Parameters

N

o

Description

Settings (default in bold)

1:LA

Language

1 = EN

, 2 = NL, 3 = DE, 4 = FR, 5 = ES

4:LL

Lower Temperature Limit

5

 - 21 (°C)

5:UL

Upper Temperature Limit

21 - 

35

 (°C)

6:SO

Schedule options

1 = 7 day (different schedule each day of the week)

2 = 5 + 2 day (w weekend schedule)

3 = 1 day (same schedule every day)

7:NP

Number of periods per day

4

 or 6

8:SS

Wired Remote Sensor

0 = No Remote Sensor

, 1 = Wired Remote Sensor

9:LC

Fail Safe mode 

0 = Boiler off

,

 

1 = Boiler 20% on / 80% off

10:BL

Backlight

0 = Off, 

1 = On (only on demand)

11:CL

Clock Format

0 = 24 hr

, 1 = AM/PM

12:DS

Daylight Saving time change

0 = Off, 

1 = Auto

13:TO

Temperature Display Offset

+/-1.5°C

15:SD

Restore Schedule Defaults

0

, 1 = reset

16:FS

Restore Factory Settings

0

, 1 = reset

Configure the System

3

Specific settings for the thermostat 
and heating system can be 
configured in the advanced menu.

Press and hold   and then   

 

buttons together until the display 
changes (approx. 

3 seconds

).

A)

   Press   and 

 buttons to navigate 

through the parameter list

B)

   Press   and   buttons to 

change a parameter

C)

   Press   button to save the change 

(or press 

 to cancel the change)

D)

   Press 

 button to exit advanced 

menu and save any changes

Parameter 

Number

Parameter 

Setting

OpenTherm Data ID's

N

o

Description

Settings (default in bold)

OT1

Low load control

0 = Off, 

1 = On

OT2

Control setpoint

5 - 99°C

OT3

Supply water temperature

5 - 99°C

OT4

Return water temperature

5 - 99°C

OT5

Max. supply water temperature

5 - 99°C

OT6

Hot water temperature

5 - 99°C

OT7

Hot water setpoint

5 - 99°C

OT8

Actual power

0 - 99%

OT9

Water pressure

0.0 - 9.9

OT10

OTC control

0 = Off

, 1 = On

OT11

OTC curve

4 - 40 (

16

)

OT12

Room compensation

0 = Off

, 1 = On

Conforms to protection requirements of the following directives: 

EMC: 2014/30/EU

 and 

LVD: 2014/35/EU

ErP: Class VI (+4%), (EU) 811/2013

WEEE Directive 2012/19/EC

 - 

Waste Electrical and Electronic Equipment directive

At the end of the product life dispose of the packaging and product in a corresponding recycling 
centre. Do not dispose of the unit with the usual domestic refuse. Do not burn the product.

Troubleshooting

Manufactured for and on behalf of the Environmental & Energy Solutions
Division of Honeywell Technologies Sàrl, ACS-E&ES, Z.A., La Pièce 16, 
1180 Rolle, Switzerland by its Authorised Representative Honeywell Inc.

Honeywell Control Systems Ltd.

Skimped Hill Lane, 
Bracknell, 
Berkshire
RG12 1EB

www.honeywelluk.com

© 2016 Honeywell International Inc.  |  Printed in UK

What’s happening?

What it could mean...

How to fix it...

Thermostat 
display is blank

No power to 
heating system

Check heating system is powered

Faulty wiring connection Check wiring at thermostat 

and boiler terminals

Display = 

  

Faulty temperature 
sensor

Replace thermostat or check wiring to 
remote temperature sensor if fitted

Thermostat shows 
heat demand   
but boiler doesn't 
respond

Boiler (water) already 
at temperature

Normal behaviour - wait for 
water temperature to drop

Faulty wiring connection Check wiring at thermostat 

and boiler terminals

Reviews: