BCU 480 · Edition 03.16l
74
Technical data
9 Technical data
Mains voltage:
230 V AC, -15/+10%, 50/60 Hz,
115 V AC, -15/+10%, 50/60 Hz,
for grounded and ungrounded mains.
Inherent consumption: approx. 9 VA plus inherent con-
sumption of the integrated ignition transformer [50/60
Hz].
Voltage to inputs and valves = mains voltage.
Signal and control line: max. 2.5 mm
2
(AWG 14).
Cable for burner ground/PE wire: 4 mm
2
(AWG 12).
Cable gland:5 cable glands with multiple seal inserts for
2 cable diameters of up to 7 mm,
BCU..P: with 2 cable glands with multiple seal inserts
for 4 cables of up to 7 mm in diameter and an industrial
chassis plug.
Each BCU is supplied for two cable glands with one seal
insert each for cable diameters between 7 and 12 mm.
Input voltage of signal inputs:
Rated value
115 V AC
230 V AC
Signal “1”
80 – 126.5
160 – 253
Signal “0”
0 – 20
0 – 40
Frequency
50/60 Hz
50/60 Hz
Input current of signal inputs:
Signal “1”: typ. 2 mA
Output current:
max. 1 A, cos
ϕ
= 1, for the valve outputs (or SRC out-
puts),
but total current for valves and ignition transformer:
max. 2.5 A
Fail-safe inputs and outputs:
All the inputs and outputs marked “ ” (see connection
diagrams) may be used for safety tasks.
Flame control with UV sensor or ionization sensor.
Flame signal for
ionization control: 1 – 28
μ
A,
UV control: 1 – 35
μ
A.
For intermittent or continuous operation.
Maximum length of ignition cable with integrated elec-
tronic ignition: 5 m (16.4 ft).
Maximum length of ionization/UV cable: 50 m (164 ft).
▼