background image

LS10143-001SK-E

Control Panel Installation

4-22

4.8

5815XL Installation

The 5815XL SLC expander lets you add additional addressable devices. The maximum number of SD SLC 
devices per panel is 2032. The number of 5815XL’s is limited by the maximum number of SBUS devices. 

Note: 5815XL will only support SD protocol devices on this panel

To install the 5815XL:

1.

Make sure power is off at the panel.

2.

Mount the 5815XL in the IFP-2100/ECS cabinet, the RPS-1000 cabinet, or the 5815RMK remote mounting 
kit. Use the standoffs located under the control panel board assembly and secure with screws provided with 
the 5815XL. For additional information see Model RPS-1000 Installation Instructions (P/N 151153) or 
5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).

3.

Connect the 5815XL to the control panel. (See Section 4.8.1.)

4.

Use on-board DIP switches to select an SBUS ID#. (See Section 4.13.1.) 

5.

Add the 5815XL module to the system through programming. JumpStart will add the module automatically 
(see Section 8.1). You can also add it manually (see Section 9.2.2). Select a name, if desired (see Section 
9.2.1.2).

You are now ready to connect SLC devices to the 5815XL (see Section 7.6).

Figure 4-31 is a drawing of the 5815XL board, showing the location of terminals and DIP switches.

Figure 4-31  5815XL Board

4.8.1

5815XL Connection to the Panel

Connect the 5815XL to the control panel as shown in Figure 4-32. After the 5815XL is connected to the panel, it 

DIP switches for

setting IDs

To panel via SBUS

To SLC loop

Summary of Contents for IFP-2100

Page 1: ...Document LS10143 001SK E Rev B ECN 17 0364 Installation and Operation Guide IFP 2100 ECS RFP 2100 Analog Addressable Fire System Emergency Communication System ...

Page 2: ...arning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explo sions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reach...

Page 3: ...ith a normal room temperature of 15 27º C 60 80º F Verify that wire sizes are adequate for all initiating and indi cating device loops Most devices cannot tolerate more than a 10 I R drop from the specified device voltage Like all solid state electronic devices this system may operate erratically or can be damaged when subjected to light ning induced transients Although no system is completely imm...

Page 4: ...tent you think should be improved or corrected Your suggestion for how to correct improve documentation To order parts contact Honeywell Silent Knight inside sales at 800 328 0103 eVance Farenhyt are trademarks and Honeywell Silent Knight and SWIFT are registered trademarks of Honeywell International Inc Microsoft and Windows are registered trademarks of the Microsoft Corporation Chrome and Google...

Page 5: ...ements for Remote Station Protected Fire Alarm Systems 3 2 2 5 Requirements for the Installation of Carbon Monoxide CO Detection and Warning Equipment NFPA 720 3 2 2 6 NFPA Requirements 3 Section 3 Before You Begin Installation 1 3 1 Inventory 1 3 2 Environmental Specifications 1 3 3 Software Downloads 1 3 4 Electrical Specifications 2 3 5 Wiring Specifications 4 3 6 Board Assembly Diagram 6 3 7 C...

Page 6: ...h Mounting 17 4 7 1 2 Surface Mounting 19 4 7 2 Model RA 100 Connection to the Panel 20 4 8 5815XL Installation 21 4 8 1 5815XL Connection to the Panel 21 4 9 6815 Installation 22 4 9 1 6815 Connection to the Panel 23 4 10 5824 Serial Parallel Interface Module Installation 24 4 10 1 Selecting 5824 Options 24 4 11 5880 LED I O Module 26 4 11 1 5880 Board Layout 26 4 11 2 FACP Connection 26 4 11 3 L...

Page 7: ... L8 Module 43 4 17 5 Transmitter Activated by Dry Contacts 44 Section 5 Networking 1 5 1 Network System Hardware Features 1 5 1 1 Networked Sites 1 5 1 2 Wiring Options to Connect Networked Panels 1 5 2 Model RFP 2100 1 5 3 Network Wiring 1 5 4 SK NIC Wiring Options 3 5 4 1 Fiber Loop Modules 3 5 4 1 1 Accessory Mounting Kits 4 5 4 2 SK NIC Installation 4 5 4 2 1 Unshielded Twisted Pair Wiring bet...

Page 8: ...uirements for SLC Devices 4 7 6 1 Wire Sizing on 5815XL for SD Devices 5 7 6 2 Wire Sizing for 6815 5 7 6 3 Wiring Requirements for IDP or SK Modules 5 7 6 4 Wiring 5815XL or 6815 in Style 6 7 Class A Configuration 6 7 7 Addressing IDP or SK SLC Devices 7 7 8 Wiring SD Detectors 8 7 9 Addressing SD Devices 8 7 9 1 SLC Devices with DIP Switches 10 7 10 Wiring the WIDP WGI or SK WGI 11 7 10 1 Power ...

Page 9: ...ts 9 9 4 3 Edit OPG Template 9 9 5 Point 9 9 5 1 Point Programming For 5815XL Module 9 9 5 2 Point Programming For 6815 Module 12 9 5 3 Point Programming For Internal or External Power Module RPS 1000 15 9 5 4 Point Programming For 5880 5865 Modules 17 9 5 5 Point Programming for 5496 17 9 5 6 Point Programming for ECS AMP 18 9 5 7 Point Programming for ECS VCM ECS NVCM or ECS RVM 19 9 6 System Op...

Page 10: ...nu Overview 2 10 3 2 Using the Menus 3 10 4 Basic Operation 3 10 4 1 Setting Time and Date 3 10 4 2 Disable Enable a Point 3 10 4 2 1 Disable Enable NACs by Template 3 10 4 2 2 Disable Enable NACs by Group 3 10 4 2 3 Disable Enable Zone Points 3 10 4 2 4 Disable Enable Point 4 10 4 2 5 Inhibit Output Group 4 10 4 3 View Event History 4 10 4 3 1 To clear the event history 4 10 4 4 Conduct a Fire Dr...

Page 11: ...1 1 ECS Control Key 1 11 2 1 2 ECS Control LED 2 11 2 1 3 ECS Message Keys 2 11 2 1 4 ECS Message LEDs 2 11 2 1 5 Select Keys 2 11 2 1 6 Select Key LEDs 2 11 2 2 Gaining ECS Control 3 11 2 2 1 LOC Priority 3 11 2 2 2 LOC Lockout 3 11 2 2 3 User Profile Access Control 4 11 2 3 Manual ECS 4 11 2 3 1 Switching between Microphone Mode and Message Mode 4 11 2 3 2 Activating Output Groups Dynamically 4 ...

Page 12: ...rk Paging 16 11 9 0 1 Priority 16 11 9 0 2 Configuration 17 Section 12 Reporting 1 12 1 Receivers Compatible with the Control Panel 1 12 2 SIA IntelliKnight IFP 2100 ECS Panels PI Modifier Reporting 13 12 3 SIA IFP 2100 ECS Panel Communicator 14 Section 13 Testing and Troubleshooting 1 13 1 Troubleshooting 1 13 2 Common Problems 1 13 3 Periodic Testing and Maintenance 2 13 4 Event History 3 13 5 B...

Page 13: ... the Built In Programmer 1 Appendix C Cadence Patterns 1 Appendix D Expanded Receiver Panel Relationship 1 Panel Security Manufacturer Warranties and Limitation of Liability Model IFP 2100 Basic Operating Instructions Model IFP 2100ECS Basic Operating Instructions ...

Page 14: ... up to 159 IDP or SK sensors and 159 IDP or SK modules or 127 SD SLC devices Additional SLC loops can be added to increase overall point capacity Additional 6815 SLC expanders supports 159 IDP or SK sensors and 159 IDP or SK modules for a maximum of 2100 points per IFP 2100 ECS control panel Additional 5815XL SLC expander supports only SD Protocol for a maximum of 2032 points per IFP 2100 ECS cont...

Page 15: ...d smoke test requirements for NFPA 72 Automatic day night sensitivity adjustment JumpStart AutoProgramming feature for easy programming Non volatile event history stores 1000 events per panel A choice of output patterns available for notification outputs including ANSI 3 41 temporal signal Built in synchronization appliance support for AMSECO Gentex System Sensor and Wheelock 1 1 4 IFP 2100ECS Fea...

Page 16: ...specifying which outputs are activated when certain events occur in the system Section 8 2 explains mapping in detail Networking Up to 32 panels can be networked Network System Consist of any combination of 32 panels of these model numbers IFP 75 IFP 300 IFP 300ECS IFP 2100 IFP 2100ECS RFP 2100 IFP 2000 or IFP 2000ECS ECS Emergency Communication System SWIFT Smart Wireless Integrated Fire Technolo...

Page 17: ... a max of 31 RA 100 LCD Alarm Annunciator 4x20 LCD annunciator Any combination of supported annunciators for a max of 31 5865 3 and 5865 4 LED Annunciator LED annunciator can display up to 30 LEDs 15 red and 15 yellow 5865 4 has key switches for silence and reset and a system trouble LED 5880 Rev C or above LED I O Module Driver for up to 40 LEDs Interfaces with customized annunciator boards In ad...

Page 18: ...eless heat ROR 135 fixed with 4 base WSK HEAT Wireless Heat 135 fixed with 4 base WSK MONITOR Wireless monitor module WSK RELAY Wireless relay module B210W 6 wireless base Misc 7860 Telephone Cord RJ31X cord for connecting phone line to the IFP 2100 ECS HFSS Honeywell Fire Software Suite For communication and panel programming with a Windows based computer Enables remote viewing of detector status...

Page 19: ...tice is not practical the telephone company will notify the customer as soon as possible Also you will be advised of your right to file a complaint with the FCC if you believe it is necessary The telephone company may make changes in its facilities equipment operations or procedures that could affect the operation of the equipment If this happens the telephone company will provide advance notice i...

Page 20: ...rmation on releasing operation 1 All field wiring must be installed in accordance with NFPA 70 National Electric Code 2 Use the addressable smoke detectors specified in Section 7 1 IDP devices Section 7 2 SK devices or Sec tion 7 3 SD devices Section 7 4 SWIFT devices of this manual and or conventional detectors listed in the compatibility chart in Appendix A 3 Use UL listed notification appliance...

Page 21: ...used 2 2 4 Requirements for Remote Station Protected Fire Alarm Systems Minimum system requirements are one Honeywell Silent Knight addressable initiating device and wither a 5220 Keltron 3158 or the built in Digital Alarm Communicator Transmitter DACT 1 Do not exceed the current draw load restrictions shown in Section 3 7 2 The AC Loss Hours option must be set from 1 3 hours 2 2 5 Requirements fo...

Page 22: ... card Y Y Y Y Y Y Y Y 5220 Direct Conn Module O O Y Y O N O N 5496 Indicating Circuit Expander O O O O O O O O 5815XL SLC Expander O O O O O O O O 5824 Serial Parallel Interface O O O O O O O O 5865 3 4 Remote Annunciator O O O O O O O O 5880 Remote Annunciator O O O O O O O O 5883 Relay Module O O O O O N O N 5895XL Power Module O O O O O O O O 7644 EOL device O O N Y O O O O 6815 SLC expander O ...

Page 23: ...ch Annunciator N N N N N Y O Y ECS VCM Voice Control Module N N N N N Y O Y ECS RVM Remote Voice Module N N N N N Y O Y ECS INT50W Amplifier N N N N N Y O Y Y YES N NO O OPTIONAL 1 At least one of the following amplifiers is required for MNS operation as well as EVAC ECS Dual50W ECS 50 ECS 125 or ECS INT50W Table 2 2 NFPA Requirements for IFP 2100ECS Model Module Description Local Releasing Auxili...

Page 24: ...directly on exterior walls especially masonry walls condensation Do not mount directly on exterior walls below grade condensation Protect from plumbing leaks Protect from splash caused by sprinkler system inspection ports Do not mount in areas with humidity generating equipment such as dryers production machinery When selecting a location to mount the IFP 2100 ECS control panel the unit should be ...

Page 25: ...its 0Ω O 100 mA for initiation circuits X I O 3 Flexput Circuits 24 VDC 3 0 A notification and auxiliary power circuits 0Ω O 100 mA for initiation circuits X I O 4 Flexput Circuits 24 VDC 3 0 A notification and auxiliary power circuits 0Ω O 100 mA for initiation circuits X I O 5 Flexput Circuits 24 VDC 3 0 A notification and auxiliary power circuits 0Ω O 100 mA for initiation circuits X I O 6 Flex...

Page 26: ... IN Used for Class A installations 0Ω SC Ring Phone Line 1 Telco Ring N A 0Ω Tip Phone Line 1 Telco Tip Ring Phone Line 1 Premises Ring Tip Phone Line 1 Premises Tip Ring Phone Line 2 Telco Ring N A 0Ω Tip Phone Line 2 Telco Tip Ring Phone Line 2 Premises Ring Tip Phone Line 2 Premises Tip Battery Battery Connection 24 VDC 1 12 A N A P3 EXT Comm Cellular Connection B input 0Ω A S 55 mA 95 mA S P7 ...

Page 27: ...oute high and low voltages separately Route the wiring around the inside perimeter of the cabinet It should not cross the circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits See Figure 3 2 for an example High frequency noise such as that produced by the inductive reactance of a speaker or bell can also be reduced b...

Page 28: ...Model IFP 2100 ECS Installation Manual LS10143 001SK E 3 5 Figure 3 2 Wire Routing Example for IFP 2100ECS Relay outputs AC Power Input lines SLC Devices To Phone SBUS Devices Battery Battery ...

Page 29: ...the board assembly for repair remove the four mounting nuts which hold the assembly in the cabinet Then lift the entire assembly out of the cabinet Do not attempt to remove the circuit boards from the metal bracket Chassis Mounting Nuts On board Annunciator AC Trouble Relay Phone lines SLC In Out Battery Connections Data USB Port Ethernet Port non power limited Programmable Alarm Relay SBUS In SBU...

Page 30: ...current ratings 5 Make sure that the total alarm current you calculated including current for the panel itself does not exceed 9 0 A This is the maximum alarm current for the IFP 2100 ECS control panel If the current is above 9 0 A you will need to use a notification power expander s such as the 5496 or the RPS 1000 intelligent power expander to distribute the power loads so that the IFP 2100 ECS ...

Page 31: ...m 7 2 mA mA IDP Monitor Standby Alarm 375 mA mA mA IDP Minimon mA mA IDP Pull SA IDP Pull DA mA mA IDP Monitor 2 Standby Alarm 75 mA mA mA IDP Monitor 10 Standby Alarm 3 5 mA mA mA IDP Control SLC Standby 375 mA mA Alarm 375 mA mA Aux Pwr Standby 1 7 mA mA Alarm 7mA mA IDP Control 6 SLC Standby 2 25 mA mA Alarm 2 25 mA mA Aux Pwr Standby 8 mA mA Alarm 20 mA mA IDP Relay Standby Alarm 255 mA mA mA ...

Page 32: ... mA Accessories Modules 6815 SLC Loop Expander 63 max 4 Standby 78 mA mA Alarm 78 mA mA RA 2000 Remote LCD Annunciator 63 max 4 Standby 20 mA mA Alarm 25 mA mA RA 1000 Remote LCD Annunciator 31 max Standby 20 mA mA Alarm 25 mA mA RA 100 Remote LCD Annunciator Standby 25 mA mA Alarm 50 mA mA 5824 Serial Parallel Module 4 max Standby Alarm 45 mA mA mA 5496 NAC Expander 63 max 4 Standby Alarm 10 mA m...

Page 33: ...e 1 Max Standby Alarm 79 mA mA mA Wireless Modules WIDP WGI Wireless Gateway Max current using ext supply 40 mA mA mA Max current SLC Power 24 mA mA mA Total System Current Auxiliary Devices2 Refer to devices manual for current rating IPDACT 2 IP Communicator 1 max Standby 93 mA mA Alarm 136 mA mA IPDACT 2UD IP Communicator 1 max Standby 98 mA mA Alarm 155 mA mA CELL MOD CELL CAB SK Standby 55 mA ...

Page 34: ...umber of Devices column for each IDP PhotoR used with a DNR 7 The DNR housing does not include a Relay circuit board If a relay is needed be sure to add one to the IDP Relay IDP Pho toR Number of Devices column for each DNR used for correct current calculations 3 7 3 Current Draw Worksheet for SK SLC Devices Use Table 3 3 to determine current requirements during alarm battery standby operation whe...

Page 35: ... mA mA mA SK MINIMON mA mA SK PULL SA mA mA SK PULL DA mA mA SK MONITOR 2 Standby Alarm 75 mA mA mA SK MON 10 Standby Alarm 3 5 mA mA mA SK CONTROL SLC Standby 375 mA mA Alarm 375 mA mA Aux Pwr Standby 1 7 mA mA Alarm 7 mA mA SK CONTROL 6 SLC Standby 2 25 mA mA Alarm 2 25 mA Aux Pwr Standby 8 mA mA Alarm 20 mA mA SK RELAY Standby Alarm 255 mA mA mA SK RELAY 6 Standby Alarm 1 45 mA mA mA SK RELAYMO...

Page 36: ... RA 2000 Remote LCD Annunciator 63 max 4 Standby 20 mA mA Alarm 25 mA mA RA 1000 Remote LCD Annunciator 31 max Standby 20 mA mA Alarm 25 mA mA RA 100 Remote LCD Annunciator Standby 25 mA mA Alarm 50 mA mA 5824 Serial Parallel I O Module 4 max Standby Alarm 45 mA mA mA 5895XL Power Supply 63 max Standby Alarm 10 mA mA mA 5496 NAC Expander Standby Alarm 10 mA mA mA 5865 4 LED Annunciator with reset ...

Page 37: ...CT 2 IP Communicator 1 max Standby 93 mA mA Alarm 136 mA mA IPDACT 2UD IP Communicator 1 max Standby 98 mA mA Alarm 155 mA mA CELL MOD CELL CAB SK Standby 55 mA mA Alarm 100 mA mA Alarm Standby mA mA mA Alarm Standby mA mA mA Alarm Standby mA mA mA Alarm Standby mA mA mA Auxiliary Devices Current Notification Appliance Circuits Refer to device manual for current rating 5495 5499 Power Supply 24 VD...

Page 38: ... with a SK DUCT 3 7 4 Current Draw Worksheet for SD SLC Devices Use Table 3 4 to determine current requirements during alarm battery standby operation when SD SLC devices are installed You can install up to 127 SD devices per loop 2032 max per panel Copy this section if additional space is required 1 Total ampere hours required Table 3 4 Current Draw Worksheet for SD SLC Devices Device of Devices ...

Page 39: ... NAC Expander 63 max 5 Standby Alarm 10mA mA mA RPS 1000 Power Supply Standby Alarm 10mA mA mA 5865 4 LED Annunciator with reset and silence switches 63 max 5 Standby 35mA mA Alarm 145mA mA 5865 3 LED Annunciator 63 max 5 Standby 35mA mA Alarm 145mA mA 5880 LED I O Module Standby 35mA mA Alarm 200mA mA 5883 Relay Interface 63 max 5 Standby 0mA mA Alarm 220mA 22 mA per relay mA ECS VCM Voice Contro...

Page 40: ... Communicator Alarm 155 mA mA Standby 98 mA mA CELL MOD CELL CAB SK Standby 55 mA mA Alarm 100 mA mA Alarm Standby mA mA mA Alarm Standby mA mA mA Alarm Standby mA mA mA B Auxiliary Devices Current Notification Devices Refer to devices manual for current rating 5495 5499 Power Supply 24 VDC One input circuit 15 mA mA Both input circuits 30 mA mA Alarm mA mA Alarm mA mA Alarm mA mA Alarm mA mA C No...

Page 41: ...d during that time However during normal operation door holders draw current and must be included in the 9 0A total current that can be drawn from the panel 4 Use next size battery with capacity greater than required 5 Maximum SBUS address capacity is 63 SBUS modules The practical limit is determined by the amount of SBUS bandwidth consumed by each SBUS module See section 4 13 2 6 The FACP can onl...

Page 42: ...in alarm 17AH 535 mA 473 mA 442 mA 18AH 569 mA 506 mA 475 mA 24AH 769 mA 706 mA 675 mA 33AH 1 07A 1 01A 975 mA 35AH 1 14A 1 07A 1 04A 40AH 1 30A 1 24A 1 21A 55AH 1 80A 1 74A 1 71A Table 3 6 Maximum Battery Standby Loads for 90 Hour Standby Rechargeable Battery Size 90 hr Standby 5 min alarm 90 hr Standby 15 min alarm 90 hr Standby 20 min alarm 33 AH N A N A N A 40 AH 347 mA 331 mA 322 mA 55 AH 480...

Page 43: ...d as a fire break The IFP 2100 ECS cabinet can be surface or flush mounted Cabinet base dimensions are 26 H x 20 W If you flush mount the cabinet there should be 1 5 to 1 75 of cabinet extruding from the wall this should be measured from either the top edge or bottom edge to the exterior side of the sheet rock Do NOT flush mount in a wall designated as a fire break Figure 4 1 FACP Cabinet Mounting...

Page 44: ...Figure 3 3 4 2 AC Power Connection The AC terminals are rated at 120VAC 50 or 60 Hz 5A for the IFP 2100 ECS or 240VAC 50 or 60 Hz 2 8A for the IFP 2100 ECSHV Figure 4 2 120 VAC Power Connection for the IFP 2100 ECS Figure 4 3 240VAC Power Connection for the IFP 2100 ECSHV WARNING RISK OF ELECRICAL SHOCK AND EQUIPMENT DAMAGE SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL DISCONNE...

Page 45: ...cabinet The RBB cabinet holds batteries up to the 35 AH size The RBB dimensions are 16 W x 10 H x 6 D 40 64 cm W x 25 4 cm H x 15 24 cm D The AB 55 Accessory cabinet holds batteries up to the 55AH size The AB 55 dimensions are 20 W x 11 5 H x 7 5 D 50 8 cm W x 30 48 cm H x 19 05 cm D 4 3 1 1 Installing the RBB or AB 55 Accessory Cabinet and Batteries To properly install the accessory cabinet and b...

Page 46: ... RBB or AB 55 cabinet no more than 18 away from the main control panel cabinet This will ensure that the battery cables reach the battery terminals Figure 4 5 RBB or AB 55 Cabinet Mounting Holes 2 Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4 6 Figure 4 6 Splicing Control panel Battery Cable to RBB or AB 55 Battery Cable Extenders Cabinet Mountin...

Page 47: ...he two cabinets 4 Connect battery leads to the backup battery terminals See Figure 4 7 Observe the proper polarity to prevent damage to the batteries or the control panel 5 Insert the RBB or AB 55 cover screws into the cover mounting holes See Figure 4 7 Screw the cover screw of the way into the cover mounting hole 6 Align the cover plate mounting keyhole over the cover mounting screws See Figure ...

Page 48: ...ditional 1 amp of SBUS current Wiring distance calculations are done separately for each RPS 1000 and separately for each control panel SBUS Note Refer to Table 3 2 if using IDP SLC devices Table 3 3 for SK devices and refer to Table 3 4 if using SD SLC devices for maximum number of each type of device that can be used per system All devices must use the same SBUS and VBUS After calculating the to...

Page 49: ...e Wiring Distance SBUS Modules to Panel Total Worst Case Current Draw amps 22 Gauge 18 Gauge 16 Gauge 14 Gauge 0 100 1852 ft 4688 ft 6000 ft 6000 ft 0 200 926 ft 2344 ft 3731 ft 5906 ft 0 300 617 ft 1563 ft 2488 ft 3937 ft 0 400 463 ft 1172 ft 1866 ft 2953 ft 0 500 370 ft 938 ft 1493 ft 2362 ft 0 600 309 ft 781 ft 1244 ft 1969 ft 0 700 265 ft 670 ft 1066 ft 1687 ft 0 800 231 ft 586 ft 933 ft 1476 ...

Page 50: ...ng Distance table it can be found that the available options are 370 feet maximum using 22 Gauge wire 938 feet maximum using 18 Gauge wire 1493 feet maximum using 16 Gauge wire 2362 feet maximum using 14 Gauge wire RA 2000 Current Draw 2 x 120 amps 240 amps RPS 1000 Current Draw 1 x 010 amps 010 amps 5865 Current Draw 1 x 200 amps 200 amps 5824 Current Draw 1 x 040 amps 040 amps Total Worst Case C...

Page 51: ...tes SBUS1 Class B configuration SBUS 2 wiring configurations are the same as SBUS1 Figure 4 9 SBUS Class A Wiring Figure 4 10 SBUS Class B Wiring Caution For proper system supervision do not use looped wire under terminals marked A B and of the SBUS device connectors Break wire runs to provide supervision of connections Supervised Power Limited Supervised Power Limited ...

Page 52: ...el 2 Mount the RA 2000 in the desired location see Section 4 5 1 3 Connect the RA 2000 to the panel see Section 4 5 2 4 Use the DIP switches on the back of the RA 2000 to assign an SBUS ID to the RA 2000 see Section 4 13 1 5 The RA 2000 module must be added to the system through programming JumpStart will add the module automatically see Section 8 1 You can also add it manually see Section 9 2 2 S...

Page 53: ...2000 using any of the mounting holes shown in Figure 4 12 Figure 4 12 Backbox Mounting Holes 2 Remove knockout holes as needed for wires See Figure 4 13 for backbox knockout locations Figure 4 13 Backbox Knockout Locations 3 Wire the annunciator board to the main control panel As described in Section 4 5 2 Mounting Holes Mounting Holes Wire Knockouts Wire Knockouts Wire Knockouts ...

Page 54: ...0GRAYTR gray trim ring kits are available for use when surface mounting the RA 2000 1 Remove the desired knock out See Figure 4 13 2 To properly mount the backbox insert a single screw into the key shaped mounting hole Do not tighten all the way See Figure 4 15 Place a level on top of the backbox with the backbox level insert the rest of the mounting screws Figure 4 15 Backbox Surface Mount Holes ...

Page 55: ...the FACP 6 Attach the annunciator and door assembly to the backbox using screws provided see Figure 4 14 4 5 2 RA 2000 Connection to the Panel Connect the RA 2000 to the panel as shown in Figure 4 17 Figure 4 17 Model RA 2000 Connection to the Panel 4 5 3 Temporary Programming Display When an RFP 2100 is being initially setup place an RA 2000 on the panel at address 63 or address 31 for an Supervi...

Page 56: ...ciator Installation The optional Model RA 1000 Remote Annunciator is shown in Figure 4 18 Up to 31 annunciators can be added to the IFP 2100 system Figure 4 18 Model RA 1000 Remote Annunciator Front View RA 1000 installation involves the following steps 1 Make sure power is off at the panel 2 Mount the RA 1000 in the desired location see Section 4 6 1 3 Connect the RA 1000 to the panel see Section...

Page 57: ...rench to remove the set screws located on the bottom of the annunciator bezel See Figure 4 20 for location of the set screws Figure 4 20 Annunciator Backbox and Bezel Details Set screw location Loosen set screws to remove bezel when disassembling annunciator Knockout holes Holes for surface mounting Holes for inserting wires for flush mounting located in all corners Stand off throughout Screw for ...

Page 58: ... following dimensions 8 1 4 w x 6 5 8 h If an electrical box is used the box must be 1 3 8 back from face of wall to accommodate the annunciator see Figure 4 21 2 Remove knockout holes as needed for wires 3 Fit the annunciator backbox into the hole and stabilize with mounting wires Angle the mounting wires into the first hole past the sheet rock Secure the wires behind the screws as shown in Figur...

Page 59: ...surface mounting 1 Drill holes in the surface to match the screw holes on the backbox 2 Fit the trim ring over the backbox 3 Attach the backbox to the surface using screws provided 4 After the annunciator wiring to the panel has been completed described in Section 4 6 2 replace the elec tronic assembly in the backbox Place the bezel over the backbox and tighten the set screws on the bezel 4 6 2 Mo...

Page 60: ...cation see Section 4 5 1 3 Connect the RA 100 to the panel see Section 4 7 2 4 Use the DIP switches on the back of the RA 100 to assign an ID number to the RA 100 see Section 4 13 1 5 The RA 100 module must be added to the system through programming JumpStart will add the module automatically see Section 8 1 You can also add it manually see Section 9 2 2 Select a name if desired see Section 9 2 1 ...

Page 61: ...the RA 100 using any of the mounting holes shown in Figure 4 25 Figure 4 25 Backbox Mounting Holes 2 Remove knockout holes as needed for wires See Figure 4 26 for backbox knockout locations Figure 4 26 Backbox Knockout Locations 3 Wire the Annunciator board to the main control panel See Figure 4 23 Mounting Holes Mounting Holes Wire Knockouts Wire Knockouts Wire Knockouts ...

Page 62: ...trim ring kit is available for use when surface mounting 1 Remove the desired knock out See Figure 4 26 2 To properly mount the backbox insert a single screw into the key shaped mounting hole Do not tighten all the way See Figure 4 28 Place a level on top of the backbox with the backbox level insert the rest of the mounting screws Figure 4 28 Backbox Surface Mount Holes 3 Run wires to the control ...

Page 63: ... Trim Ring 5 Connect wires from the RA 100 to the SBUS connectors on the FACP See Figure 4 30 6 Attach the annunciator and door assembly to the backbox using screws provided 4 7 2 Model RA 100 Connection to the Panel Connect the RA 100 to the panel as shown in Figure 4 30 Figure 4 30 Model RA 100 Connection to the Panel Supervised Power Limited ...

Page 64: ...S 1000 Installation Instructions P N 151153 or 5815RMK Remote Mounting Kit Installation Instructions P N 151391 3 Connect the 5815XL to the control panel See Section 4 8 1 4 Use on board DIP switches to select an SBUS ID See Section 4 13 1 5 Add the 5815XL module to the system through programming JumpStart will add the module automatically see Section 8 1 You can also add it manually see Section 9...

Page 65: ...P 2100 ECS cabinet the RPS 1000 cabinet or the 5815RMK remote mounting kit Use the standoffs located under the control panel board assembly and secure with screws provided with the 6815 For additional information see Model RPS 1000 Installation Instructions P N 151153 or 5815RMK Remote Mounting Kit Installation Instructions P N 151391 3 Connect the 6815 to the control panel See Section 4 9 1 4 Use...

Page 66: ...re 4 33 6815 Board 4 9 1 6815 Connection to the Panel Connect the 6815 to the control panel as shown in Figure 4 34 After the 6815 is connected to the panel it must be added to the system This programming steps are described in Section 9 2 2 Figure 4 34 6815 Connection to Main Panel Assembly To panel via SBUS To SLC loop Supervised Power Limited ...

Page 67: ...he DIP switches on the 5824 board to assign an SBUS ID to the 5824 see Section 4 13 1 4 Configure the 5824 device through programming See Section 4 10 1 Figure 4 35 5824 Connection to the Panel 4 10 1 Selecting 5824 Options Configuring the 5824 includes the following steps Add the module to the system JumpStart will add the module automatically see Section 8 1 You can also add it manually see Sect...

Page 68: ...l Note When setting Monitor Printer to Yes the system defaults to printing only for the connected panels site Use HFSS Honeywell Fire Software Suite to configure the 5824 to print for multiple sites 7 If you are using a serial printer use the next screen to select serial port options as required for your printer Refer to your printer manual if you need more information Option Choices Baud Rate 75 ...

Page 69: ...itoring The following sub sections describe hardware installation Refer to Section 9 for programming information 4 11 1 5880 Board Layout Figure 4 37 shows the locations of screw terminals for connection to the panel and contact monitor wiring pin connectors for connecting LEDs and the DIP switch for selecting an SBUS ID number for the 5880 Figure 4 37 5880 Board Layout 4 11 2 FACP Connection The ...

Page 70: ... Internal resistors are sized so that there is approximately 10 mA of current for each LED no series resistors are required LED outputs can be mapped to output circuits See Section 9 5 4 for programming details Wire the LEDs as shown in Figure 4 39 On connector P1 Pin 12 is an open collector output for controlling a PZT If used the 5880 PZT will match the PZT pattern of the on board or remote annu...

Page 71: ...circuits on the 5880 board are for monitoring switch inputs Any type of switch supported by the control panel can be used with the 5880 For example you can use a 5880 to monitor pull stations water flow tamper reset or silence switches Wire dry contacts as shown in Figure 4 40 Notice grouping of terminals power terminals are shared by two inputs Figure 4 40 Dry Contact Wiring 4 7k EOL resistor sup...

Page 72: ...ware Refer to Section 9 for programming information Note This manual uses 5865 when referring to aspects of the 5865 3 and 5865 4 that are common to both models Figure 4 41 5865 3 and 5865 4 Assembly front view 4 12 1 FACP Connection The 5865 connects to the panel via the SBUS Make connections as shown in Figure 4 42 After the 5865 is connected to the panel it must be added to the system This prog...

Page 73: ...attached to a 4 gang box is used as an example Figure 4 43 5865 Mounting Example The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly These labels can be used in a typewriter or can be written on by hand Slide the labels under the plexiglass as shown in Figure 4 44 The LEDs will show through the label when illuminated Figure 4 44 Inserting Zone Des...

Page 74: ...dule see Table 4 1 for a list of compatible devices you must use the DIP switches on the module to assign an ID to the module Address zero is an invalid address and is not allowed Figure 4 45 shows all possible DIP switch positions and their correlation to a numerical ID For example to select ID 2 place DIP switch 2 in the up or on position Figure 4 45 Possible SBUS module addresses Refer to Secti...

Page 75: ...e Lines 4 15 Flexputs I O Circuits The eight Flexput circuits are an innovative and versatile feature of the control panel They can be used as Class A or B notification circuits Class A or B initiation circuits either 2 or 4 wire detectors or as auxiliary power resettable continuous sounder base sync or door holder The polarity of the Flexput terminals differs depending on whether the circuit is p...

Page 76: ...at the back of this manual To install a Class A notification appliance circuit 1 Wire the Class A notification appliances as shown in Figure 4 48 Table 4 4 Maximum Impedance Class B Current Maximum Impedance 1 0A 3Ω 1 5A 2Ω 2 0A 1 5Ω 2 5A 1 2Ω 3 0A 1 0Ω Caution For proper system supervision do not use looped wire under terminals marked O and X of the Flexput connectors Break wire runs to provide s...

Page 77: ...um voltage drop is 3V per Class A circuit See Table 4 5 4 15 2 Conventional Input Switch Circuits This section of the manual explains how to install conventional initiating devices for Class A or Class B configurations 4 15 2 1 Class B Inputs You can connect conventional Class B switches such as waterflow switches and pull stations directly to the Flexput circuits of the control panel To install a...

Page 78: ...that uses multiple Flexput circuits the lowest Flexput circuit number is used to refer to the circuit pair For example Figure 4 50 uses both Flexput circuit 1 and 2 so in programming it would be referred to as point 1 4 15 3 Installing 2 Wire Smoke Detectors Any compatible UL listed two wire smoke detector can be used with the control panel see Appendix A for list of compatible smoke detectors Fig...

Page 79: ...ample Figure 4 52 uses both Flexput circuit 5 and 6 so in programming it would be referred to as point 5 4 15 4 Installing 4 Wire Smoke Detectors Any compatible UL listed four wire smoke detector can be used with the control panel see Appendix A for list of compatible smoke detectors Figure 4 53 and Figure 4 54 illustrate how to connect a UL listed four wire Note Flexput circuit 5 used as an examp...

Page 80: ...it Figure 4 53 Class B 4 Wire Smoke Detector Connections Note In programming any point that uses multiple Flexput circuits the lowest Flexput circuit number is used to refer to the circuit pair For example Figure 4 53 uses both Flexput circuit 5 and 6 so in programming it would be referred to as point 5 4 15 4 2 Installing 4 Wire Class A Smoke Detectors Figure 4 54 illustrates how to install 4 wir...

Page 81: ...able are Door Holder Power see Section 4 15 5 1 Constant Power see Section 4 15 5 2 Resettable Power see Section 4 15 5 3 Sounder Sync Power see Section 4 15 5 4 Auxiliary power circuits are power limited Each circuit can source up to 3A total current for all Flexput circuits must not exceed 9 0 A in alarm and 6A when used as constant auxiliary power in normal standby To install an auxiliary power...

Page 82: ...or circuits selected as Resettable 24 volt power is always present at the terminals unless a fire system reset occurs If a fire system reset occurs power is disconnected from the terminals for 30 seconds then re applied See Table A 3 for compatible four wire smoke detectors 4 15 5 4 Sounder Sync Power Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is intended...

Page 83: ...larm to the municipal communication center which houses the central operating part of the fire alarm system City Box Standby Current 0 Notification supervision current accounted for in control panel draw Alarm Current 1 Amp for 1 second 27 2 VDC max The maximum coil and wire resistance combined must not exceed 30 ohms To install the 5220 for city box connection 1 Use one of the knockouts on the ri...

Page 84: ...n Wire the Relay module as shown in Figure 4 58 Figure 4 58 Relay Module for City Box Connection 4 17 4 NFPA 72 Polarity Reversal Note Intended for connection to a polarity reversal circuit of a control unit at the protected premises having Not suitable for remote station protected premise service where separate transmission circuits are required for fire supervisory if applicable and trouble sign...

Page 85: ...wn in Figure 4 59 This dia gram also shows how to connect the 5220 to the remote indicator Do not install an EOL resistor in the ter minals of the Flexput circuit used for this application 3 Connect earth ground wire to the 5220 chassis with mounting screw 4 Program the Flexput circuit as a notification circuit refer to Section 9 5 3 Assign this Flexput to an output group that is mapped to activat...

Page 86: ...ire the 7644 L8 to the control panel as shown in Figure 4 60 Do not install an EOL resistor on the termi nals of the Flexput circuit used Note Use only Flexput circuits on the control panel for reverse polarity 2 Program the Flexput circuit as a notification circuit See Section 9 5 3 3 Map the group to activate non silenceable constant on in response to a system general alarm and to discon nect in...

Page 87: ...2100 ECS dry relay contacts The IFP 2100 ECS FACP contacts must be supervised by the remote station transmitter module using end of line resistors ELRs with a value determined by the transmitter manufacturer Power is also provided by the remote station transmitter manufacturer Refer to the remote station transmitter manufacturer s manual for details Figure 4 61 Transmitter Activated by Dry Contact...

Page 88: ...ng Options to Connect Networked Panels 1 Fiber Optic Single Mode must use the SK NIC and SK FSL for up to 30dB loss of signal separation SK FSL connects to the network using 9 125 micron single mode fiber 2 Fiber Optic Multi Mode must use the SK NIC and SK FML for up to 8dB loss of signal separation SK FML connects to the network using 62 5 125 micron multi mode fiber 3 Twisted Pair Copper Wire mu...

Page 89: ...LS10143 001SK E Networking 5 2 Figure 5 1 External SK NIC Wiring Option Figure 5 2 Internal SK NIC Wiring Option ...

Page 90: ...Fiber Loop Modules The SK FML Fiber Optic Multi Mode and SK FSL Fiber Optic Single Mode are plug in fiber loop modules The two types of fiber optic modules are used as one channel to transmit or receive communications with the SK NIC ARCNET communication circuit The following describe the two types of fiber optic modules The SK FML is a fiber module that allows the multi mode fiber to network betw...

Page 91: ...he SK NIC outside of the IFP 2100 ECS cabinet The accessory kit part number is 1 SK NIC KIT which includes the SK NIC a small cabinet with door cable and mounting hardware 5 4 2 SK NIC Installation The SK NIC is designed to mount on one of the SLC expander standoff sets inside the cabinet or remotely using the accessory cabinet Use the following steps to mount the SK NIC inside the IFP 2100 ECS 1 ...

Page 92: ... of TB2 is done at the next previous SK NIC due to these wiring connections being connected to Port 1 of TB2 at the next previous SK NIC 4 Unused optic ports on fiber loop modules must have their dust caps placed on the port 5 Based on the type of data medium chosen run the twisted pair wiring fiber optic cable to the next SK NIC using a class B or class A wiring method A combination of both mediu...

Page 93: ... 1 Unshielded Twisted Pair Wiring between Multiple Panels Unshielded twisted pair wiring between multiple panels is shown in Figure 5 7 Class A wiring is shown with a dotted line Figure 5 7 Twisted Pair Wiring Configuration Class A wiring ...

Page 94: ...0143 001SK E 5 7 5 4 2 2 Fiber Optic Multi Mode Wiring between Multiple Panels Fiber optic cable between multiple panels is shown in Figure 5 8 Class A is shown with a dotted line Figure 5 8 Fiber Optic Wiring Multi Mode Example Class A wiring ...

Page 95: ...LS10143 001SK E Networking 5 8 Figure 5 9 Fiber Optic Wiring Single Mode Example Class A wiring ...

Page 96: ...ic and Twisted Pair Wiring between Multiple Panels A mixture of fiber optic cable and twisted pair wiring between multiple panels is shown in Figure 5 10 Class A cabling is shown with dotted line Figure 5 10 Twisted Pair and Fiber Optic Combination Wiring Example Class A wiring ...

Page 97: ...at much thought is given when choosing the network IDs for each panel It is difficult to change the IDs once panel programming has begun The network ID for each panel is set using DIP switch positions 1 through 5 See Figure 5 11 below for possible DIP switch settings Figure 5 11 Network ID Settings ...

Page 98: ...nu 6 1 3 Voice Network Status The Voice Network Status screen will display statistics that are indicators of Network performance 1 Enter the Installer Code The panel will automatically go to the main menu 2 Select 5 for Network Diagnostics 3 Press 3 to enter the Voice Network Status menu 6 2 Network Programming This section of the manual describes how to program network options using the built in ...

Page 99: ... to the network future wiring of two buildings together The Network Panel ID setting has to be unique for each panel on the network This menu will allow you to change the currently assigned Network Panel ID to the current Network ID dip switch setting The system will be down as the panel needs to reboot in order to complete the transition When using the PC configuration software to program the pan...

Page 100: ...Fire Fighter Key has access to Because this is the profile for a key the user name and the access code can not be edited for this profile Profile 2 is the profile for the installer and is referred to as the Installer Code This profile s user name and panel functions can not be edited Table 7 9 lists the panel functions that can be selected for each user profile Table 6 1 User Profile Selectable Pa...

Page 101: ...lti Site Installer is defaulted with the Multi Site access option but the entire profile can be edited 6 2 5 1 Edit Name 6 See Appendix B for a list of available characters and their numeric designators 7 Then press ENTER to finish 6 2 5 2 Edit Access Code 8 Enter new access code minimum of 4 digits maximum of 7 digit 9 Press ENTER 10 Enter code again Press ENTER 6 2 5 3 Panel Functions 11 Press t...

Page 102: ... SIA reporting format the communicator sends information according to the SIA Reporting Type The selections for this option are 1 pi modifier default 2 Panel ID 6 2 6 3 Receiver Configuration The IFP 2100 ECS network can report events to as many as 68 receivers See Appendix D for panel receiver relationship numbers Each receiver can be assigned reporting credentials When using a format that suppor...

Page 103: ...s ENTER to edit data Figure 6 1 Communicator Reporting 6 3 Voice Options 6 3 1 Edit Timers 1 Enter the installer code The panel will automatically go to the main menu 2 Select 6 for Network Programming 3 Select 7 for Voice Options 4 Choose Site 5 Select 1 for Edit Timers 6 3 1 1 Control Lockout The Control Lockout countdown timer is set to the programmed value when an LOC gains ECS Control The tim...

Page 104: ...ing Menu 3 Select 7 for Voice Options 4 Choose Site 5 Select 2 for Edit Voice Commands 6 Select the command you wish to edit Table 6 2 Auto Reset ECS MIC Triggered Event Timer Menu ECS Timer Option Control Lockout Immediate Timer Never Auto Reset ECS MIC Triggered Event Never Timer Event Disabled Auto Reset ECS Event 1 Never Timer Event Disabled Auto Reset ECS Event 2 Never Timer Event Disabled Au...

Page 105: ...o restart on a new activation 6 4 Sync Network Options If after making changes to network programming the distribution of network options fail the system will report a trouble of network options out of sync Use this menu to redistribute changed options to the rest of the network The user will be required to choose a panel to source the options from Scroll down through the informational message and...

Page 106: ...is the profile that dictates what functions the Firefighter Key has access to Because this is the profile for a keys the user name and the access code can not be edited for this profile Profile 2 is the profile for the installer and is referred to as the Installer Code This profile s user name and panel functions can not be edited See Section 6 2 5 Edit Access Code Panel Functions System Reset Sys...

Page 107: ...ion Key F3 Function Key F4 Function Key ECS Control Request Function ECS Super User Function Send Receive Firmware Update Communicator Options Communicator Assignments Select Panel Primary 0 unused See Section 6 2 6 Communicator Miscellaneous SIA Options Enable pi SIA Modifier See Section 6 2 6 2 Include Panel ID in SIA Reporting Receiver Configuration Select Panel Select Receiver Receiver Number ...

Page 108: ...IC Triggered Event Edit Voice Commands Fire Alarm See Section 6 3 2 Fire System Aux 1 Fire System Aux 2 Fire Zone Aux 1 Fire Zone Aux 2 Fire Supervisory Fire Pre Alarm Custom Emergency Comm Emergency Communication 1 8 System Alert 1 5 Trouble Fire Interlock Release Choose Site Edit Voice Commands Fire Interlock Alert See Section 6 3 2 Emergency Supervisory CO Alarm CO Supervisory Sync Network Opti...

Page 109: ...detector without test feature I56 2735 00 IDP Beam T Reflected beam smoke detector with test feature DNR DNRW Duct smoke detector housing Non relay photo sold separately I56 3051 000 IDP Heat Fixed temperature thermal detector 135 F I56 3608 000 IDP Heat ROR Rate of rise thermal detector with 135 fixed temperature IDP Heat HT Fixed high temperature thermal detector 190 F IDP Pull SA Addressable si...

Page 110: ...lected beam smoke detector without test feature I56 3433 001 SK Beam T Reflected beam smoke detector with test feature SK Duct Photoelectric duct smoke detector with extended air speed range I56 3432 000 SK Heat Fixed temperature thermal detector 135 F I56 3429 000 SK Heat ROR Rate of rise thermal detector with 135 fixed temperature SK Heat HT Fixed high temperature thermal detector 190 F SK Pull ...

Page 111: ...I56 3542 00 SD505 6SB 6 sounder base I56 3540 00 SD505 DUCT Duct Smoke Detector Duct Housing including the SD505 Analog Photoelectric Smoke Sensor Intake tubing for duct available in three lengths SD505 T2 2 5 foot SD505 T5 5 foot SD505 T10 10 foot 1700 09882 SD505 DUCTR Duct Detector housing with relay base Duct housing with relay base including SD505 Analog Photoelectric Smoke detector pre insta...

Page 112: ... 1 SWIFT Gateway and up to 49 in any combination wireless detectors and monitor modules Multiple Gateways can be used See the SWIFT manual P N LS10036 000FH E for more information 7 6 Wiring Requirements for SLC Devices The following information applies to SLC devices Refer to the section that describes the type of device you are installing for details Table 7 4 SWIFT Wireless Devices SWIFT Model ...

Page 113: ...rogrammed to operate in IDP SK mode While shielded wire is not required it is recommended that all SLC wiring be twisted pair to minimize the effects of electrical interference Use Table 7 6 to determine the specific wiring requirements for the SLC Table 7 6 SLC Wiring Requirements for IDP or SK modules Wire Requirements Distance in Feet meters Wire Type RECOMMENDED Twisted unshielded pair 12 to 1...

Page 114: ...ain bus must not exceed 40 000 feet This requirement must be met in addition to the maximum distance requirements for the various wire gauges Figure 7 2 Calculating Wire Run Length for a T tap 7 6 4 Wiring 5815XL or 6815 in Style 6 7 Class A Configuration Figure 7 3 illustrates how to wire the SLC loop for Class A installations Note Style 6 does not use short circuit isolator devices Note Style 7 ...

