background image

DIRECT DRIVE DAMPER ACTUATOR M847D

3

95C-10905—02

Wiring

See Figure 3 for typical wiring hook-ups of the M847D.

Fig. 3. Typical M847D Hookup.

CHECKOUT

After completing the installation, check that the equipment 

operates correctly as follows:

1.

When 24 Vac is applied to the motor leads, the motor 

powers to the closed or open position.

2.

When power is removed, the motor releases and spring 

returns to the normal position.

If full opening and closing is not achieved, check the lower 

adjustment lever is to the extreme left and the upper lever is to 

the extreme right. See Fig. 4 (Air Flow Adjustments).

Air Flow Adjustments

NOTE: The following describes the adjustments available 

with the actuator installed in the 

power closed

 

mode. If the damper you are installing is to operate in 

the 

power open

 mode, the function of the upper and 

lower levers is reversed.

1.

When viewed on end, the lower lever is normally posi-

tioned to the extreme left (See Fig. 4). This position 

allows the damper to fully open 90° when de-energized.

2.

To restrict the air flow in the open position, loosen (do 

not removed) the wing nut and move the lower lever to 

the right until the desired position is reached. Tighten 

the wing nut. In the extreme right position the damper 

should open approx. 50° with the power off.

3.

The upper lever is normally positioned to the right to 

provide complete shut off when the actuator is ener-

gized (See Fig. 4).

4.

If desired, to prevent complete closure of the damper, 

loosen (do not remove) the wing nut on the bottom of 

the unit and move the upper lever to the left until the 

desired position is achieved. Tighten the wing nut. In the 

extreme left position the damper should close to approx. 

40° with the power on.

5.

If additional rotation is required beyond 90°, an addi-

tional 15° may be obtained by removing the Upper 

Lever. To do this, first remove the actuator from the 

damper. Remove the wing nut and retaining ring then 

remove the levers. Reassemble and install.

Fig. 4. Air Flow Adjustment

2

1

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

NOMINAL CURRENT 0.32 AMP.

1

2

24 VAC

60 HZ

ZONING SWITCH

OPERATOR

MOTOR

ORANGE

YELLOW

M32381

Summary of Contents for M847D

Page 1: ...conduit Nominal Angular Rotation 90 max 105 Torque Min 423 mNm 60 in oz output torque available when motor is energized and device is at the spring returned initial start position Nominal Motor Timing 25 C ambient Energized at rated load 30 seconds De energized spring return 10 seconds Ambient Temperature Rating 5 to 60 C 40 to 140 F Finish zinc plated steel anodized aluminium Direction of Shaft R...

Page 2: ...h the connection coupling is attached is such as to firmly hold the actuator in a position to adequately engage the anti rotation pin in the warm air duct See Figure 1 for the critical dimensions Replacing M847D on a Trol A Temp ARD damper 1 Disconnect the motor wiring 2 Using a 1 8 in hex wrench to loosen the motor coupling from the blade shaft remove the existing motor assem bly 3 Observe that t...

Page 3: ...he damper to fully open 90 when de energized 2 To restrict the air flow in the open position loosen do not removed the wing nut and move the lower lever to the right until the desired position is reached Tighten the wing nut In the extreme right position the damper should open approx 50 with the power off 3 The upper lever is normally positioned to the right to provide complete shut off when the a...

Page 4: ...D Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2010 Honeywell International Inc 95C 10905 02 T D Rev 12 10 Printed in U S A ...

Reviews: