Honeywell INNCOM E529 Product Manual Download Page 8

E529 Product Guide 

 

Rev 2.0 3/20/2017

 

8

 

 

 

batteries are completely installed with the right polarities and that the 

batteries are not dead. Just after startup the E529 will cycle through RF 

Channels 26, 25, 24… all the way to 11 and send a 0x00061 Battery 

Powered thermostat exchange message on each RF Channel looking for 

a reply from an HVAC thermostat partner with the same Room ID 

currently stored in the E529.4G. You will typically not have the HVAC 

partner configured yet. Just allow this process to continue until 

completion. You will be configuring the actual Room ID and other 

required parameters into the E529.4G later. 

5.  Hook the tabs at the top rear of the E529.4G housing into the matching 

depressions at the top of mounting plate and rotate the bottom of the 

E529.4G housing toward the wall until it snaps into the place on the 

mounting plate. Secure the E529.4G housing to the mounting plate with 

the two small screws provided with the E529.4G. The screws thread into 

two small holes on the bottom of the E529.4G housing. 

 
 

Technical Specifications 

     Table 7. Technical Specifications 

 

FCC Statement 

This equipment has been tested and found to comply with the limits for Class B 

digital device, pursuant of part 15 of the FCC Rules. These limits are designed 

to provide reasonable protection against harmful interference in a residential 

installation. This equipment generates, uses and can radiate radio frequency 

energy and, if not installed and used in accordance with the guarantee that 

interference will not occur in a installation. If this equipment does cause 

harmful interference to radio or television reception, which can be determined 

by turning the equipment off and on, the user is encouraged to try to correct 

the interference by one or more of the following measures: 

 

Reorient or relocate the receiving antenna. 

 

Increase the separation between the equipment and receiver. 

 

Connect the equipment into an outlet on a circuit different from that to 

which the receiver is connected. 

 

   Consult the dealer or experienced radio/TV technician for help 

 

Dimensions 

4.7” W x 4.7” H x 1.2” D (119mm x 119nn x 30mm) 

Operating Range  

41ºF to 149ºF (5ºC to 65ºC) 

Temperature  

± 

1ºF-60ºF to 85 ºF (

± 

5ºC-15ºC to 30ºC)

 

Power in  

Four AA Batteries  

Summary of Contents for INNCOM E529

Page 1: ...Page 1 Overview and General Concept Page 2 Application Page 3 Features Page 4 LCD Item Descriptions Page 5 Back and Bottom Features Page 6 Wireless Communication Page 6 Installation Page 7 Placement Page 7 Mounting Instructions Page 7 Technical Specifications Page 8 FCC Statement Page 8 Document Revision History Page 9 ...

Page 2: ...ol the room HVAC unit It can only measure temperature an optionally humidity and report this to its HVAC controller partner The E529 4G has no IR Eye or S5 Bus installed and only communicates with other devices via RF The HVAC partner in the room must be equipped with a Deep Mesh Layer X radio or S5 Bus connected to a radio equipped device such as a PC502 4G Appendix 4 shows typical installations ...

Page 3: ...equirements to central servers It comes standard with five relays and can be equipped with a radio frequency RF transceiver and Passive Infrared PIR motion detector The e529 interfaces with all common HVAC unit voltage configurations 24 volt to 277 volt The e529 can be installed in a wireless INNCOM guestroom control system which makes installation feasible and affordable in either new constructio...

Page 4: ...gain sets medium MED and another press sets high HI The fan speed cycle begins again with the next push 7 DISPLAY Cycles the LCD between the Set selected temperature and the measured Room temperature Outdoor temperature may also be displayed if the system is networked to a server or the Web broadcasting readings from an outside sensor 8 ecoMODE button Optional Feature Pressing this button allows t...

Page 5: ...nline and connected to the INNCOM server NOTE As of 6 2016 this feature DOES NOT currently work if using a CBL32 Room Gateway such as an E528 4G or PC502 4G You will NOT get a Dot on the E529 display You must use the E529 rUn2 WAN Test to check that the room is connected to the network 7 HVAC Control Mode AUTO displayed when HVAC control is in AUTO Mode 8 Fan Speed LO MED or HI Displayed when FAN ...

Page 6: ... room to be used for energy management 4 ES 1 Key Header Used to copy new software from the ES 1 Key to the E529 Wireless Communication 2 4HHz Wireless RF Table 1 E529 RF Performance 0dB 20dB RF Data Rate 250kbps 250kbps Antenna Type SMT SMT Indoor Range 70ft 100ft Outdoor RF line of site range 540ft 1000ft Transmit Power 1mW 10mW Receive Sensitivity 94 6dBm 94 6dBm Frequency Band 2 4GHz 2 4GHz En...

Page 7: ... from the E529 4G body and then pull the mounting plate down NOTE If the back mounting plate is rotated more than 2 or 3 degrees the plastic tabs at the top of the plate may fracture or break off 2 Attach the mounting plate to the wall or electrical box with the arrow embossed on the mounting plate pointing upward The E529 4G is provided with four 6 32 sheet metal screws for mounting the plate to ...

Page 8: ...the E529 4G housing Technical Specifications Table 7 Technical Specifications FCC Statement This equipment has been tested and found to comply with the limits for Class B digital device pursuant of part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequen...

Page 9: ...tions or warranties with respect to this document In no event shall Honeywell be liable for technical or editorial omissions or mistakes in this document nor shall it be liable for any damages direct or incidental arising out of or related to the use of this document No part of this document may be reproduced in any form or by any means without prior written permission from Honeywell Copyright 201...

Reviews: