Honeywell INNCOM e7 Installation Instructions Manual Download Page 4

SETUP HVAC TYPE 

'Floe 

1-flc 

nn 

uu 

61 ..... 

1. After HAC is displayed, press MODE.

2. Set the HVAC type desired using the UP/DOWN arrow

buttons to choose one of the following options:

00:  Not Defined. 

FC4: 4 pipe fan coil unit (also applicable to 2-pipe 

without a changeover - cold water only with electric 

heat). 

FW2: 2 pipe fan coil unit with back-up electric heat 

(requires a pipe temperature sensor to detect 

seasonal water temperature change over). 

FC2: 2 pipe fan coil unit without back-up electric heat 

(requires a pipe temperature sensor to detect 

seasonal water temperature change over). 

PAC: 

PTAC unit. 

HbW:Heat Pump B with W2 assist (default 

compressor signal (Y) is cooling, reverse valve and 

compressor signals (B + Y) required concurrently 

for heating. When applicable, 2nd stage heat signal 

(W2) is engaged in addition to compressor and 

reversing valve (B+Y+W2). Use this HVAC type 

also for Heat Pumps B without 2nd stage heat. 

HpB: Heat Pump B with W2 replace (default 

compressor signal (Y) is cooling, reverse valve and 

compressor signals (B + Y) required concurrently 

for heating. When applicable, 2nd stage heat signal 

(W2) is engaged by itself, releasing the compressor 

(Y) and reversing valve (B) signals.

HoW:: Heat Pump O with W2 assist ( default 

compressor signal (Y) is heating, reverse valve and 

compressor signals (0 + Y) required concurrently 

for cooling. When applicable, 2nd stage heat signal 

(W2) is engaged in addition to the compressor 

(O+W2). Use this HVAC type also for Heat Pumps 

0 without 2nd stage heat. 

HpO: Heat Pump O with W2 replace (default 

compressor signal (Y8 is heatmg, reverse valve and 

compressor signals (  + Y) required concurrently 

for cooling, when applicable! 

Znd 

stage heat signal

(W2) is engaged by itself, re easing tlie compressor 

(Y) signal.

3. Press FAN to accept the value. The unit 

beeps 

to confirm

the value has been set.

4. The display will show - -. Press the DOWN arrow button

to display the Fan speed (FAN) menu, then press

MODE.

36-00012-01 

SETUP FAN SPEED 

'Floe 

FRn 

nn 

uu 

O IMooe 

1. Once FAN is displayed, use the Up/DOWN arrow but-

tons to choose the fan speed:

00:  Not Defined 

Lo:  Low Speed (single speed) 

LH:  Low / High 

LMh:Low /Medium*/ High 

*For heat pump models utilizing reversing valve,

medium heat and medium fan speed will not be

available.

2. Press FAN to execute the setting, the unit 

beeps 

to con­

firm it is set.

EXIT INITIALIZATION MODE 

'Floe 

FRn 

Str 

MOO[ 

When setup is complete, exit INITIALIZATION MODE by 

pressing the F 

IC 

key. Sir is displayed, indicating the setup 

values are stored in memory, the unit reboots and begins 

operating the HVAC equipment as configured. 

RESETTING INITIALIZATION MODE 

'Floe 

rSI: 

25s 

� 

•�aoe: 

If the user needs to return to the settings made in 

INITIALIZATION MODE, do the following: 

1. Enter SERVICE MODE: Press and hold F/C, Press and

hold MODE, Press and hold FAN, Release all three but­

tons.

2. Use the UP/DOWN arrow buttons to display rst, then

press MODE.

3. Use the DOWN button to select 255.

4. Press FAN.

5. The unit will reset, clear all previous values, and enter

INITIALIZATION MODE again.