Application
1 .1 .3 Modulating-controlled burner
Control: Main burner continuous
The butterfly valve for air BV is
moved to ignition position in order
to start the main burner. The main
burner can be started at low-fire
rate after the operating signal from
the pilot burner has been detected.
The control system controls the
burner capacity via the butterfly
valve for air BV after the operating
state has been signalled. Pilot and
main burners can be operated si-
multaneously.