Honeywell L4064R Installation Instructions Download Page 3

L4064B, L4064R UNIVERSAL COMBINATION FAN AND LIMIT CONTROLLERS

3

69-0115—11

Fig. 3. Swivel mount (front view).

WIRING

Disconnect power supply before beginning 
installation to prevent electrical shock or equipment 
damage. All wiring must comply with local electrical 
codes and ordinances or in the absence of local codes 
with the National Electrical Code ANSI Cl-1981-NFPA 
70. Follow burner or furnace manufacturer’s 
instructions if available; otherwise, see Fig. 5 and 
proceed as follows.

IMPORTANT

The brass jumper is the breakaway type. It 
must be removed when the limit is used in the 
low voltage circuit. To remove jumper, break 
with a needlenose pliers and remove com-
pletely. Once removed, it is not replaceable. 
See Fig. 5 
for location.

1.

If cable is used, we recommend using a strain-
relief bushing in the knockout. Bushing is pro-
vided with control.

2.

Refer to the following section for type of wiring 
connections (standard wire push-in terminals or 
female receptacle).

Fig. 4. Wiring Diagram for L4064.

Wiring Connections

When connecting cable or conduit to this controller, 
use care to avoid strain on the control case. 
Connections can be made to standard wire push-in 
terminals or female receptacles for 1/4 in. (6.4 mm) 
male flag connectors on both the fan and limit 
switches (Fig. 5).

For Standard wire Push-in terminals

Connect wires to the terminals as follows:

1.

Use Nos. 14,16, or 18 solid wire or Nos. 14 or 16 
stranded wire, depending on electrical require-
ment.

2.

Strip insulation from wires the distance shown 
by the strip gauge on the controller. If wire insu-
lation is 4/64 in. (2 mm) thick, strip additional 
1/4 in. (6 mm) to ensure wire seats securely in 
push-in connectors.

3.

Solid wire may be inserted directly into the ter-
minal holes. If stranded wire is used, insert a 
small screwdriver into the slot next to the termi-
nal. Push screwdriver in and hold while inserting 
wire into terminal (Fig. 5). Remove screwdriver. If 
stranded wire is solder-dipped, it can be pushed 
directly into terminal holes.

For Female Receptacles

It is recommended that the female receptacles be 
used for wiring accessory equipment; i.e., electronic air 
cleaner, humidifier, etc. Connect wires to the 
receptacles as follows:

1.

Use Nos. 14 to 18 size wire, depending on elec-
trical requirement.

2.

Attach 1/4 in. (6.4 mm) male flag connector to 
each wire.

M34080

L4064

A

B

FAN

SIDE

FAN

MOTOR

JUMPER

REMOVED

JUMPER

IN PLACE

POWER

SUPPLY

(HOT)

L1

L2

L1

L2

(HOT)

POWER

SUPPLY

ADD DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

TO CONTROLLED LOW VOLTAGE EQUIPMENT.

LIMIT

SIDE

L4064

FAN

SIDE

LIMIT

SIDE

FAN

MOTOR

1

1

1

2

2

2

TO CONTROLLED LINE VOLTAGE EQUIPMENT.

3

3

POWER

SUPPLY

HEATING

SYSTEM

TRANSFORMER

JUMPER

REMOVED

24V

120V

(HOT)

L1

L2

1

FAN

MOTOR

M31165A

L4064

C

FAN

SIDE

LIMIT

SIDE

Summary of Contents for L4064R

Page 1: ...N OFF setting is reached If the call for heat continues until the temperature in the plenum rises to the LIMIT setting the bimetal element will mechanically break the limit contacts and de energize the heating control circuit INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to fol low them could damage the product or cause a hazardous condition 2 Check the rati...

Page 2: ... 20 6 mm hole Surface Mounting Fig 1 L4064B Hole in plenum should be just large enough to accommodate the 3 4 in 19 1 mm diameter element tube A 13 16 in 20 6 mm diameter hole is recommended 1 Remove cover by removing screw squeezing sides and pulling off Insert element in plenum and mark location of mounting holes Make sure the case is snug against the plenum before marking the mounting holes 2 P...

Page 3: ...Fig 5 For Standard wire Push in terminals Connect wires to the terminals as follows 1 Use Nos 14 16 or 18 solid wire or Nos 14 or 16 stranded wire depending on electrical require ment 2 Strip insulation from wires the distance shown by the strip gauge on the controller If wire insu lation is 4 64 in 2 mm thick strip additional 1 4 in 6 mm to ensure wire seats securely in push in connectors 3 Solid...

Page 4: ...n is complete disconnect the fan motor circuit at the L4064 Turn on power and set thermostat to call for heat Burner should come on and limit controller should shut burner off when plenum temperature reaches the limit set point Turn off power reconnect the fan switch turn on power and again set thermostat to call for heat The fan should start when plenum temperature has reached fan on setting Fig ...

Reviews: