Honeywell MP909E Installation Instruction Manual Download Page 2

MP909E UL LISTED DAMPER ACTUATOR

95-6076

2

17

(430)

1-1/8 (30) CLEARANCE

1-1/8 (30) CLEARANCE

MP909E

1-1/2

(39)

1-1/2

(39)

6-7/8
(175)

5-3/4
(145)

AXLE

ROTATION TO

NORMAL

C8092

Fig 1. External Mounting Dimensions in Inches (Millimeters).

FACEPLATE

MOUNTING

BRACKET

C8209

90°

AXLE

ROTATION TO

NORMAL

MOUNTING HOLES

C8208

CRANKARM

CLEVIS PIN LOCATION ON
3.1-INCH STROKE OPERATORS 
(FACTORY INSTALLED) 

1-3/8(35)

REF.

1-5/8 INCH (41 MM) FOR 3.1 INCH STROKE
OPERATORS AND N.C. DAMPERS

1

1

Fig. 2. External Mounting Faceplate Positioning.

Fig. 3. External Installation.

5

Remove mounting screw from damper end of truss link.
Loosen screw between base and truss link. Remove
clevis pin from damper end of actuator pushrod.

6

Set actuator in place by hooking actuator mounting
clamp over bottom edge of damper frame.

7

Set damper to the normal (closed) position.

8

Insert clevis pin in drive ear hole marked P and the
pushrod hole nearest the actuator.

9

Connect truss link to damper and tighten both truss link
screws.

J

Tighten damper mounting screws.

K

Go to PIPING section.

Summary of Contents for MP909E

Page 1: ... pressure limits 15 psi minimum 25 psi maximum Tools needed 1 7 16 inch box end wrench 2 1 8 inch Allen wrench 3 Squeeze bulb INSTALLATION External Mounting 1 For external mounting dimensions see Figure 1 2 Check faceplate position Fig 2 Adjust faceplate position if necessary 3 Determine the damper drive axle direction of rotation to the normal position position with 0 psi applied to actuator 4 Ro...

Page 2: ... 1 INCH STROKE OPERATORS AND N C DAMPERS 1 1 Fig 2 External Mounting Faceplate Positioning Fig 3 External Installation 5 Remove mounting screw from damper end of truss link Loosen screw between base and truss link Remove clevis pin from damper end of actuator pushrod 6 Set actuator in place by hooking actuator mounting clamp over bottom edge of damper frame 7 Set damper to the normal closed positi...

Page 3: ...Mounted Normally Closed Mounting Dimensions in Inches Millimeters 3 8 10 CLEARANCE 17 430 EDGE OF DAMPER 6 3 8 160 C8210 FACEPLATE PARALLEL TO BACK EDGE OF MOUNTING BRACKET C8212 TRUSS LINK TRUSS LINK MOUNTING SCREW 1 1 FACEPLATE PIVOT PLATE PUSHROD 1 13 32 INCH 36 MM REF DAMPER DRIVE EAR E HOLE CLEVIS PIN P HOLE DAMPER MOUNTING CLAMP SHIPPING STOP SETSCREWS MOUNTING BRACKET PUSHROD DAMPER DRIVE E...

Page 4: ...er drive ear with clevis pin J Tighten set screws on mounting clamp K Connect truss link to damper and tighten both truss link screws Truss link must be bent slightly 17 430 EDGE OF DAMPER 6 1 2 165 C8213 MP909E Fig 7 Internal Mounting Normally Open Dimensions in Inches Millimeters C8214 1 1 REFERENCE DIMENSIONS 4 INCH STROKE FACTORY SET 3 3 16 INCH 81 MM CLEVIS PIN C CLEVIS PIN B FACTORY INSTALLE...

Page 5: ...E BRASS FERRULE WITH RED FERRULE CCT1574 NOTE ORIENTATION REPLACE BRASS FERRULE 1 4 IN BARBED FITTING ACTUATOR C8217 TO CONTROLLER NUT NUT 1 4 IN COPPER TUBING Fig 10 Transition Piping for 1 4 Inch Barbed Fitting to 1 4 Inch Copper Tubing C8215 DAMPER FRAME DUCT FLOOR 1 4 IN COPPER TUBING MP909E ACTUATOR Fig 11 Routing Copper Tubing Near Trunnion Pivot Multiple Actuators Multiple actuators must be...

Page 6: ...u Control Your World Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 95 6076 1 96 Printed in U S A Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 ...