SERIES 41 AND 81 MODUTROL IV™ MOTORS

63-2187—3

8

Setting Stroke (Fig. 11)

CAUTION

Motor Damage Hazard.

Pressing screwdriver against sides of cam slots or 

use of excessive force can damage the cams.

Set cams by moving top of screwdriver only.

1.

Drive the motor to its fully open position by applying 

24 Vac across terminals T1 and T2.

2.

Insert 1/8 in. screwdriver blade into brown cam slot and 

move top of screwdriver handle clockwise, to the right, 

(allowing motor to reposition after each adjustment) until 

motor reaches desired position.

NOTE: Each cam click is approximately a 2° rotation.

3.

If motor turns beyond desired position, 

do not move 

the cam

:

a. Allow the motor to spring return fully closed by 

disconnecting power.

b. Move the cam back to the left (counterclockwise).

c. Repeat steps 1, 2 and 3.

4.

Replace the motor cover.

Fig. 11. Stroke adjustments.

Auxiliary Switches

The auxiliary switches are spdt switches that are actuated by 

adjustable cams. The cams are factory-mounted on the motor 

shaft at the power end of the motor. The cam settings 

determine the point in motor shaft rotation at which the 

auxiliary equipment will be switched on or off. These cams 

can be set to actuate the switches at any angle within the 

motor stroke.

NOTE: For auxiliary switch wiring, see Fig. 12.

With a 1° differential, the N.C. switch contacts make and the 

N.O. switch contacts break on a counterclockwise (closed) 

rotation. If a 10° differential is chosen, the operation is 

reversed, the N.O. switch contacts make and the N.C. switch 

contacts open on a counterclockwise (closed) rotation.

NOTE: When the slow-rise portion of the cam is used, the 

switching differential is approximately 10° of rotation. 

When the fast-rise portion of the cam is used, the 

switching differential is approximately 1° of rotation. 

Do not use the fast rise portion of the cam if fast 

cycling of auxiliary equipment is undesirable.

Switching action is different depending on whether 1° or 10° 

differential is chosen. See Table 3.

Fig. 12. Auxiliary switch schematic.

WARNING

Fire or Explosion Hazard.

Incorrect auxiliary switch wiring can allow the 

burner to come on at high fire causing severe 

injury or death.

Check auxiliary switch wiring and cam adjustment 

before turning on the system.

Watch controlled equipment through a complete cycle.

Shut the system down immediately if switches do not 

sequence the equipment correctly.

Auxiliary Switch Adjustment

Adjustable cams actuate the auxiliary switches. These cams 

can be set to actuate the switches at any angle within the 

stroke of the motor. Select switch differential of 1° or 10°.

OUTER STROKE

ADJUST CAM

OUTER STROKE ADJUST CAM IS ONLY 

PRESENT ON HIGH TORQUE MOTORS.

M17100

POWER END

OF MOTOR

INNER STROKE

ADJUST CAM

AUXILIARY 

SWITCH CAMS 

MOVE SCREWDRIVER AT 

TOP ONLY TO ADJUST CAM.

1/8 INCH 

STRAIGHT-BLADE 

SCREWDRIVER

CAM

1

2

1

2

TORQUE

NO. OF

CAMS

CAM

COLOR

HIGH

LOW

2

1

YELLOW

BROWN

BLUE LEAD

YELLOW LEAD

RED LEAD

USE NEC CLASS 1 WIRING UNLESS POWER SUPPLY
MEETS CLASS 2 REQUIREMENTS.  TAPE UNUSED LEADS.  
ENSURE THE CURRENT DRAW OF THE EXTERNAL CIRCUIT 
IS LESS THAN SWITCH CONTACT RATING.

ON TWO-SWITCH MOTORS, SECOND SWITCH HAS BLACK
LEADS WITH BLUE, YELLOW, AND RED TRACERS.

SOME AUXILIARY SWITCH ASSEMBLIES INCLUDE ONLY
RED AND YELLOW LEADS. SOME OTHERS DO NOT INCLUDE 
THE YELLOW LEAD.

M17099

1

1

1

2

2

2

2

3

3

Summary of Contents for Modutrol IV 41 Series

Page 1: ...d long life Wiring box provides NEMA 3 weather protection Motor operates from 24 Vac Models are available with factory installed transformer or an internal transformer can be field added Quick connect terminals are standard screw terminal adapter is available Adapter bracket for matching shaft height of older motors is standard with TRADELINE motors TRADELINE motors have field adjustable stroke 90...

Page 2: ...lude auxiliary switch cams These cams cannot be field added Modutrol IV Order Number Guide See Table 1 Dimensions See Fig 1 Crankshaft 3 8 in 9 5 mm square Electrical Ratings See Table 2 Controller Type Two wire on off switching action Auxiliary Switch Ratings See Table 3 Table 1 Series 41 and Series 81 Modutrol IV Order Number Guide a Electrically normally closed Shaft rotates clockwise viewed fr...

Page 3: ...l Auxiliary Switch Kit can be field installed on TRADELINE models One 220736A and Two 220736B switch kits available 220738A Adapter Bracket raises motor shaft height by 19 mm to match that of previous Modutrol Motor models 220741A Screw Terminal Adapter converts the standard quick connect terminals to screw terminals 221455A Infinitely Adjustable Crank Arm approximately 0 75 in shorter than the 40...

Page 4: ... suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect all power supplies before installation Motors with auxiliary switches can have more than one discon...

Page 5: ...ded clearance to allow Crank arm rotation through the downward position Sufficient damper linkage to reach the motor shaft All valve linkages except the Q5001 NOTE When the bracket is not used in a replacement application the damper linkage can require adjustment for the new shaft position To mount the motor with the bracket 1 Mount the bracket to the equipment with existing or standard bolts 2 Us...

Page 6: ...er Bracket with the Q100 Linkage in all valve applications The 220738A Adapter Bracket is not required with the Q5001 Valve Linkage see Fig 4 Fig 4 Mounting the motor on a Q5001 valve linkage Wiring CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect all power supplies before installation Motors with auxiliary switches can have more tha...

Page 7: ...e motor shaft see Fig 2 TRADELINE motors are factory set for 160 IMPORTANT Detach linkage from motor before adjusting stroke Instructions are for normally closed models Reverse for normally open Before Setting Stroke 1 Remove top cover from motor 2 Disconnect controller from motor MOTOR 1 1 M806A THERMOSTAT LIMIT CONTROL POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED MOT...

Page 8: ...tation NOTE When the slow rise portion of the cam is used the switching differential is approximately 10 of rotation When the fast rise portion of the cam is used the switching differential is approximately 1 of rotation Do not use the fast rise portion of the cam if fast cycling of auxiliary equipment is undesirable Switching action is different depending on whether 1 or 10 differential is chosen...

Page 9: ...ner cam actuates the right switch and the outer cam actuates the left switch viewed from the power end Refer to Fig 11 Each division on the cam represents 15 of motor rotation 1 Turn off the power and remove the wiring box cover 2 Determine the amount of shaft rotation in degrees desired before the switch is to be energized 3 Note the cam slot positions 4 With a screwdriver rotate the cam to the d...

Page 10: ... on the damper crank arm is properly placed to give the required amount of travel 2 Energize the motor and run it to the end of its stroke Check the damper linkage while the motor is running to see that there are no loose or binding connections 3 If the motor does not run check the control circuit for an open or short the presence of power and voltage at the motor Voltage at the motor must be at l...

Page 11: ... for fluid pressure in excess of the close off rating 5 Replace the linkage cover REPLACEMENT Damper Application 1 Turn off power and remove wiring from the old motor 2 Remove crank arm from the old motor shaft and remove the old motor 3 Check to determine whether or not the mounting bracket is needed If the linkage can reach the new motor lower shaft position and the crank arm has clearance for t...

Page 12: ...Europe S A Honeywell Latin American Honeywell Honeywell Limited Honeywell Limitée Room 3213 3225 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Sun Hung Kai Centre 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario No 30 Harbour Road Belgium Suite 200 M1V 4Z9 Wanchai Sunrise FL 33325 Hong Kong ...

Reviews: