Installation

1.

A filter or strainer of 40 mesh (0.6 mm maximum) or 

greater is recommended in the fuel piping to protect 

the downstream safety shut-off valves.

2.

Properly support and pipe the valve in the direction of 

the flow arrow on the valve body. Valve seats are direc

-

tional. Sealing will be maintained at full rated pres

-

sures in one direction only. Sealing will be provided in 

reverse flow only at reduced pressures.

3.

Mount valve so that open/shut window indicator will 

be visible to your operating personnel. The open/shut 

window indicator should never face downward.  The 

valve side plates should be located in a vertical plane 

for best performance. Valves are usually installed in 

horizontal piping; however, other orientations are 

acceptable, subject to the above limitations. The top 

assemblies of all MAXON valves are field rotatable to 

allow installations involving conflicts with these 

mounting restrictions.

4.

Wire the valve in accordance with all applicable local 

and national codes and standards. In U.S. and Can

-

ada, wiring must conform to the NEC ANSI/NFPA 70 

and/or CSA C22.1, Part 1.

• Supply voltages must agree with valve’s 

nameplate voltage within -15%/+10% for proper 

operation. For electrical wiring schematic, see 

instructions or sample affixed inside valve 

terminal block cover.

• Grounding is achieved with a grounding screw, 

which is located in the top assembly.

• Customer connections are provided via terminal 

blocks located in the top assembly.

• Main power wiring (120 VAC or 240 VAC) must be 

segregated from lower voltage 24 VDC signal 

wiring, when both are required.

• To eliminate any potential for gas to enter the 

electrical wiring system, install a conduit seal 

fitting at the actuator conduit hub.

5.

Maintain integrity of the electro-mechanical actuator 

enclosures by using the appropriate electrical connec

-

tors for the (2) 3/4” NPT conduit threaded connec

-

tions.

6.

All access cover plate screws should be tightened 

using a torque wrench in an alternate cross-corner 

tightening pattern to the values shown in “Torque 

Specifications” on page 4.

7.

Verify proper installation and operation by electrically 

actuating the valve for 10-15 cycles prior to the first 

introduction of gas.

8.

WARNING - Explosion hazard

• Do not connect or disconnect this equipment 

unless power has been removed or the area is 

known to be non-hazardous. 

• Substitution of components may impair 

suitability for Class I, Division 2 (applies to 

4700NI valves only).

9.

This equipment is suitable for installation in Class I, 

Division 2 Groups B, C, D, and Class II Groups F and G, 

and Class III hazardous locations or non-hazardous 

locations (applies to 4700NI valves only).

Auxiliary features

• Non-adjustable proof of closure switch(es) with 

valve seal over travel interlock

• Auxiliary switch for indication of full travel (open for 

normally-closed valves, closed for normally-open 

valves)

Operating environment

• Actuators rated for NEMA 4 or optional NEMA 4X
• Ambient and fluid temperature range of -20°F to 

+140°F for 1" & 1-1/4" valves

• Ambient and fluid temperature range of -20°F to 

+125°F for  3/8", 1/2" & 3/4" valves

• All valves for oxygen service or using Ethylene Pro

-

pylene body seals are limited to a minimum ambient 

and fluid temperature of 0°F

Summary of Contents for MAXON 4760 Series

Page 1: ...ORTER BELGIUM Maxon International BVBA Luchthavenlaan 16 18 1800 Vilvoorde Belgium Tel 32 2 255 09 09 Fax 32 2 251 82 41 Please read the operating and mounting instructions before using the equipment Install the equipment in compliance with the prevailing regulations Bedrijfs en montagehandleiding voor gebruik goed lezen Apparaat moet volgens de geldende voorschriften worden geïnstalleerd Lire les...

Page 2: ...ult the nameplate of your valve This lists the maximum operating pressure temperature limitations voltage requirements and service conditions of your specific valve Do not exceed nameplate ratings Abbreviation or symbol Description M O P Maximum operating pressure OPENING Valve opening time for automatic valves only Units shown in seconds Solenoid clutch voltage and frequency Motor voltage and fre...

Page 3: ...y top assembly or motor drive unit Any alterations void all warranties To determine suggested spare parts identify series designation and serial number from the valve s nameplate Refer to the illustration and legend below to identify suggested spare parts To order specify 1 Quantity 2 Assembly part number if available 3 Description 4 Electrical specification 5 Full nameplate information from exist...

Page 4: ...ch locations are noted on sketch Fig 1 Table 11 Torque Specifications Valve Type Item Number Description Torque 8700 1 Adaptor Base Mounting Screws 3 8 16 x 2 UNC 239 in lbs 2 Cover Mounting Screws 1 4 20 x 625 UNC 71 in lbs 3 Nameplate Mounting Screws 8 32 x 25 10 in lbs 4 Actuator Adaptor Screws 3 8 16 x 1 5 239 in lbs 4700 33479 5 Adaptor Base Mounting Screws 3 8 16 x 2 UNC 239 in lbs 6 Namepla...

Page 5: ...verted snap switch mounted on rear of switch bracket VCS 1 is an SPDT single pole double throw switch VCS 2 is a DPDT double pole double throw switch All contacts are available for external circuitry VOS Valve Open Switch is actuated when valve reaches full open It is the lower snap switch mounted on front of switch bracket VOS 1 is an SPDT switch On automatic reset valves its normally closed cont...

Page 6: ...40 VAC must be segregated from lower voltage 24 VDC signal wiring when both are required To eliminate any potential for gas to enter the electrical wiring system install a conduit seal fitting at the actuator conduit hub 5 Maintain integrity of the electro mechanical actuator enclosures by using the appropriate electrical connec tors for the 2 3 4 NPT conduit threaded connec tions 6 All access cov...

Page 7: ...60 C T3C Ta 60 C UL UL 429 Not Applicable Not Applicable CSA CSA 6 5 CSA 22 2 No 139 CSA 22 2 No 0 CSA 22 2 No 0 4 CSA 22 2 No 25 CSA 22 2 No 94 CSA 22 2 No 142 CSA 22 2 No 213 Class I Div 2 Groups ABCD Class II Div 2 Groups FG Class III T4 AC 60 C T3C DC 60 C IEC Approvals Not Applicable Not Applicable IEC 60079 0 IEC 60079 15 IEC 60079 31 Ex nA nC IIC T4A AC T3 DC Gc Ex tc IIIC T135 C Dc IP65 29...

Page 8: ...2P 2D with PEEK backed Disc for lower actuation friction Solenoid Voltage 0 None A 115V 50HZ B 115V 60HZ C 230V 50HZ D 230V 60HZ E 208V 50HZ F 24VDC G 120VDC Clutch Voltage 0 None B 115V 60Hz Motor Voltage A 115V 50Hz B 115V 60Hz G 230V 50Hz H 230V 60Hz Motor Timing 6 6 Sec 7 Sec on 50Hz VOS Switch 1 VOS 1Switch 2 VOS 2 Switch VCS Switch 0 NoSwitchOrdered 1 VCS 1 Switch 2 VCS 2 Switch Enclosure Ra...

Page 9: ...it and electrical leads then check that signal switch wands are properly positioned and that the open shut indicator moves freely Failure to correct any such misalignment can result in extensive damage to the internal mechanism of your valve 12 Energize valve and cycle several times from closed to full open position Also electrically trip the valve in a partially opened position to prove valve ope...

Page 10: ...Testing of MAXON Shut off Valves 10 35 2 at www docuthek com Any valve that exceeds the allowable leakage as set forth by your local codes or insurance requirements should be removed from service and your MAXON representative should be contacted Actuator assemblycomponents require no field lubrication and should never be oiled Auxiliary switches solenoids motors clutches or circuit boards may be r...

Page 11: ...E i 05 22 11 32M 95002 03 ...

Page 12: ...alSolutions honeywell com or contact your Honeywell Sales Engineer Honeywell MAXON branded products 201 E 18th Street Muncie IN 47302 USA www maxoncorp com Honeywell Process Solutions Honeywell Thermal Solutions HTS 2101 CityWest Blvd Houston TX 77042 ThermalSolutions honeywell U S Registered Trademark 2022 Honeywell International Inc 32M 95002 03 e05 22 EAS 50116777 001 rev B Printed in United St...

Reviews: