
S7810M MODBUS™ MODULE
7
65-0249—07
a
Remote Reset command not accepted by S7810M1029.
0067
40104
Valve Proving Mode
R
U16
0 = Valve Proving is not enabled
1 = Enabled before Run
2 = Enabled after Run
3 = Enabled before and after Run
4 = Enabled split half before and half after Run
0068
40105
Valve Proving option
R
U16
1 = Uncommissioned
2 = Commissioned
0069
40106
Valve Proving time
R
U16
Seconds
0066-
007E
40103-
40127
Unused
007F
40128
BC Remote Command
R/W
U16
Only one bit in the LSByte must be set, with the exception of bit 15:
Bit 0 = Revert to autonomous operation.
Bit 1 = Don’t fire, remain off.
Bit 2 = Go to Hi Fire during Run.
Bit 3 = Go to Lo Fire during Run.
Bit 4 = Remote reset.
a
Bits 5-7 must be 0.
Bits 8-14 are ignored.
Bit 15: Copied to the control status register. The remote
control status register can be used to verify operation of the
command.
NOTE: Bits 1-3 must be refreshed at least every 120 sec-
onds, but not more than once a second, for the
burner control to remain in the commanded state.
Table 10. ModBus™ Register Assignments. (Continued)
Address
(hex)
Register
(dec)
Parameter Name
Read/
Write Format
Notes
Table 11. ModBus™ R7999 Register Assignments.
Address
(hex)
Register
(dec)
Parameter Name
Format
Notes
0080
40129
R7999 reserved
U16
Not used—always zero.
0081
40130
R7999 program mode
U16
0—Initiate State.
1—Normal Operation.
2—Alarm Initiate State.
3—Lockout.
4—Not Configured.
5—Factory Test.
6—Low Voltage.
7—Commissioning.
8—Reset.
0082
40131
R7999 fault code
U16
See Table 26.
0083
40132
R7999 operational
status
U16
00—Standby Hold.
01—Standby Stop Position.
02—Standby Main Valve.
03—Standby Low Fire Main Valve.
04—Standby Purge.
05—Fault 1.
06—Standby Hi Fire Main Valve.
07—Fault 2.
08—Processing Demand.
09—Light Off.
10—Modulate.
11—Light Off Low Fire Main Valve.
12—Purge.
13—Fault 3.
14—Purge Main Valve.
15—Fault 4.
16—Initialize.
17—Post Purge.