Page 115: ...n IDP SK detector or IDP SK module is installed For this reason IDP SK detectors can be assigned any unique address from 1 to 159 and IDP SK modules can be assigned any unique address from 1 to 159 There can be an IDP SK detector using address 1 and an IDP SK module using address 1 0 is an invalid address In order to set the sensor above address 99 carefully remove the stop on the upper rotary swi...

Page 116: ...vice bases as shown in Figure 7 5 2 Set the address for each device as described in Section 7 9 Figure 7 5 Heat or Smoke Detector Connection to the FACP 7 9 Addressing SD Devices This section explains how to address SD detectors and modules See Table 7 3 for a list of SD devices An access code with the option to set SLC Device Address enabled is required to perform this task To address a SD detect...

Page 117: ...essing the up arrow then press ENTER The panel will go into trouble at this point You can use the SILENCE key to stop the PZT The trouble will clear automatically when the panel re initializes when you finish programming 6 When the wait message clears the following options display 1 for Read Address Use to read or check a single detector s address 2 for Write Address Use to program a single detect...

Page 118: ...nd relay module addresses are set using the DIP switches on the module board The chart below shows the available addresses For example to select address 3 place DIP switches 1 and 2 in the up position The range of valid addresses is 1 127 0 is an invalid address Figure 7 7 Device Addressing using DIP Switches ...

Page 119: ...he USA Note It is recommended to use the same wire gauge is there are multiple connections to the same terminal For more information regarding Gateway wiring instructions see SWIFT manual LS10036 000FH E or LS10036 000SK E 7 10 1 Power Connections for the Gateway The WIDP WGI or SK WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and a SLC loop on the IFP 2100 ECS It ...

Page 120: ...tart AutoProgramming The JumpStart AutoProgramming feature allows for faster system setup When you run JumpStart AutoProgramming the panel searches for expanders and SLC devices not currently in the system The new devices are added in their default configuration At the end of the JumpStart you can choose to not accept the new devices and go back to the configuration you had before JumpStart saves ...

Page 121: ...er options such as names for devices already in stalled Follow instructions in Section 8 for configuration To run JumpStart AutoProgramming follow these steps 1 Select 7 for Panel Programming Enter Access Code 2 Select 6 for JumpStart AutoProgramming 3 The message The system will be shut down during JumpStart Press ENTER to accept 4 When the message SLC FAMILY message appears select IDP SK or SD d...

Page 122: ... contains the duct detectors 4 The first photoelectric or ionization detector on the system will display Select 1 for DUCT and 2 for NonDUCT 5 Press up arrow to select the next detector Select 1 for DUCT and 2 for NonDUCT Continue until all duct detectors have been selected Note You can move backwards through the list with down arrow 6 When you reach the last detector on this device press left arr...

Page 123: ...put zones output points to output groups and then linking or mapping zones and output groups Figure 8 1 is a brief overview of the concept of mapping The next several pages of the manual show these subjects in detail Figure 8 1 Mapping Overview Note Supervised notification Outputs mapped to General troubles on the NAC circuit should be made latching Failing to do so will cause the circuit to conti...

Page 124: ...ts are assigned to input zones as the example if Figure 8 2 shows Any input point can be assigned to any input zone Input points can be assigned to one zone only An input point can be designated as Unused which means it has not been assigned to a zone Figure 8 2 Example of Input Point Assignment ...

Page 125: ...E Programming Overview 8 6 8 2 2 Output Circuit Mapping Figure 8 3 is a simple example showing how to assign notification and relay output circuits to groups Figure 8 3 Example of Assigning Output Circuits to Groups ...

Page 126: ...or smoke detectors General Fire Supervisory Zone Aux 1 Alarm General Fire Pre Alarm Zone Aux 2 Alarm Interlock Alert Interlock Release Pre Alarm Fire Supervisory Status Point CO Alarm CO Supervisory Emergency LOC ECS 1 8 Alarm General ECS Alarm General ECS Supervisory Point ECS 1 8 Alarm Advisory Trouble SBUS Expander Trouble General Trouble Status Point Active SBUS Class A Trouble Site Silenced S...

Page 127: ...LS10143 001SK E Programming Overview 8 8 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns ...

Page 128: ...Model IFP 2100 ECS Installation Manual LS10143 001SK E 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel ...

Page 129: ...LS10143 001SK E Programming Overview 8 10 Figure 8 6 Example of Events Mapped to Output Groups and Patterns within a Networked Site ...

Page 130: ... how LED points are mapped to zones and output groups Typically you would create two output groups for each zone one for alarms and one for troubles LED points are available when models 5865 3 4 and or 5880 are used with the system Figure 8 7 Example of LED Points Mapped to Output Groups Applies to Models 5865 3 4 and 5880 ...

Page 131: ...can connect to the control panel directly using the onboard USB Updates are available at www farenhyt com 8 4 Programming Using an Annunciator Many of the features can be programmed through the system annunciator using either the control panel s on board annunciator or RA 2000 RA 1000 or RA 100 remote annunciators The following subsections describe programming basics including a description of edi...

Page 132: ...ws how to move through the menu screens using the main menu screen as an example Figure 8 9 Moving through Main Menu Main Menu used as an Example 8 4 1 2 Selecting Options and Entering Data There are several ways to make programming selections using the control panel depending on which screen you are currently viewing The chart below is a generic explanation To Press Select from a menu The corresp...

Page 133: ...ection 9 2 1 Enter Module Name Edit Module specific options Add Module 5824 Serial Parallel IO Section 9 2 2 RA 2000 LCD Annunciator RA 1000 LCD Annunciator RA 100 LCD Annunciator 6815 SLC Loop Expander 5815XL SLC Loop Expander RPS 1000 Power Supply 5496 NAC Expander 5880 LED IO Module 5865 LED Annunc Module ECS 50W Voice Amplifier ECS 125W Voice Amplifier ECS DUAL50W Voice Amplifier ECS INT50W Vo...

Page 134: ...h Zone Accessory Opt Single Multi station Cadence 00 23 Section 9 3 1 3 CO Single Multi station Cadence 00 23 Local Zone Yes No View Zone Points Select Zone Section 9 3 2 Group Edit Group Select Group Group Name Section 9 4 1 1 Group Properties Voice Group Y or N Section 9 4 1 2 Switch 1 64 Template Override Y or N Allow Sys Override Y or N Dynamic Act Template Override Cadence 00 23 See Appendix ...

Page 135: ...LL SILENCE RESET P A S ACK ZONE AUX1 LATCH NON LATCH ZONE AUX2 LATCH NON LATCH SYSTEM AUX1 LATCH NON LATCH SYSTEM AUX2 LATCH NON LATCH DETECTOR FIRE TAMPER LATCH NON LATCH MANUAL RELEASE INTERLOCK STATUS POINT CO DETECTOR SWITCH CO SUPERVISORY DETECTOR SWITCH LATCH NON LATCH ECS INPUT LATCH NON LATCH ECS TAMPER LATCH NON LATCH ECS SUPER VISORY LATCH NON LATCH NOTIF1 2 3 4 5 6 OUTPUT PT Select Grou...

Page 136: ...OR SLC LED 1 6 LED Number 1 80 LED Function Notif Unused DETECTOR 2 3 4 5 2 WIRE SMOKE Select Zone W Gateway 2 3 4 5 W SWITCH 2 3 4 5 8 Same as SWITCH W RELAY2 3 4 5 8 Same as Relay UNUSED DETECTOR1 2 3 4 5 6 PHOTO No Accessory SDR BAS 1 2 3 4 5 6 RLY BAS 1 2 3 4 5 6 I SdrBa Intelligent Sounder Base 2 3 4 5 6 ION No Accessory SDR BAS 1 2 3 4 5 6 RLY BAS 1 2 3 4 5 6 I SdrBa Intelligent Sounder Base...

