Honeywell N05 Series Product Data Download Page 2

2

 

 
PRODUCT IDENTIFICATION SYSTEM 

 

C

-Electrical Motor 

 

N

-Fail Safe Function (Non-Spring Return) 

 

 

61

-24V Floating Control 

 

 

75

-24V Modulating Control 

 

 

05

-44 lb-in. (5 Nm) 

 

 

10

-88 lb-in. (10 Nm) 

 

 

A

-Standard Model 

 

 

 

1

-No Feedback 

 

 

 

2

-Voltage Feedback Signal 

 

 

 

0

-No Internal Auxiliary Switches 

 

 

 

2

-Two Internal Auxiliary Switches 

 

 

 

 

 

 

 

XX-

System Controlled Numbers 

 

 

 

 

 

 

 

C

 

N

 

75

 

10

 

A

 

2

 

 0  XX

 

 

 

 

BASIC FEATURES 

 

Fig. 1. Setting units and control elements 

Legend for Fig. 1: 

1) Universal shaft adapter 
2) Mechanical end limits (manually adjustable) 
3) Declutch button 
4) Function selection switch 
5) Removable access cover 
6) Anti-rotation bracket 

 

 

 

 

Contents of Package 

The delivery package includes the actuator, parts 1 through 6 
(see Fig. 1), plus two cable grommets and a spare cable 
grommet. 

RUN MODES 

The function selection switch (see Fig. 2) can be used to place 
the actuator into any one of two different modes: 

•   Service/Off; or 
•   the floating/2-position run mode (“Dir” for CCW-closing 

dampers or “Rev” for CW-closing dampers). 

•   the modulating run modle. 
 

Fig. 2.  Function selection switch 

Power-Off Behavior 

If power is removed, the shaft adapter remains in position. 

Service/Off 

If the function selection switch is set to the “Service/Off” position, 
then all rotary movement is cancelled, and all control signals are 
ignored, thus allowing the actuator to be manually operated 
safely.

 

Floating/2-Position Run Mode 

Without Feedback Signal 

If, however, the function selection switch has been set to one of 
the two floating/2-position control settings - but the actuator has 
not been wired for a feedback signal (see Fig. 12 and Fig. 13) - 
then as soon as operating power is applied, the shaft adapter will 
run according to the control signals applied. 

With Feedback Signal 

If the function selection switch has been set to one of the two 
floating/2-position control settings - and if the actuator has been 
wired for a feedback signal (see Fig. 12 and Fig. 13) - then as 
soon as operating power is applied, the shaft adapter will likewise 
run first completely counterclockwise and then completely 
clockwise (see also section “Adaption”), after which it will run 
according to the control signals applied.  

Modulating Run Mode 

If the function selection switch has been set to one of the four 
modulating control settings - and if the actuator is wired 
correspondingly (see Fig. 10) - then as soon as operating power 
is applied, the shaft adapter will run first completely 
counterclockwise and then completely clockwise (see also 
section “Adaption”), after which it will run according to the control 
signals applied. 

 

 

 

63-6233T 
CN0B-0545CH33 R0805 

N05,N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL 

Summary of Contents for N05 Series

Page 1: ...ge 24 Vac dc 15 20 50 60 Hz Nominal voltage 24 Vac dc 50 60 Hz All values stated hereinafter apply to operation under nominal voltage conditions Power consumption CN7505 5 VA 2 W CN7510 5 VA 2 W Control signal Modulating 0 2 10 Vdc Floating 2 Position 24 Vac dc Ambient limits Ambient operating limits 5 140 F 20 60 C Ambient storage limits 22 176 F 30 80 C Relative humidity 5 95 non condensing Safe...

Page 2: ...ent is cancelled and all control signals are ignored thus allowing the actuator to be manually operated safely Floating 2 Position Run Mode Without Feedback Signal If however the function selection switch has been set to one of the two floating 2 position control settings but the actuator has not been wired for a feedback signal see Fig 12 and Fig 13 then as soon as operating power is applied the ...

Page 3: ...rol signal at switch settings terminal 3 terminal 4 0 2 10V Dir Service Off Rev 10 0 2 V open open stops stops stops open 24 Vac dc CCW stops CW 24 Vac open CW stops CCW Table 2 Shaft adapter behavior in the 2 position mode control signal at switch settings terminal 3 terminal 4 0 2 10V Dir Service Off Rev 10 0 2 V 24 Vac open CW stops CCW 24 Vac 24 Vac dc CCW stops CW Table 3 Shaft adapter behavi...

Page 4: ...r dead band i e to more than the max control signal minus 0 24 V or drops down into the lower dead band i e to less than the min control signal plus 0 24 V after which the shaft adapter must then remain at the respective upper or lower mechanical end limit for at least 3 seconds However in this case the actuator will then recognize the position of only the respective upper or lower mechanical end ...

Page 5: ... single point mounting Mounting Instructions All information and steps are included in the Installation Instructions Product Literature No 62 0224 supplied with each actuator Mounting Position The actuators can be mounted in any position IP54 is dependent upon orientation see Fig 9 Choose a mounting position permitting easy access to cables and controls Fig 8 Mounting for IP54 NOTE Further in orde...

Page 6: ...to gain access to the terminal block s and perform wiring Fig 9 Access Cover Wiring Diagrams Fig 10 CN7505 CN7510 modulating mode Wiring Diagrams Fig 11 CN7505 CN7510 floating mode Fig 12 CN7505 CN7510 2 position mode Fig 2 End switches NOTE Both of the internal end switches must be connected to the same power source Table 4 and Table 5 summarize the information presented in the preceding wiring d...

Page 7: ... NOTE All cables connected to these terminals must be equipped with spark suppression Table 5 Internal end switches terminal type of switch S1 common lead for switches A and B S2 S3 change over switch A S1 S2 opens and S1 S3 closes when shaft adapter moves CW past 5 reverts to original state when shaft adapter moves CCW past 5 S5 S6 change over switch B S1 S5 opens and S1 S6 closes when shaft adap...

Page 8: ...ional Inc Honeywell Tianjin Limited 1985 Douglas Drive North 66 BaiHe Road TEDA Golden Valley MN 55422 Tianjin 300457 P R C Honeywell Printed in China on recycled paper containing at least 10 post consumer paper fibers N05 N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL ...

Reviews: