Checking the usage

DG..H, DG..N, DG..I

For monitoring increasing and decreasing gas or 
air pressure.

-6  -5  -4  -3  -2  -1   0  1  2  3  4  5  6

Increasing

negative pressure

Decreasing

negative pressure

Increasing pressure

Decreasing pressure

Positive pressure

Negative pressure

DG..H, 
DG..N

Gas, air, flue gas Air, flue gas

DG..I

Air, flue gas

Gas, air, flue gas

DG..H switches and locks off with rising pressure, 
DG..N switches and locks off with falling pressure. 

They can be unlocked using the manual reset.
This function is only guaranteed when used within 

the specified limits – see page 7 (Technical data).

Any other use is considered as non-compliant.

Type code

Code

Description

DG

Pressure switch for gas

1,5 – 500

Max. setting in mbar

I

Locks off with rising pressure 

Locks off with falling pressure 

Negative pressure for gas

G

With gold-plated contacts

 

- 

-4 

-5 

-6 

-9

Electrical connection  

via screw terminals 

via screw terminals, IP 65 

4-pin plug, without socket 

4-pin plug, with socket 

4-pin plug, with socket, IP 65

K 

T 

N

Red/green pilot LED for 24 V DC/AC 

Blue pilot lamp for 230 V AC 

Red/green pilot LED for 230 V AC 

Blue pilot lamp for 120 V AC

A

External adjustment

Part designations

1

2

3

5

4

1

  Upper housing section with cover

  Lower housing section

  Hand wheel

4

  M16 cable gland

5

  DG..H, DG..N with manual reset

Type label

DG

2
1

3

D-49018 Osnabrück, Germany

CE

Max. inlet pressure p

max. 

= withstand pressure, mains 

voltage, ambient temperature, enclosure: see type 

label.

Installation

 CAUTION

Please observe the following to ensure that the DG 
is not damaged during installation and operation:

–    Continuous operation with gases containing more 

than 0.1 %-by-vol. H

2

S or ozone concentrations 

exceeding 200 µg/m³ accelerate the ageing of 
elastomer materials and reduce the service life.

–   Dropping the device can cause permanent dam-

age. In this event, replace the entire device and 
associated modules before use.

–   Use approved sealing material only.
–   Check max. ambient temperature  – see 

page 7 (Technical data).

–   When using silicone tubes, only use silicone 

tubes which have been sufficiently cured.

–   Vapours containing silicone can adversely affect 

the functioning of electrical contacts.

–   Condensation must not be allowed to get into 

the housing. At subzero temperatures, malfunc-
tions/failures due to icing can occur.

–    When installing outdoors, place the DG in a 

roofed area and protect from direct sunlight 
(even IP 65 version). To avoid condensation, a 
cover with pressure equalization element (see 
page 6 (Pressure equalization element)) can 
be used.

–  Avoid strong impact on the unit.
–   In case of highly fluctuating pressures, install 

a restrictor orifice (see page 6 (Restrictor 
orifice)).

 

The DG must not be in contact with masonry. 

Minimum clearance 20 mm.

 

Ensure that there is sufficient installation space.

 

Ensure unobstructed view of the hand wheel.

 

Installation position as required, preferably with 
vertical diaphragm. Then the switching point p

S

 

corresponds to the scale value SK set on the 
hand wheel. In other installation positions, the 
switching point p

S

 will change and no longer 

correspond to the scale value SK set on the 
hand wheel. Check the switching point.

Summary of Contents for Krom Schroder DG H Series

Page 1: ...tes possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 11 17 The following chapters have been changed Adjustment Technical da...

Page 2: ... Installation CAUTION Please observe the following to ensure that the DG is not damaged during installation and operation Continuous operation with gases containing more than 0 1 by vol H2S or ozone concentrations exceeding 200 µg m accelerate the ageing of elastomer materials and reduce the service life Dropping the device can cause permanent dam age In this event replace the entire device and as...

Page 3: ...et at port 3 4 On IP 65 units the filter pad is fitted as standard see type label 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply 3 Ensure that the pipeline is clean 4 Purge the pipe Installing DG H DG N Positive pressure measurement at port 1 5 Seal port 2 1 2 Rp 1 4 1 2 0 Positive pressure measurement at port 2 5 Seal port 1 1 Rp 1 2 pmax Rp 1 4 2 Rp 1 4 0 Nega...

Page 4: ...maged during opera tion note the switching capacity see page 7 Technical data In the case of low switching capacities such as 24 V 8 mA for example we recommend using an RC module 22 Ω 1 μF in air containing silicone or oil NO C 1 µF R 22 2 NC 1 COM 3 1 Disconnect the system from the electrical power supply M16 x 1 5 ø 4 10 mm 3 4 2 5 6 7 Contacts 3 and 2 close when subject to increas ing pressure...

Page 5: ...essure and pos sible reset Mean switching differential at min and max set ting Deviation from the switching point during testing pursuant to EN 1854 Gas pressure switches 15 Air pressure switches Deviation DG H N I 15 DG 1 5I 15 or 0 4 mbar DG 12I 15 or 0 5 mbar DG 18I 15 or 0 5 mbar If the DG does not trip at the desired switch ing point correct the adjusting range using the hand wheel Relieve th...

Page 6: ...tion of condensation the cover with pressure equalization element can be used The diaphragm in the screw connector is designed to ventilate the cover without allowing water to enter Order No 74923391 Restrictor orifice In the case of high pressure fluctuations we recom mend using a restrictor orifice contains non ferrous metals R Rp Hole diameter 0 2 mm Order No 75456321 hole diameter 0 3 mm Order...

Page 7: ...of the elastomer ma terials and reduces the service life please contact manufacturer Enclosure IP 54 or IP 65 Safety class 1 This unit is not suitable for cleaning with a high pressure cleaner and or cleaning products Mechanical data Gas type natural gas town gas LPG gaseous flue gas biogas max 0 1 by vol H2S and air Max inlet pressure pmax withstand pressure see page 5 Adjustment Max test pressur...

Page 8: ...ithout delay Check that the delivery is complete see page 2 Part designations Storage Storage temperature see page 7 Technical data Storage is subject to the ambient conditions de scribed Storage time 6 months before using for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time Packaging The packaging material is ...

Reviews: