LCBS CONNECT SOLUTION
31-00118EFS—01
34
6. Two Heat Two Cool Integrated Economizer Differential Enthalpy
Changeover and Temperature Limit
BUILDING NAME
CVAHU RTU NAME
DATE
COOL 2
HEAT 1
HEAT 2
FAN
COO
COOL 1
TWO HEAT TWO COOL INTEGRATED ECONOMIZER DIFFERENTIAL ENTHALPY
MCR36713
C7250A
MA SENSOR
C7250A
DA SENSOR
M7215A
ECONOMIZER
ACTUATOR
ACTUATOR
24 VAC POWER
HVAC SYSTEM
24 VAC POWER
EXISTING
TRANSFORMER
C7250A
MIXED AIR SENSOR
C7250A
OUTDOOR AIR SENSOR
C7250A
DISCHARGE AIR SENSOR
M7215A
ECONOMIZER ACTUATOR
AT40A
TRANSFORMER (SIZE APPROPRIATELY)
THIS APPLICATION PROVIDES AUTOMATIC CONTROL OF TWO STAGES OF GAS OR ELECTIR HEAT, TWO
STAGES OF DIRECT EXPANSION COOLING, AND INTEGRATED ECONOMIZER WITH DIFFERENTIAL ENTHALPY
CONTROL AND HIGH TEMPERATURE LIMIT (SEE APP GUIDE FOR HIGH LIMIT (SEE APP GUIDE FOR DETAILED
SEQUENCE). CONFIGURER HAS THE ABILITY TO SET UP SETBACK, SETUP FEATURES THAT WILL ENABLE
BUILDING OWNER TO ACHIEVE ENERGY SAVINGS BY REDUCING EQUIPMENT OPERATION DURING
UNOCCUPIED PERIODS. ADAPTIVE INTELLIGENT RECOVERY IS ALSO A STANDARD FEATURE. IT PERMITS
CONTROLLED OPERATIONAL TRANSITION OF HEATING AND COOLING EQUIPMENT FROM UNOCCUPIED TO
OCCUPIED TO 1] GUARD AGAINST EQUIPMENT OVERUSE AND 2] HELP CONTROL POTENTIAL ELECTRICAL
SPIKES RESULTING IN DEMAND CONTROL UTILITY CHARGES. SYSTEM SUPPLY FAN AUTOMATICALLY
OPERATES IN A CONTINUOUS MANNER DURING OCCUPIED PERIODS AND CYCLES ON A CALL FOR HEATING
OR COOLING DURING UNOCCUIPED PERIODS TO MEET THE NEED OF PREVAILING BUILDING CODES.
LCBS CONNECT – INFORMATION
OS#
DESCRIPTION
YCRL6438SR LCBS CONTROLLER (WITH WALL MODULE)
LCBS CONNECT – COMPONENTS SHOWN
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
24VAC CO
M
24VDC
24VAC
R
W1
W2
W
3 O
B
G-L
Y1
Y2
Y3
G-L
RH
RC
CO
M
AU
X
DO
1 AUX
G
UI-1
DI-2
DI-3
UI-4
UI-5
UI-6
UI-2
UI-3
COM
COM
COM
DI-4
DI-1
COM
AO-3
AO-1
COM
A0-2
COM
NET-1
NET-2
S-BUS
S-BUS
SHIELD
EGND
LCBS
CONTROLLER
SYLK BUS
24 VAC
CONTROLLER
POWER
LCBS
CONTROLLER
WALL
MODULE
C7400S SYLK OUTSIDE AIR
ENTHALPY SENSOR
C7400S SYLK RETURN AIR
ENTHALPY SENSOR