120
43-TV-25-30 Iss.6 GLO Aug 07 UK
Recipients -
(only available when the Email function has been enabled). Select from a list
of email recipients.
Email addresses and Server names must be entered in
Print -
Set to a tick to enable the Print function. The printer settings must be set up before
this feature will operate, see
Export Device -
Select from a list of options if you require your report to be exported to an
external media device or select Do not export. The removable media device needs to be fit-
ted to the recorder when the report is run and have enough memory available.
When the configuration is complete select the Finish button to Commit, Discard or Commit
Later. Select the Back button to return to the previous menu.
Run a Report
Once the report details have been completed in the report menu you can run your report
either manually or by using the Event system.
• For a manual report see
“Reports (Process)” on page 153.
• For a report triggered using the Event system see
Pen Report Information
Currently pens provide real-time values, max, min and totals. Reports need some history of
these values to be maintained, so a set of period based data is maintained. The periods be-
ing an hour, day, week and month. The recorder builds up the current hour, day, week and
monthly data and keeps the previous (completed) hour, day, week and month stored.
At anytime it is possible to access the current hour, day, week or month for Max, Min, Aver-
age and Totals, also you can get access to the previously complete whole hour, day, week
or month for each pen.
• An hour is a whole hour starting on the hour eg. 10.00 to 11.00
• A day starts at one second passed midnight.
• A week starts one second passed midnight on Sunday
• A month starts at one second passed midnight on the 1st of the month
Access to this is provided automatically via reports but this information can also be included
in maths/scripts and by using embedded variables.
Pen Report Maths
In maths the following syntax is available:
prmax[x,y,z]
=
Pen report Max value
prmin[x,y,z]
=
Pen report Min value
prave[x,y,z]
=
Pen report Average value
prtot[x,y,z]
=
Pen report Totaliser value
where ...
x
= Pen Number 1 to 96
y
= period 1 = Hour, 2 = Day, 3 = Week, 4 = Month,
z
= report set 1 = Current, 2 = Previous completed
e.g.
P1 =prmax[23,2,1]
- Max value so far for current day for Pen 23
Summary of Contents for Minitrend QX
Page 2: ...ii 43 TV 25 30 Iss 6 GLO Aug 07 UK User manual ...
Page 50: ...44 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 192: ...186 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 210: ...204 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 242: ...236 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 249: ...43 TV 25 30 Iss 6 GLO Aug 07 UK 243 Multitrend SX Recorder 14 15 32 46 50 30 31 35 36 28 55 ...
Page 250: ...244 43 TV 25 30 Iss 6 GLO Aug 07 UK 52 11 23 33 39 5 6 RS485 USB host Ethernet 1 2 3 4 ...
Page 254: ...248 43 TV 25 30 Iss 6 GLO Aug 07 UK eZtrend QXe Recorder 16 5 3 1 4 2 24 49 9 45 19 6 49 ...
Page 258: ...252 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 274: ...268 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 276: ...270 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 296: ...290 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 308: ...302 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 312: ...306 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 323: ......