background image

INSTALLATION INSTRUCTIONS

31-00150EF-03

MN6105VAV 5 Nm VAV Actuator

NON-SPRING RETURN DIRECT-COUPLED 
DAMPER ACTUATOR FOR FLOATING CONTROL

GENERAL

Replacement actuator, only for use with Spyder and 
Stryker controllers with integral actuators.

This non-spring return direct-coupled actuator provides 
floating control of VAV units.

It provides reliable control for air damper applications with 
up to 10 sq ft (0.9 sq m) / 44 lb-in. (5 Nm) (seal-less 
damper blades; air friction-dependent).

FEATURES

• Declutch for manual adjustment.

• Adjustable mechanical end limits.

• Mountable in any orientation.

SPECIFICATIONS

Supply voltage:

MN6105: 24 Vac -15%/+20%, 50/60 Hz.

Nominal voltage:

MN6105: 24 Vac, 50/60 Hz.

All values stated herein after apply to operation under 
nominal voltage conditions.

Power consumption:

MN6105: 5 VA / 2 W.

Ambient limits:

Ambient operating limits: -5...+122° F (-20...+50° C).
Ambient storage limits: -22...+176° F (-30...+80° C).
Relative humidity: 5...95%, non-condensing.

Lifetime:

Full strokes: 60000.
Repositions: 1.5 million.

Mounting:

Round damper shaft: 3/8…1/2 in. (9.5...12.7 mm).
Square damper shaft: 1/4…1/2 in. (6.4...12.7 mm);

45° steps.

Shaft length: min. 1-5/8 in. (41.3 mm).

Torque rating: 

44 lb-in. (5 Nm).

Runtime for 90°:

MN6105: 90 sec (60 Hz Vac).

Rotation stroke: 

95° + 3°.

Approvals: 

cULus, CE

UL listing categorization:

Action: Type 1 Operating Control 
Pollution degree: 2 
Impulse voltage: 330 V
Impedance protected motor

INSTALLATION

Some Spyder and Stryker controllers include a direct-
coupled actuator with declutch mechanism, which is 
shipped hard-wired to the controller.

The actuator mounts directly onto the VAV box damper 
shaft and has up to 44 lb-in. (5 Nm) torque, 90-degree 
stroke, and 90 second timing at 60 Hz. The actuator is 

Summary of Contents for MN6105VAV

Page 1: ...er nominal voltage conditions Power consumption MN6105 5 VA 2 W Ambient limits Ambient operating limits 5 122 F 20 50 C Ambient storage limits 22 176 F 30 80 C Relative humidity 5 95 non condensing Lifetime Full strokes 60000 Repositions 1 5 million Mounting Round damper shaft 3 8 1 2 in 9 5 12 7 mm Square damper shaft 1 4 1 2 in 6 4 12 7 mm 45 steps Shaft length min 1 5 8 in 41 3 mm Torque rating...

Page 2: ...ws set to 95 degrees of rota tion Adjust the two set screws closer together to reduce the rotation travel Each hash mark indicator on the bracket represents approxi mately 6 5 of rotation per side 2 The declutch button when pressed allows you to rotate the universal shaft adapter see Fig 1 IMPORTANT Determine the damper rotation and opening angle prior to installation See Fig 2 Fig 1 Series 60 Flo...

Page 3: ...chanical end limit set screws to provide the desired amount of rotation Adjust the two set screws closer together to reduce the rotation travel c Tighten the two mechanical end limit screws Phillips 2 screwdriver 26 5 31 lb in 3 0 3 5 Nm torque d Using the declutch button rotate the universal shaft adapter fully clockwise e Mount the actuator to the VAV damper box and shaft f Tighten the two bolts...

Page 4: ...t any liability cost or damages including attorneys fees arising out of or resulting from any modification to the literature by you Panel Mounting The controller enclosure is constructed of a plastic base plate and a plastic factory snap on cover NOTE The controller is designed so that the cover does not need to be removed from the base plate for either mounting or wiring The controller mounts usi...

Page 5: ... 60 Hz Toutes les valeurs du présent document s appliquent à une utilisation à tension nominale normale Consommation électrique MN6105 5 VA 2 W Plages d utilisation Plage de températures de fonctionnement 20 à 50 C 5 à 122 F Plage de températures d entreposage 30 à 80 C 22 à 176 F Humidité relative 5 à 95 sans condensation Durée de vie Courses complètes 60000 Repositionnements 1 5 million Montage ...

Page 6: ...ossède une course rotationnelle totale de 95 voir la figure 1 REMARQUES 1 Le servomoteur est livré avec les vis de réglage de butée mécanique de fin de course réglées à une rotation de 95 Réglez les deux vis plus près l une de l autre pour réduire la course de rotation Chaque indicateur hachuré sur le support correspond à environ 6 5 de rotation de chaque côté 2 Vous pouvez tourner l adaptateur d ...

Page 7: ...et à la main rotation horaire b Le servomoteur est livré avec les vis de réglage de butée mécanique de fin de course réglées à une rotation de 95 Réglez les deux vis de réglage de butée mécanique de fin de course pour obtenir le degré de rotation voulu Réglez les deux vis plus près l une de l autre pour réduire la course de rotation c Serrez les deux vis de butée mécanique de fin de course tournev...

Page 8: ...ts qui s ouvrent en sens antihoraire Le servomoteur est livré configuré pour une ouver ture dans le sens horaire ce qui s applique au sens de rotation du volet des étapes 1 et 2 ci dessus Si l arbre de volet tourne en sens antihoraire pour ouvrir le volet vous devez modifier le logiciel du régulateur et régler la rotation à Inverser pour ouvrir ce qui s applique au sens de rotation du volet des ét...