background image

Quick Start Guide

Midas

®

 Gas Detector

High-Temperature Pyrolyzer Option

(MIDAS-T-HTP)

1. Introduction

The MIDAS-T-HTP pyrolyzer option is installed 
underneath the standard Midas

®

 gas detector. The air 

sample is drawn through the pyrolyzer to the sensor 
cartridge. The pyrolyzer converts perfluorocompounds 
(PFCs) present in the air sample into hydrogen 
fluoride (HF) by means of pyrolysis. The HF can then 
be measured by the sensor and the concentration 
displayed as the equivalent reading in ppm.

NOTE: 

To maintain stated sensor accuracy when 

using the pyrolyzer, ensure ambient temperature of 
installation point does not exceed 30°C (86°F). It is 
recommended that the ventilated Midas

®

 top cover 

part number MIDAS-A-039 is used in all pyrolyzer 
applications. Usage above this temperature may 
require more frequent bump testing or calibration to 
confirm working specification.

(Contact Honeywell Analytics for the availablity of 
other detectable gases using this pyrolyzer module)

2. Fitting the pyrolyzer module

See reverse for all diagrams

1.  Isolate power to the detector.
2.  Unscrew the captive thumbscrew located on the 
 

front panel.

3.  Remove the cover by pulling it forward off the main  
 

chassis (See Diagram 1).

4.  Unscrew the two captive retaining screws located 
 

at the bottom front of the chassis.

5.  Pull the main chassis forward to disconnect it from 
 

the mounting bracket assembly (See Diagram 2).

6.  Thread the connector and wire harness from 
 

the pyrolyzer through the rectangular access in the 

 

bottom of the mounting bracket and secure wires 

 

with retention clip (if available).

7.  Plug the connector into the socket (con5) at the 
 

bottom left of the terminal board.

8.  Offer the pyrolyzer module up underneath the 
 

mounting bracket ensuring that the fitting at the 

 

top rear of the pyrolyzer mates with the sample 

 

inlet port at the bottom of the mounting bracket.

9.  Align the three screw mounting bosses on the 
 

top of the pyrolyzer with the three screw holes in 

 

the mounting bracket.

10. Insert and tighten the three screws provided 
 

(See Diagram 3).

3. Reassembling the Midas® detector

1.  Align the PCB at the top rear of the main chassis 
 

with the connector at the top of the mounting 

 

bracket.

2.  At the same time, align the two tubes at the 
 

bottom rear of the main chassis with the two 

 

tubes located on the bottom of the mounting 

 

bracket.

3.  Slide the chassis backwards on the mounting 
 

bracket assembly so that the PCB, connector 

 

and tubes engage fully by firmly pushing 

 

the main chassis horizontally backwards on the 

 

mounting bracket.

 

WARNING:

 

DO NOT PUSH ON THE LCD AS THIS MAY 

 

CAUSE DAMAGE.

4.  Align the two fixing screws located at the 
 

bottom of the chassis with the screw threads on 

 

the mounting bracket.

5.  Tighten the screws to secure the chassis to the 
 

mounting bracket.

6.  Fit the MIDAS-S-CFX sensor cartridge into the 
 

sensor cartridge chamber (See Diagram 4, and 

 

refer to the Sensor Cartridge Installation Quick 

 

Start Guide MIDAS-A-021).

7.  Set the power switch to the “on” position.
8.  Refit optional Midas

®

 ventilated top by aligning the 

 

slots on either side with locating tabs on the 

 

mounting bracket assembly and push the cover 

 

horizontally until seated.

9.  Tighten thumbscrew on the front panel 
 

(See Diagram 5)

4. Configuration

1.  After completion of the startup sequence, press 
 

the ‘

s

’ button for a few seconds to select the   

 

setup menu.

2.  Enter the passcode (if set).
3.  Use the ‘

s

’ or ‘

t

’ buttons to select the set up 

 

menu ‘

’ icon and press the ‘

3

’ to accept.

4.  Use the ‘

s

’ or ‘

t

’ buttons to select the set alarms 

 

‘ ALm’ submenu and press ‘

3

’ to accept.

5.  The flashing gas ID code is displayed along with 
 

the gas cylinder and alarms icon ‘

’.

6.  Use the ‘

s

’ or ‘

t

’ buttons to change the gas ID 

 

number to to the appropriate PFC gas. See the 

 

manual for further details.

7.  Continue to accept or change the rest of the alarm 
 

settings. *

8.  Press ‘

3

’ to update all changes (UPdt displayed).

9.  Press ‘X’ twice to return to normal operation.

 

* For further details regrading the Midas

®

 pyrolyzer 

 

option, refer to the Midas

®

 operating manual 

 

MIDAS-A-001.

Contact Honeywell Analytics:

  

Find out more

www.honeywellanalytics.com

Europe, Middle East, Africa, India

Life Safety Distribution AG
Wilstrasse 11-U31
CH-8610 Uster
Switzerland
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
[email protected]

Americas

Honeywell Analytics Inc. 
405 Barclay Blvd.
Lincolnshire, IL 60069
USA
Tel: +1 847 955 8200 
Toll free: +1 800 538 0363 
Fax: +1 847 955 8208
[email protected]

www.honeywell.com

Technical Services

[email protected]

Asia Pacific 

Honeywell Analytics Asia Pacific 
#508, Kolon Science Valley (I) 
187-10 Guro-Dong, Guro-Gu 
Seoul, 152-050, 
Korea 
Tel: +82 (0)2 2025 0300
Fax: +82 (0)2 2025 0329
[email protected]

Issue 1.1 03.06 
Part No. MIDAS-A-038
10/08
© 2008 Honeywell Analytics

Please Note:

While every effort has been made to ensure accuracy in this 
publication, no responsibility can be accepted for errors or 
omissions. Data may change, as well as legislation, and you are 
strongly advised to obtain copies of the most recently issued 
regulations, standards, and guidelines.This publication is not 
intended to form the basis of a contract.