ISA100_GET_INITIAL_INFO
28
Get the initial information serial number
and device tag descriptor from the sensor.
ISA100_ADD_UAP_ALARM
30
Add alarm message received from UAP to
ARMO queue
ISA100_NOTIFY_RESET_CMD
120
Radio issues the command to reset the
UAPMO
ISA100_NOTIFY_TAI_TIME
121
Radio sends the TAI time to the sensor
board every 20 seconds
ISA100_NOTIFY_UAP_STATUS
129
Read Request /Response for the UAP
status
ISA100_NOTIFY_POWER_STATUS
130
Sensor sends power supply status to
radio
ISA100_NOTIFY_DEVICE_INFO
131
Sensor sends the serial number and
device tag description to the Radio
ISA100_NOTIFY_ALARM_REGEN_BEGIN
140
Radio issues Alarm regen to sensor when
system issues the Alarm recovery
ISA100_NOTIFY_ALARM_REGEN_END
141
Sensor generates Alarm Regen end when
all pending alarms are generated
ISA100_NOTIFY_RSSI_RSQI
151
Sensor gets the RSSI and RSQI value from
the device and updates in the LCS display
Initial Information Related Messages
ISA100_GET_INITIAL_INFO
On reset, the Radio requests the initial information from the Sensor as per the packet
format in the following table.
Sync
h
Byte
Packe
t
Lengt
h
Packe
t
Class
Packe
t
Type
Packe
t ID
Packe
t size
Checksum
LSB
Checksu
m MSB
0x5A
0x04
0x30
0x1C
0x9C
0x00
XX
XX