S7810M MODBUS™ MODULE
65-0249—4
8
Table 12. ModBus™ R7999 Register Assignments.
Address
(hex)
Register
(dec)
Parameter Name
Bytes
Notes
009F
40160
R7999 Message Counter
Format—U16
Bits 0-2 = The Buffer Index of the oldest information from the R7999.
(Incremented by the BC status message once a second.)
Bits 0-15 = A counter synchronized with R7999 messages.
00A0-
00A5
40161-
40166
R7999 buffer # 0
0-11
These buffers store an 8-second history of status data from the
R7999. The oldest buffer is indicated by register 40160, bits 0-2. This
scheme forms a circular buffer of information. A buffer will contain all
zeros if the S7810M received bad data for the buffer time slot. See
Table 25 for interpretation of bytes 0-11.
00A6-
00AB
40167-
40172
R7999 buffer # 1
0-11
00AC-
00B1
40173-
40178
R7999 buffer # 2
0-11
00B2-
00B7
40179-
40184
R7999 buffer # 3
0-11
00B8-
00BD
40209-
40220
R7999 buffer # 4
0-11
00BE-
00C3
40221-
40232
R7999 buffer # 5
0-11
00C4-
00C9
40233-
40244
R7999 buffer # 6
0-11
00CA-
00CF
40245-
40256
R7999 buffer # 7
0-11
Table 13. ModBus™ R7999 Register Assignments.
Address
(hex)
Register
(dec)
Parameter Name
Format
Notes
00D0-
015F
40209-
40352
R7999 Profile
See Table 23.
0160
40353
Fuel 1 closed endpoint
U16
0-4095
0161
40354
Fuel 1 open endpoint
U16
0-4095
0162
40355
Fuel 2 closed endpoint
U16
0-4095
0163
40356
Fuel 2 open endpoint
U16
0-4095
0164
40357
Inactive motor position
U16
0-4095
0165
40358
Registers 40353-40357 are current
U16
0-1
0166
40359
Air closed endpoint position
U16
0-4095
0167
40360
Air open endpoint position
U16
0-4095
0168
40361
FGR closed endpoint position
U16
0-4095
0169
40362
FGR open endpoint position
U16
0-4095
016A
40363
Unused
U16
016B
40364
Registers 40359-40363 are current
U16
0-1
016C-
018F
40365-
40400
R7999 Fault Information
Ref. Table 24.
0190
40401
Air Total Resistance
U16
0-4095. Air actuator feedback pot resistance.
0191
40402
Fuel 1 Total Resistance
U16
0-4095. Fuel 1 actuator feedback pot resistance.
0192
40403
Fuel 2 Total Resistance
U16
0-4095. Fuel 2 actuator feedback pot resistance.
0193
40404
FGR Total Resistance
U16
0-4095. FGR actuator feedback pot resistance.
0194
40405
Air Resistance Change
U16
0-4095. Bit 15 is a sign flag. 1 = negative, 0 = positive.
0195
40406
Registers 40401-40405 are current
U16
0-1
0196
40407
Fuel 1 Resistance Change
U16
0-4095. Bit 15 is a sign flag. 1 = negative, 0 = positive.
0197
40408
Fuel 2 Resistance Change
U16
0-4095. Bit 15 is a sign flag. 1 = negative, 0 = positive.
0198
40409
FGR Resistance Change
U16
0-4095. Bit 15 is a sign flag. 1 = negative, 0 = positive.
0199
40410-
40411
LCO Cycle Count
U32
0-1,000,000
019B
40412
Registers 40407-40411 are current
U16
0-1
019C
40413
Air Purge Preset Position
U16
0-4095
019D
40414
Fuel Purge Preset Position
U16
0-4095