Honeywell L482A Installation Instructions Download Page 3

L482A LOW LIMIT CONTROLLER 

L1 

(HOT) 

L2 

FAN  RELAY 

LOCAL ALARM 

C792 

Fig. 5. Hookup providing freeze protection by shutting

down fan with line powered local alarm. 

LINE 2 

LINE 1 

M2 

M1 

36 INCH 
(914 MM) 
MAXIMUM 

CONDUIT 

TO 
FAN 
RELAY 

JUNCTION 

BOX 

LINE 2  LINE 1 

M1

M2 

TO 
AUTOMATION 
SYSTEM 

C793 

Fig. 6. Providing separate conduit for switched ac and 

automation input wiring. 

Adjustment 

Turn the setpoint adjustment screw (Fig. 1) on the top of the 

controller case to the value called for on the job drawings. 

NOTES: 

1.

  

The setpoint adjustment is limited to 35-55°F 

(2-13°C) by an internal physical stop. 

2.

  

The setpoint is factory set at 35°F. Setpoint is the 

temperature at which LINE 1 to M1 contacts close 

and LINE 2 to M2 contacts open on a temperature 

fall. The controller differential is fixed at 5°F (3°C) 

nominal and is additive to the setpoint. 

3.

  

The operating point drops for elevations above 

sea level. To compensate, increase the setpoint 

adjustment 1°F (0.6°C) above the required set-

point for each 1000 feet (305m) above sea level. 

CHECKOUT 

Because of the L482A limited setpoint range, operational 

checkout can be difficult. Use one of the following methods to 

verify proper controller operation:

1.

  

If the ambient temperature is below 50°F (10°C): 

a.

  

Turn the setpoint adjustment through the ambient 

temperature and note the switch action. 

b.

  

When the setpoint is increased to equal the ambient 

temperature: 

(1) LINE 1 to M1 contacts should close. 

(2) LINE 2 to M2 contacts should open. 

c.

  

Decreasing the setpoint to 5°F (3°C) below the 

ambient temperature should not affect the contact 

positions. 

d.

  

Pushing the manual reset button should: 

(1) Open contacts LINE 1 to M1 

(2) Close contacts LINE 2 to M2. 

2.

  

If the ambient temperature is above 50°F (10°C): 

a.

  

Immerse at least one foot of the element in ice water 

(or wrap same in ice). 

b.

  

As the element drops through the setpoint: 

(1) LINE 1 to M1 contacts should close. 

(2) LINE 2 to M2 contacts should open. 

c.

  

Remove the element from the ice water (or ice 

wrapping). 

d.

  

As ambient temperature rises to 5°F (3°C) the set-

point, there should be no effect on contact positions. 

e.

  

Pushing the manual reset button should: 

(1) Open contacts LINE 1 to M1. 

(2) Close contacts LINE 2 to M2. 

95-7432–1 

996-496 Rev. A 

Summary of Contents for L482A

Page 1: ...oller case and bellows where ambient temperature is always warmer than the set point 3 For settings above the scale range midpoint it can be necessary to locate the controller case close to a steam pipe or other warm surface and make sure the element does not extend across a cold surface Controller Surface mount the controller Fig 1 vertically on any Fig 1 L482A Low Limit Controller dimensions in ...

Page 2: ...al straps Fig 3 Fig 2 Element mounted to duct with CCT2600 Clips Fig 3 Element mounted in duct with perforated metal straps C789 GROMMET ELEMENT CLIP DETAIL USE NO 10 SHEET METAL SCREWS BEND HERE IF NECESSARY C790 WIRE FASTENINGS ELEMENT PERFORATED METAL STRAPS OPERATION On a temperature drop to setpoint LINE 1 to M1 contacts close and LINE 2 to M2 contacts open Reset to the normal state is manual...

Page 3: ...m above sea level CHECKOUT Because of the L482A limited setpoint range operational checkout can be difficult Use one of the following methods to verify proper controller operation 1 If the ambient temperature is below 50 F 10 C a Turn the setpoint adjustment through the ambient temperature and note the switch action b When the setpoint is increased to equal the ambient temperature 1 LINE 1 to M1 c...

Page 4: ...eywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 996 496 Rev A Printed in U S A on recycled 95 7432 1 B B Rev 4 04 paper containing at least 10 www honeywell com post consumer paper fibers ...

Reviews: