INSTALLATION INSTRUCTIONS

69-0115-11

L4064B, L4064R 
Universal Combination Fan and 
Limit Controllers

APPLICATION

These combination warm air fan and limit controllers 
are suitable for various types of forced air heating 
systems. The controllers have 2 switches; one which 
opens the limit circuit if the plenum temperature 
exceeds the preset safety limit; it resets automatically. 
The other switch turns the fan on and off. The fan is 
turned on and off according to plenum temperature. 
The L4064R has a special high temperature range 
suitable for gravity heating systems. All models may 
be used as limit controllers by wiring only the limit 
side. Limit contacts are suitable for both line voltage 
and low voltage. For low voltage applications, the 
brass jumper must be removed.

OPERATION

As the plenum temperature rises, the coiled bimetal 
sensing element of the control warps and 
mechanically makes the fan contacts (at the FAN ON 
temperature setting). During normal operation, the 
call for heat ends before the LIMIT setting is reached 
and the fan contacts break as the plenum 
temperature falls and the FAN OFF setting is reached. 
If the call for heat continues until the temperature in 
the plenum rises to the LIMIT setting, the bimetal 
element will mechanically break the limit contacts 
and de-energize the heating control circuit. 

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to fol-
low them could damage the product or cause a 
hazardous condition.

2.

Check the ratings given in the instructions and 
on the product to make sure the product is suit-
able for your application.

3.

Installer must be a trained, experienced service 
technician.

4.

For 230 VAC application, use of double insu-
lated cable is required.

5.

After installation is complete, check out product 
operation as provided in these instructions.

WARNING

If limit switch is used on a low voltage 
circuit, failure to remove brass jumper can 
cause electrical shock hazard and/or 
damage to low voltage controls.

CAUTION

 

1.

Disconnect power supply before connecting 
wiring to prevent electrical shock or equipment 
damage.

2.

When connecting cable or conduit to control, 
avoid straining the control case.

Follow furnace or burner manufacturer’s instructions,
if available. Maximum element temperature is:
  L4064B—350 ºF (177 ºC).
  L4064R—250 ºF (121 ºC) above limit setting.
Maximum switch temperature is:
  L4064B,R—190 ºF (88 ºC).

Summary of Contents for L4064R

Page 1: ...N OFF setting is reached If the call for heat continues until the temperature in the plenum rises to the LIMIT setting the bimetal element will mechanically break the limit contacts and de energize the heating control circuit INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to fol low them could damage the product or cause a hazardous condition 2 Check the rati...

Page 2: ... 20 6 mm hole Surface Mounting Fig 1 L4064B Hole in plenum should be just large enough to accommodate the 3 4 in 19 1 mm diameter element tube A 13 16 in 20 6 mm diameter hole is recommended 1 Remove cover by removing screw squeezing sides and pulling off Insert element in plenum and mark location of mounting holes Make sure the case is snug against the plenum before marking the mounting holes 2 P...

Page 3: ...Fig 5 For Standard wire Push in terminals Connect wires to the terminals as follows 1 Use Nos 14 16 or 18 solid wire or Nos 14 or 16 stranded wire depending on electrical require ment 2 Strip insulation from wires the distance shown by the strip gauge on the controller If wire insu lation is 4 64 in 2 mm thick strip additional 1 4 in 6 mm to ensure wire seats securely in push in connectors 3 Solid...

Page 4: ...n is complete disconnect the fan motor circuit at the L4064 Turn on power and set thermostat to call for heat Burner should come on and limit controller should shut burner off when plenum temperature reaches the limit set point Turn off power reconnect the fan switch turn on power and again set thermostat to call for heat The fan should start when plenum temperature has reached fan on setting Fig ...

Reviews: