SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS
63-2188—4
8
Fig. 6. Series 61 motor wiring.
Fig. 7. Series 62 motor wiring.
Fig. 8. Connections to R927C or R9107A Relay.
NOTE: Vibration does not affect Modutrol IV Motor
performance (as it did in earlier Modutrol Motors).
When replacing a motor that was connected to an
R927C or R9107A Relay, Honeywell recommends
performing a retrofit to remove the relay and the old
motor. Replace both with one Series 90 Modutrol IV
motor (that is, do not replace the relay).
Fig. 9. Auxiliary switch schematic.
SETTINGS AND ADJUSTMENTS
Adjustable Stroke
On adjustable stroke motors, stroke is field-adjustable
between 90° and 160°.
• The mechanical adjustment (cams) establishes the fully
open (clockwise, as viewed from the power end) and fully
closed positions of the motor shaft.
• The electrical adjustment (trim potentiometer) matches the
feedback resistance change to the motor stroke.
• TRADELINE® motors are shipped with stroke set at 160°.
CAUTION
Careless Installation Hazard.
Use of excessive force while adjusting cams
damages the motor.
To avoid damaging motor end switches, set cams by
moving only the screwdriver top.
CAUTION
Equipment Damage Hazard.
Can damage the motor beyond repair.
Never turn the motor shaft by hand or with a wrench.
Forcibly turning the motor shaft damages the gear
train and stroke limit contacts.
Before Setting Stroke
1.
Remove the top cover from the motor.
2.
Disconnect the controller from the motor.
3.
For models with an internal transformer (line voltage
motors), ensure that power (and nothing else) remains
connected to the motor.
IMPORTANT
Detach linkage from motor before adjusting stroke.
R
B
W
R
W
B
T2
T1
L1
(HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
TRANSFORMER MAY BE INTERNAL OR EXTERNAL
TO MOTOR.
M17095
SERIES 60
CONTROLLER
SERIES 61
MOTOR
1
2
1
2
R
B
W
R
1
2
T
G
Y
4
3
L1
(HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
TRANSFORMER MAY BE INTERNAL OR EXTERNAL
TO MOTOR.
FEEDBACK POTENTIOMETER.
M17096
SERIES 60
CONTROLLER
SERIES 62
MOTOR
1
2
3
1
2
3
W
R
B
G
Y
T
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
CONNECTION REQUIRED ONLY FOR SPRING RETURN MOTORS.
M17098
SERIES 90
CONTROLLER
R927C OR R9107A RELAY
160 STROKE SERIES 62 MOTOR
Q181A
2
1
T
1
2
2
L1
(HOT)
L2
1
R
W
Y
T
G
2
B
R
W
B
1
4
3
BLUE LEAD
YELLOW LEAD
RED LEAD
USE NEC CLASS 1 WIRING UNLESS POWER SUPPLY
MEETS CLASS 2 REQUIREMENTS. TAPE UNUSED LEADS.
ENSURE THE CURRENT DRAW OF THE EXTERNAL CIRCUIT
IS LESS THAN SWITCH CONTACT RATING.
ON TWO-SWITCH MOTORS, SECOND SWITCH HAS BLACK
LEADS WITH BLUE, YELLOW, AND RED TRACERS.
SOME AUXILIARY SWITCH ASSEMBLIES INCLUDE ONLY
RED AND YELLOW LEADS. SOME OTHERS DO NOT INCLUDE
THE YELLOW LEAD.
M17099
1
1
1
2
2
2
2
3
3