Honeywell MN6105A1011 Manual Download Page 8

VRN PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

38-00032—01

8

MVN Actuator

APPLICATION

MVN 3Nm (27 lb-in.) Control Valve Actuator is used with 
the VRN2 Pressure Independent Control Valves to control 
hot and chilled water with glycol solutions up to 50% in 
heating, ventilating, and air conditioning (HVAC) systems 
to provide two-position or modulating functions. 

FEATURES 

• Non-spring Return

• Floating and modulating

• Space saving, click-on installation – no tool required

• Extendable position indicator for easy commissioning

• Available with or without cable

• Compatible with control ball valves from 1/2 to 1-1/4 

inches.

• Actuator can be mounted on the valve in any of four 

positions.

Fig. 3. Dimensions; see Table 5 on page 6.

SPECIFICATIONS

Actuator Type: 

 Valve

Rotational Stroke:  

90° ±3°.

Fail Safe Mode: 

 Non-spring return, Fail in place

Torque:  27 lb-in. (3 Nm). 

 

 External Auxiliary Switches Available: 

 No

Supply Voltage: 

 24 Vac +20%, -15%, 24 Vdc

Power Consumption: 

 5 VA- Modulating, 1.5 VA - Floating, 

6 VA - Fast Acting SPDT

Environmental Rating: 

 NEMA2

Frequency: 

 50 Hz; 60 Hz

Mounting: 

 Click-on installation – no tool required

Noise Rating at 1m (Maximum): 

 35 dB(A) max at 1 m 

[50 dB(A) for MVN643].

Materials: 

 Plenum rated plastic housing

Operating Humidity Range (% RH): 

 

5 to 95% RH, non-condensing

Ambient Temperature Range: 

 

-4°F to 131°F (-20°C to 55°C)

Storage Temperature Range:  

-40°F to 176°F (-40°C to 80°C) 

Weight: 

 0.6 lb. (0.27 kg)

Dimensions: 

 See Fig. 1 and Table 5.

Timing: 

 90 sec. (+/-10%) for MVN613 and MVN713; 

30 sec. (+/-10%) for MVN643

Electrical Connections: 

 Field wiring 18 to 20 AWG to 

screw terminals, located under the removable access 
cover.

Humidity Ratings: 

 5% to 95% RH non-condensing.

Design Life (at Rated Voltage): 

60,000 cycles; 1 cycle = 0°…90°…0°

Cable Specification: 

18 AWG, Plenum Rated, 300 V, 10 A, 3 ft. length from end of 

access cover.

Environmental Protection Ratings: 

 IP40.

Approvals: 

UL/cUL
UL60730

To order actuator with accessories order actuator part 

accessory. For example: MVN61 C1

E

B

CLEARANCE ABOVE ACTUATOR 3/4 (19)

G

M34969

MVN WITH 2-WAY BALL VALVE

Table 7. Actuators and Accessories

Actuator

Description

Accessory

MVN613A0000

Floating control ball valve actuator

C1- 1 meter 

cable

MVN643A0000

Fast acting SPDT contol ball valve actuator

MVN713A0000

Modulating control ball valve actuator

Summary of Contents for MN6105A1011

Page 1: ...perform better than reverse return piping designs without the extra materials these systems need Pressure independent control requires less flow enabling use of smaller piping pumps and chillers FEATURES Sizes from 1 2 to 3 in with internal female NPT connections Controls hot or chilled water with up to 50 glycol Regulated flow rates available from 1 to 95 gpm Differential pressure regulator for c...

Page 2: ...valve straight through flow full port with patented flow control insert Pipe Size 1 2 to 3 inches with female NPT pipe fittings Body Pressure Rating maximum 360 psi 2500 kPa at 250 F 121 C Controlled Medium Water or Glycol solutions up to 50 Not suitable for combustible gases oil or steam Medium Temperature Range 22 to 250 F 30 to 121 C Maximum Differential Pressure See Table 1 Close off pressure ...

Page 3: ...ee Table 4 P Plated Brass S Stainless Steel A Standard Base X MN MS DCA Actuator Bracket VR N 2 A 001 00 P A MVN613A0000 C1 Table 2 Actuator Control Description Actuator Control MVN613A0000 Floating Two position SPDT or SPST 90 sec timing 24 V Fail in Place MVN643A0000 Floating Two position SPDT Fast Acting 30 sec timing 24 V Fail in Place MVN713A0000 Modulating 24 V Fail in Place MN6105A1011 Floa...

Page 4: ...c Floating 2 Pos 30 sec MVN643 Fail in place 2 Fail Safe Closed FSC 02 3R NEMA enclosure 3 24 Vac Modulating 0 2 10 Vdc MVN713 Fail in place 4 24 Vac Floating 2 Position MN6105 Fail in place 5 24 Vac Mod 0 2 10 Vdc MN7505 Fail in place 6 24 Vac Mod 0 2 10 Vdc Floating MS7505 Fail safe Flow Rate GPM Options range from B 9 See Table 4 7 24 Vac 2 Position MS8105 Fail safe 8 100 250 Vac 2 Position MS4...

Page 5: ...VRN2A 0 5 3 35 3 1 2 3 4 5 6 7 VRN2B 0 75 3 35 3 1 2 3 4 5 6 7 6 35 6 8 9 10 VRN2C 1 3 35 3 1 2 3 4 5 6 7 6 35 6 8 9 4 50 4 10 15 20 VRN2D 1 25 4 50 4 10 15 20 5 50 5 25 30 6 5 58 6 5 35 VRN2E 1 5 4 50 4 10 15 20 5 50 5 25 30 4 58 4 35 6 58 6 40 45 50 7 58 7 55 60 65 70 75 80 85 11 58 11 95 VRN2F 2 4 50 4 10 15 20 5 50 5 25 30 4 58 4 35 6 58 6 40 45 50 7 58 7 55 60 65 70 75 VRN2G 2 5 4 58 4 25 30 ...

Page 6: ... Rating Full Port A B C D E F G VRN2A 1 2 DN15 1 0 0 23 7 0 1 6 5 71 145 4 56 116 6 57 167 2 32 59 3 87 98 7 36 187 2 8 71 2 5 1 1 Stem 5112 19 5112 22 SS Regulator 8615 100 for 1 3 gpm 8615 101 for 4 10 gpm VRN2B 3 4 DN20 9 0 2 0 10 2 3 6 63 168 VRN2C 1 DN25 15 0 3 4 5 83 148 20 4 5 20 4 5 9 65 245 9 13 232 2 41 61 8 01 203 7 1 3 2 Stem 5112 20 5112 23 SS Regulator 8615 102 VRN2D 1 1 4 DN32 10 2 ...

Page 7: ...Size Flow gpm m3 h Dimensionsc in in mm Weight lb kg ServiceReplacement Parts NPT in S I metric Min Rating Max Rating Full Port A B C D E Fza Fsa VRN2A 1 2 DN15 1 0 0 23 7 0 1 6 5 71 145 5 43 138 8 87 225 2 32 59 2 5 64 10 02 255 8 77 223 2 5 1 1 Stem 5112 19 5112 22 SSb Regulator 8615 100 for 1 3 gpm 8615 101 for 4 10 gpm VRN2B 3 4 DN20 9 0 2 0 10 2 3 8 94 227 VRN2C 1 DN25 15 0 3 4 5 83 148 20 4 ...

Page 8: ...equency 50 Hz 60 Hz Mounting Click on installation no tool required Noise Rating at 1m Maximum 35 dB A max at 1 m 50 dB A for MVN643 Materials Plenum rated plastic housing Operating Humidity Range RH 5 to 95 RH non condensing Ambient Temperature Range 4 F to 131 F 20 C to 55 C Storage Temperature Range 40 F to 176 F 40 C to 80 C Weight 0 6 lb 0 27 kg Dimensions See Fig 1 and Table 5 Timing 90 sec ...

Page 9: ...Yes SSW2 1M Environmental Rating NEMA2 Frequency 50 Hz 60 Hz Manual operation Declutch mechanism Mounting Direct coupled Maximum Noise Rating Driving dBA 1m 35 Rotation to Open By switch Rotational Stroke Adjustment Dual Integral Adj Stops 3 degree increments Compatible Damper Shafts 1 4 to 1 2 in square or 3 8 to 5 8 in round 6 to 13 mm square or 8 to 16 mm round Shaft Adapter Type U bolt clamp S...

Page 10: ...ection By orientation External Auxiliary Switches Available No Environmental Rating NEMA2 Frequency 50 Hz 60 Hz Mounting Direct Coupled Maximum Noise Rating Holding dBA 1m 20 no audible noise Maximum Noise Rating Driving dBA 1m 50 Rotation to Open By switch Rotational Stroke Adjustment Mechanically limited 5 degree increments Compatible Damper Shafts 1 4 to 1 2 in square or 3 8 to 5 8 in round 6 t...

Page 11: ...th Terminal 1m Modulation RED BLACK WHITE x MVNAC6131 Replacement Cable with Terminal 1m Floating RED BLACK WHITE x x MVNAT3 Replacement Screw type Terminal Block Pluggable x x x 5112 11 Replacement actuator bracket x x 205860 Minimum position Potentiometer x x 32006306 001 Resistor Kit 500 ohm converts 4 20 mA signal to 2 10 Vdc x x Q7002B1009 Universal Interface Module x x STRN SCSA Self centeri...

Page 12: ...s and chillers Flow Characteristics The VRN2 two way dynamic pressure regulating control valves have an equal percentage flow characteristic with characterized flow control insert Required Operating Torque Both Honeywell non spring return MVN and spring return low torque direct coupled actuators can be utilized with the VRN2 valves VR valves use a patented seat design that reduces the torque neede...

Page 13: ...h pipe wrench by hexagonal fitting ONLY Do NOT handle the valve body with the pipe wrench product damage may result The valves are tapped in NPT and should be sealed with an approved pipe sealant Torque should not exceed 75 lb ft Refer to actuator literature for actuator dimensions 1 Clean the lines upstream of particles larger than 1 16 in diameter welding slag pipe scale and other contaminants 2...

Page 14: ... set aside the two screws that attach the mounting plate to the valve 5 Remove and set aside hold down ring from mounting plate 6 Rotate mounting plate around valve top to the desired position NOTE Take note of the screw hole positions on the valve They limit the mounting plate positions 7 Lower ring down to valve body and engage it in the new position relative to the mounting plate 8 Tighten scre...

Page 15: ...D FOR SPST CONTROL 24 VDC SUPPLY ACCEPTABLE FOR MVN643 2 CONTROLLER 2 DIRECT REVERSE SERVICE OFF M34869 3 3 4 3 2 FLOATING ACTUATOR 24 VAC Direct Reverse Service Off 1 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FLOATING CONTROLLER M18946A 24 VAC 1 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PROPORTIONAL CONTROLLER FEEDBACK 1 3 2 5 PR...

Page 16: ...AD PROTECTION AS REQUIRED USE CLASS II 24V TRANSFORMER 4 20mA CONTROLLER M33141B 1 2 3 DIP SWITCH POSITION 1 2 MODE OFF OFF 2 10V OFF ON 0 10V ON OFF 10 2V ON ON 10 0V PROPORTIONAL MODULATING 4 20mA CONTROLLER OUTPUT WITH 500Ω SERIES RESISTOR TO OTHER ACTUATORS 500 OHMS 1 2 W MINIMUM 24 VAC 2 RED BLACK WHITE 1 2 PROPORTIONAL ACTUATOR 24 VAC 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROT...

Page 17: ... AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE SET SWITCH TO MODULATING V OR OR N A FEEDBACK FEEDBACK 5 4 3 1 2 M19577B 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 SPST ACTUATOR 4 TO 20 mA PROPORTIONING CONTROLLER 24 VAC 1 1 2 3 2 490 TO 510 OHMS 1 2 W MINIMUM LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE ...

Page 18: ...uator from the valve shaft d Move the Self Centering Shaft Adaptor to the opposite side of the actuator as displayed in Fig 28 Fig 28 Change actuator to normally open 1 Remove the retainer clip from the Self Centering Shaft Adapter and set it aside for later use 2 Remove SCSA from actuator 3 Reinstall SCSA on the opposite side of the actuator aligning it based on the stroke labeling 4 Replace the ...

Page 19: ... loss If desired maximum flow may be trimmed to a lesser value in one of two ways 1 With modulating actuator limit span of control voltage issued by the building automation controller Valves with flow control inserts have an equal percentage flow characteristic See Fig 31 Each 10 reduction in maximum control voltage will result in a 10 reduction in flow Fig 31 Typical flow characteristics 2 To mec...

Page 20: ...of valve 3 Align arrow with short leg of T symbol on new stem assembly NOTE T symbol will vary 4 Insert the new stem assembly Be sure to line up the stem key with the ball slot 5 Fasten stem retainer high pressure plate to the valve using the new countersunk screws Then fasten the mounting plate to the valve 6 Repressurize valve and confirm stem does not leak before proceeding 7 Slide the sub shaf...

Reviews: