LonWorks interface
nvoDrvPwr
This output network variable provides the drive output power in kW.
nvoDrvRunHours
This output network variable provides the drive resettable operation time counter for the motor
in running hours. The maximum value for used SNVT is 65535 h. On the frequency converter
the value can go much higher. If the counter exceeds the SNVT's maximum value, the network
variable stays at its maximum. In such cases the real value can be seen on drive operating key-
pad.
nvoDrvStatus
This output network variable provides the drive status.
nvoDrvEnrgy
This output network variable provides the drive resettable energy consumption counter. The
maximum value for used SNVT is 65535 kWh. On the frequency converter the value can go
much higher. If the counter exceeds the SNVT's maximum value, the network variable stays at
its maximum. In such cases the real value can be seen on drive operating keypad.
nvoActFault
This output network variable provides the drive active fault code. If the value is 0 the frequency
converter has no fault. See the fault code list in drive User's Manual for fault identification.
nvoProcessOut1..8
These output network variables are sent directly from the application (see more detailed expla-
nation in chapter 6.5 Process data) The valid range is 0 to 65535 (-163,840 to 163,835)
nvoDigitalOut1..8
These output network variables are sent directly from the application (see more detailed expla-
nation in chapter 6.5 Process data).
Bit
Description
Value = 0
Value = 1
0
Not Ready
Ready
1
FC stopped
Running
2
Clockwise
Counterclockwise
3
No fault
Fault active
4
No warning
Warning active
5
Reference not Actual value
Reference = Actual value
Table 15. Status word bit descriptions