Honeywell ML4105 Product Data Download Page 6

ML4105, ML4115, ML8105, ML8115 FAST-ACTING, TWO-POSITION ACTUATORS

63-2540—9

6

OPERATION

The ML4105, ML4115, ML8105, and ML8115 DCA are 

designed for use in Smoke Control Systems. If power fails, the 

actuator spring returns to the 0° position. The actuator mounts 

flush with the damper box. The actuator drives from 0° to 95° 

and spring returns back to 0°.

IMPORTANT

A break in power of less than two seconds can cause 

the actuator to spring-return 5 degrees or less and 

remain in place until a break in power of longer 

duration.

The actuators are operated by an spst two-position controller. 

When using an spst two-position controller, the actuator drives 

to the damper fully open position when controller contact 

makes and spring returns to the damper fully closed position 

when controller contact breaks. The actuator drops to holding 

power level on detection of stall, independent of hub position.

Cycling

The actuator and the internal spring are designed so that no 

special cycling during long-term holding is required. 

Honeywell recommends following all local, state, and national 

codes for periodic testing of the entire smoke control system. 

Refer to National Fire Protection Association (NFPA) National 

Fire Codes

®

: NFPA90A, NFPA92A, and NFPA92B for your 

application.

Temperature Indicator

The temperature indicator, located on the cover of the 

actuator, provides evidence that the ambient temperature has 

exceeded 200°F (93°C). This is an indication that something 

in the building has caused temperatures to rise well above the 

long-term actuator operation temperature. While the actuator 

is capable of operating at 350°F (176°C) for extended periods 

of time, this indicator provides a visual signal that the actuator 

has been exposed to high temperatures for an undetermined 

period of time. The indicator provides a visual indication to fire 

authorities regarding the extent of damage after an event in 

the building.

IMPORTANT

If the indicator turns black, replace the actuator.

NOTE: The actuator is designed to operate for 30 minutes 

during a one-time excursion to 350°F (176°C).

CHECKOUT

ML4105A,B and ML4115A,B (120 Vac model)

1.

Verify that the indicator has not turned black (see 

Temperature Indicator section).

2.

Check damper position.

3.

Connect 120 Vac to the black and white leadwires to 

drive the damper to the open position. The actuator 

should drive the damper.

4.

If the actuator does not run, remove power for at least 

two seconds.

5.

If the actuator spring returns, allow it to close entirely, 

then return to step 3.

6.

If the actuator does not spring return, verify that the 

actuator is properly installed. See Installation section.

7. I

f the actuator is correctly installed but neither runs nor 

spring returns, replace the actuator.

ML4105C,D and ML4115C,D (230 Vac model)

1.

Verify that the indicator has not turned black (see 

Temperature Indicator section).

2.

Check damper position.

3.

Connect 230 Vac to the blue and brown leadwires to 

drive the damper to the open position. The actuator 

should drive the damper.

4.

If the actuator does not run, remove power for at least 

two seconds.

5.

If the actuator spring returns, allow it to close entirely, 

then return to step 3.

6.

If the actuator does not spring return, verify that the 

actuator is properly installed. See Installation section.

7. I

f the actuator is correctly installed but neither runs nor 

spring returns, replace the actuator.

ML8105 and ML8115 (24 Vac model)

1.

Verify that the indicator has not turned black (see 

Temperature Indicator section).

2.

Check damper position.

3.

Connect 24 Vac to the red and black leadwires to drive 

the damper to the open position. The actuator should 

drive the damper.

4.

If the actuator does not run, remove power for at least 

two seconds.

5.

If the actuator spring returns, allow it to close entirely, 

then return to step 3.

6.

If the actuator does not spring return, verify that the 

actuator is properly installed. See Installation section.

7.

If the actuator is correctly installed but neither runs nor 

spring returns, replace the actuator.

Summary of Contents for ML4105

Page 1: ...al spring return ensures level of return torque Fifteen second spring return timing No special cycling required during long term holding See Operation section No audible noise during holding Patent pending design eliminates need for limit switches to reduce power consumption Models available for 24 120 and 230 Vac Ninety five degree angle of rotation Actuator holds rated torque at reduced power le...

Page 2: ...28 UNF set screws Use 1 8 in Allen wrench to tighten set screws ML4105C D Four 3 mm set screws Use 3 mm Allen wrench to tighten set screws ML4115 ML8115 Two 1 4 28 UNF set screws Use 1 8 in Allen wrench to tighten set screws IMPORTANT Honeywell does not recommend using linkages with these actuators because side loading of the output hub reduces actuator life Temperature Ratings Ambient 0 F to 130 ...

Page 3: ...ication NFPA recommends periodic examination of each fire smoke damper semi annually or annually to ensure proper performance Design Life at Rated Voltage 60 000 full stroke cycles Approvals See Table 2 Environmental Protection Ratings See Table 3 Accessories 201391 Shaft Adapter for 3 8 in shafts not supplied with actuator 205649 Mounting Bracket not supplied with actuator Table 2 Approvals Table...

Page 4: ... the bottom that with a 205649 Mounting Bracket secure it flush to a damper box see Fig 2 When mounted correctly these slots allow the actuator to float without rotating relative to the damper shaft CAUTION Equipment Damage Hazard Tightly securing actuator to damper housing can damage actuator Mount actuator to allow it to float along its vertical axis NOTE ML4105 ML4115 ML8105 and ML8115 Actuator...

Page 5: ... lb in maximum 60 lb in torque Use 1 8 in or 3 mm Allen wrench see Specifications for details to tighten set screws Wiring See Fig 4 through 8 for typical wiring diagrams WARNING Electrical Power Hazard Line voltage can cause death or serious injury and short equipment circuitry Disconnect power supply before installation CAUTION Electrical Shock or Equipment Damage Hazard Low voltage can shock in...

Page 6: ... building IMPORTANT If the indicator turns black replace the actuator NOTE The actuator is designed to operate for 30 minutes during a one time excursion to 350 F 176 C CHECKOUT ML4105A B and ML4115A B 120 Vac model 1 Verify that the indicator has not turned black see Temperature Indicator section 2 Check damper position 3 Connect 120 Vac to the black and white leadwires to drive the damper to the...

Page 7: ... DK Installasjonsinstruks N Installationsinstrukioner SF Asennusohje S Installations Instrukioner E Instrucciones de montage M11874 ASSEMBLY EINBAU MONTAGE MONTAGGIO MONTAGE MONTERE MONTERING ASENTAMINEN MONTERA MONTAJE D F I NL DK N FIN S E 24 VAC 120 VAC M11875 b a M11876 a b c d M12030 a b M11881 b a M11882 HEX 4mm MIN 45 lb in 5 1 Nm MAX 60lb in 6 8 Nm a b c A A1 A4 A3 A5 A2 A6 ...

Page 8: ...Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario 17 Changi Business Park Central 1 Belgium Suite 200 M1V 4Z9 Singapore 486073 Sunrise FL 33325 National Fire Codes is a registered trademark of the National Fire Protection Association NFPA 24 VAC 120 VAC M11884 DISASSEMBLY AUSBAU DÉMONTAGE SMONTAGGIO DEMONTAGE AFM...

Reviews: