![Honeywell MCT404 User Manual Download Page 85](http://html.mh-extra.com/html/honeywell/mct404/mct404_user-manual_148805085.webp)
5. Managing DE Devices using MC Toolkit Software
5.5. Online configuration
Revision 3
MC Toolkit (MCT404) User Manual
73
Summary of Operating Procedures
To access displays for Honeywell DE Transmitters:
Start the MC Toolkit application; the
MC TOOLKIT ...
display will appear.
Refer to 5.1 Starting
Upload the database from the transmitter. (The
QUICK MONITOR
display will enable viewing of
key parameters before taking the time for database uploading.) The
DE MAIN MENU
appears.
5.3 MC Toolkit Application Software Display Conventions
in this section.)
Select the appropriate display from the
DE MAIN MENU
. (Refer to Table 11 DE Displays / Tasks
Summary in this section, and to the list of DE displays.)
The content of each display is summarized in Table 11.
Note:
Only the Basic display is available for the STT 750 Temperature Transmitter.
Table 11 DE Displays / Tasks Summary
Menu Item
Task
DEVICE INFO
Enter:
Device Type:
Tag ID
Message (in Scratch Pad)
Observe (Read):
Type
Serial Number
Firmware Version
GENERAL
Select:
PV Type
Enter:
Comm Mode
Line Filter (STT)
T/C Fault Detect (STT)
Observe (Read):
Failsafe Direction
DE CONFIGURE
Select:
PV Units
SV Units
Conformity (ST)
Damping
Sensor Type (STT)
Linear
Enter:
LRV
URV
Observe (Read):
LRL
URL
Span
Sensor Type (ST)
CALIBRATION
Enter/Select:
Correct Input (Zero)
Correct Input (LRV)
Correct Input (URV)
Reset Corrects (Zero, LRV,
URV)
Loop Test (Check Analog Output
Level)
Trim DAC Current (Calibrate
output current)
Apply Values (that is, re-range
LRV and URV to PV input)
Observe (Read):
Input at Zero, LRV, and URV
(Verify) Reset Corrects
Loop Current (continuity)
Output Current level (at 0 %,
100%)
Applied values of LRV and URV
Summary of Contents for MCT404
Page 12: ......
Page 26: ......
Page 88: ...5 5 Online configuration 76 MC Toolkit MCT404 User Manual Revision 3 DE Upload Procedures ...