106
43-TV-25-30 Iss.6 GLO Aug 07 UK
CJC Calibration
For Thermocouple Input calibration only.
There is a single CJC sensor for each AI card, but the temperature across the connector will
not be constant. The CJC calibration allows the user to compensate for temperature gradi-
ent.
In this menu there is a button for each slot for Cold Junction Calibration. Calibration is per-
formed per slot/card.
• Select the desired slot button. If a CJC connector is not fitted a message box will
appear.
• The CJC temperature reading is displayed in the
CJ Temp
column.
• If the known temperature is different to the recorder’s reading an Offset can be entered
to make an adjustment to future values. The Cold Junction temperature should be
measured at the point where the thermocouple is connected in the terminal block.
Ensure the measured temperature is accurate to within 0.1
°
C.
• Enter the difference between the
CJ Temp
on the recorder and the measured reading
as the
Offset Value.
The offset is added to all future readings and displayed in the
Cal-
ibrated CJ Temp
column.
• The
Measured Temp
column will display the actual temperature using the
Calibrated
CJC Temp,
on channels with T/C fitted. For more details of how a thermocouple works,
“Appendix C: Thermocouple Connections” on page 285.
• Select the tick box to go back and the Finish button to Commit, Discard or Commit
Later.
Demo Traces
(Main Menu > Configure > Setup > Edit Setup> General > Factory > Demo Traces)
A set of demo traces available for demonstration or simulation purposes when no Analogue
cards are fitted.
Options for each demo trace are:
•
No Simulation -
Demo traces are deactivated and no simulation traces are
available.
•
Simulate if board not fitted -
Simulation is activated when an Analogue In card is
not fitted in one of the top two slot positions. Configure the
Demo Setup
in
Summary of Contents for Minitrend QX
Page 2: ...ii 43 TV 25 30 Iss 6 GLO Aug 07 UK User manual ...
Page 50: ...44 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 192: ...186 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 210: ...204 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 242: ...236 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 249: ...43 TV 25 30 Iss 6 GLO Aug 07 UK 243 Multitrend SX Recorder 14 15 32 46 50 30 31 35 36 28 55 ...
Page 250: ...244 43 TV 25 30 Iss 6 GLO Aug 07 UK 52 11 23 33 39 5 6 RS485 USB host Ethernet 1 2 3 4 ...
Page 254: ...248 43 TV 25 30 Iss 6 GLO Aug 07 UK eZtrend QXe Recorder 16 5 3 1 4 2 24 49 9 45 19 6 49 ...
Page 258: ...252 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 274: ...268 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 276: ...270 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 296: ...290 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 308: ...302 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 312: ...306 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 323: ......