiating device activates the releasing zone.
Cross=
Yes
An alarm from any two initiating devices activates the releasing zone.
Cross=
Zone
For example:
An alarm from two initiating devices mapped to different primary general zones, but
mapped to the same releasing zone.
• An alarm from L02D101 and L02D103
• An alarm from L02D102 and L02D104
• An alarm from L02D101 and L02D104
• An alarm from L02D102 and L02D103
The two detectors listed in each set above are each mapped to different primary
general zones, but both list ZR01 in their zone maps.
Cross=
Heat
Activation of heat detector L02D104 and one smoke detector (L02D101, L02D102,
or L02D103).
Type Code
What the Type Code does
Refer to
ABORT
SWITCH
(tracking)
Provides an abort function through a
monitor module (connected to a UL-listed
abort station) for a releasing zone.
“How to Program an Abort Switch” on
page 106
MAN
.
RELEASE
(latching)
Provides a manual release through a
monitor module (connected to a UL-listed
pull station) for a releasing zone.
“How to Program a Manual Release
Switch” on page 107
MAN
REL
DELAY
(latching)
Provides a manual release with a
10-second delay through a monitor module
(connected to a UL-listed pull station) for a
releasing zone.
“How to Program a Manual Release Delay
Switch” on page 108
SECOND
SHOT
(latching)
Provides a second manual release through
a monitor module (connected to a UL-listed
pull station) for a releasing zone.
“How to Program a Second Shot Switch”
on page 109
Type Code
What the Type Code does
Refer to
REL
END
BELL
Activates an NAC audio or visual device
when releasing circuits shut off.
“How to Program a Release End Bell
Circuit” on page 110
REL
CKT
ULC
Directs outputs to perform a release
function as required by ULC.
“How to Program a ULC Release Circuit”
on page 111
RELEASE
CKT
Directs outputs to perform a releasing
function.
“How to Program a Release Circuit” on
page 112
REL
.
FORM
C
Directs relay outputs to perform a releasing
function.
“How to Program a Release Form-C
Circuit” on page 113
REL
AUDIBLE
Activates audio or visual devices steady
when releasing starts.
“How to Program a Release Audible
Circuit” on page 114
INST
RELEASE
Activates non-releasing output (SLC
modules) with no delay time.