NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
107
Abort Switches
Releasing Applications
How to Program a Manual Release Switch
The following contains information needed to program a Manual Release switch for a monitor
module
.
Description
A monitor module—connected to a UL-listed manual station (such as the Notifier
NBG-12LRA)—used to monitor a pull station for the manual release of agents. A Manual Release
switch overrides all timers, such as Delay Time or a Soak Time. Multiple monitor modules can be
programmed with a
MAN
.
RELEASE
type code. They work like multiple conventional manual release
switches on a conventional zone.
Program
Select a monitor module for the manual release function. While programming this
module (refer to Section 3.4.2, “Module Point”, on page 51 for instructions),
1. Select the
MAN
.
RELEASE
type code.
2. Enter the number of the desired releasing zone into the module’s zone map. The releasing zone
must be fully programmed (refer to Section 3.4.4, “Releasing Zone”, on page 57).
Example
A programming example of a monitor module programmed as an manual release switch
for releasing zone ZR05.
Figure B.10 Monitor Module Configured as a Manual Release Switch
SYSTEM
NORMAL
SYSTEM
ACT IVATED
Detector
ZR05
NBG-12LRA station with Manual Release Lever
Monitor
Module
Type Code
MAN. RELEASE
SLC
output
module
SLC
output
module