Page 137: ...ligent Sounder Base 2 3 4 5 PHOTO DUCT 1 2 3 4 5 6 No Accessory DCT RLY ION DUCT1 6 No Accessory DCT RLY 2 WIRE SMOKE1 6 ACCLIMATE 2 3 4 5 No Accessory SDR BAS RLY BAS I SdrBa Intelligent Sounder Base HEAT HT 2 3 4 5 No Accessory SDR base RLY base I SdrBa Intelligent Sounder Base PHOT HEAT 2 3 4 5 No Accessory SDR BAS RLY BAS I SdrBa Intelligent Sounder Base BEAM2 3 4 5 SUP DET 1 2 3 4 5 6 Same fu...

Page 138: ...SUPR No Accessory SDR BAS Single station or Multi station Silence or Non Silence RLY BAS I SdrBA Intelligent Sounder Base Latch or non latch Single station or Multi station Silence or Non Silence CO SUPR FIRE ALARM No Accessory SDR BAS Single station or Multi station Silence or Non Silence RLY BAS I SdrBA Intelligent Sounder Base Latch or non latch Single station or Multi station Silence or Non Si...

Page 139: ...USED Section 9 5 B NOTIF NOTIF OUTPUT Select Group Super vised Yes or No CONTROL CIRCUIT A NOTIF NOTIF OUTPUT Select Group Super vised Yes or No CONTROL CIRCUIT AUX PWR CONSTANT AUX RESET AUX DOOR AUX SYNC9 B SWITCH MANUAL PULL Latch and Non Latch feature only appear for WATERFLOW FIRE SUPERVISORY FIRE TAMPER ZONE AUX1 ZONE AUX2 SYSTEM AUX1 SYSTEM AUX2 ECS INPUT ECS TAMPER and ECS SUPERVISORY WATE...

Page 140: ...P DET Latch Non Latch A DETECT 2 WIRE SMOKE 4 WIRE SMOKE CO 4 WIRE DET CO 4 WIRE SUP DET Latch Non Latch Select Group or Zone Number Group or Zone selection will appear depending on the function selected Edit Name Enter Name 5496 Edit Point UNUSED Section 9 5 5 B NOTIF Control Circuit Notif Output Select Group Super vised Yes or No A NOTIF AUX_PWR Constant Edit Name Aux Sync Aux Door Aux Reset 588...

Page 141: ...efore panel answers a call from a computer Section 9 6 1 2 Select Dialing Option TT TT Touch Tone TT PL TouchTone alternating with pulse see Section 9 6 1 2 PULSE Pulse dialing Rotary Pulse Format U 60 40 U Section 9 6 1 2 E 66 34 Dial Tone Disabled Y or N N Monitor Line Y or N N Section 9 6 1 2 Answering Machine Bypass Y or N N Section 9 6 1 2 Phone Line Unused Y or N N Section 9 6 1 2 Edit Ether...

Page 142: ... 250 seconds 60 sec Alarm Verification time section 9 6 4 2 Low AC Report Time 0 30 hours 3 hrs Low AC Report Delay Section 9 6 4 3 AC Freq 50 Hz 60Hz Section 9 6 4 4 60 Hz Internal Clock Display Format AM PM AM PM System Clock Format AM PM or military Section 9 6 4 5 MIL Auto resound 4 hours 24 hours Section 9 6 4 6 24 hours Miscellaneous Options SYNC Strobes when Silenced Y N Section 9 6 5 1 N A...

Page 143: ... 5 Available with SLC Family as SK 6 Available with SLC Family as SD 7 Requires ECS module programmed into the panel 8 Requires wireless Gateway 9 Aux Sync setting is only applicable for the B200S Sounder Base Voice Options VCM Maintenance PC Connection Section 9 7 Local Recording Edit Voice Settings Enable Dual Channel System Default Menu Options Defaults Comments ...

Page 144: ...ICTION AND OTHER INVOLVED PARTIES This product incorporates field programmable software In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 and Stand for Mass Notifications Systems UL 2572 certain programming features or options must be limited to specific values or not used at all as indicated below Programming O...

Page 145: ...nstaller code The panel will automatically go to the main menu 2 Select 7 for Panel Programming Note If you are working on a networked system you will need to select which panel you want to program 3 Press 1 to enter module menu 4 Press 1 to edit a module 5 Use the up or down arrow key to select the module you wish to edit Then press ENTER 9 2 1 1 Editing Module ID 6 Press the up or down arrow key...

Page 146: ...pe screen where you can add additional modules if desired You must save changes when you exit the Panel Programming or the new module will not be added Note If you Add a Module that has not been physically connected the panel will go into trouble after it reinitial izes when you exit the Panel Programming When the new module is attached the trouble will correct itself automatically 9 2 3 Deleting ...

Page 147: ...t a zone 5 Enter the zone number then press ENTER 9 3 1 1 Edit Zone Name 6 Press 1 to edit the selected zone name You can use words to display a descriptive name for a zone Note See Appendix B for editing names 9 3 1 2 Edit Zone Properties Zone properties consist of alarm delay characteristics heat detector sensitivity and smoke detector sensitivity 1 Do steps 1 through 5 of Section 9 3 1 2 Press ...

Page 148: ...ay indicates that a prealarm has occurred If the zone has been mapped to an output group for the prealarm event the output group will activate The prealarm will not be reported to the central station Alarm Verification Alarm verification is an optional false alarm prevention feature that verifies an alarm condition by resetting the smoke detector If the alarm condition still exists by the time the...

Page 149: ...mming is required See Section 10 4 11 for information about how to check if a detector is in UL compliance Table 9 2 IDP SK and SD Sensitivity Choices Detector Protocol Type of Smoke Detector Choices Comments IDP SK Photo Acclimate Photo T Low 3 5 obscurity If the day night sensitivity option is selected you can have different sensitivity settings during the day and at night You can program the da...

Page 150: ... edit group option you can program the name of an output group Section 9 4 1 1 and change the properties Section 9 4 1 2 of that group To edit a group follow these steps 1 Enter the installer code The panel will automatically go to the main menu 2 Select 7 for Panel Programming 3 Press 3 to enter group menu 4 Press 1 to edit group 5 Enter the number of the group you wish to edit then press ENTER 9...

Page 151: ...M ECS NVMC ECS RVM and ECS SW24 This allows the user to see the state of the voice groups assigned to the switches This also lets the user individually select which areas they want to do a live page into Output groups not defined as voice groups can also be assigned to these switches as long as there is a voice group already assigned to the group This allows for dynamically activating deactivating...

Page 152: ...ming This section explains how to change options for type of input point latching non latching status switches and name and zone group assignment of a point 9 5 1 Point Programming For 5815XL Module To program for points on an 5815XL module follow these steps 1 Enter the installer code The panel will automatically go to the main menu 2 Select 7 for Panel Programming 3 Press 4 to enter point menu 4...

Page 153: ...elay of up to 90 seconds to be used with a water flow switch The delay allows for normal brief changes in sprinkler system water pressure The water flow alarm will not activate unless the switch is active for the programmed delay time If a delay is used the system begins counting down when the switch closes If the switch opens restores before the timer expires a water flow alarm is not generated I...

Page 154: ...witch but will be indicated as a tamper switch on the LCD annunciator Non Latching MANUAL RELEASE Manual release switch INTERLOCK Interlock release switch input STATUS POINT ECS INPUT Latching User also has ECS Event Number 1 8 option for ECS INPUT Only available when an ECS VCM is installed in the system Non Latching ECS TAMPER Latching Non Latching ECS SUPER VISORY Latching Non Latching CO DETEC...

Page 155: ... and so on AUX RESET Use for auxiliary power resettable applications See Section 4 15 5 for a description of how this option operates AUX DOOR Use for auxiliary power door holder applications For example if you were using an auxiliary power supply for door holders you would use this option See Section 4 15 5 1 for a description of how this option operates SLC LED LED NUMBER 01 80 For use with SD d...

Page 156: ...with a water flow switch The delay allows for normal brief changes in sprinkler system water pressure The water flow alarm will not activate unless the switch is active for the programmed delay time If a delay is used the system begins counting down when the switch closes If the switch opens restores before the timer expires a water flow alarm is not generated If the water flow switch remains clos...

Page 157: ...ndicated as a tamper switch on the LCD annunciator Non Latching MANUAL RELEASE Manual release switch INTERLOCK Interlock release switch input STATUS POINT ECS INPUT Latching User also has ECS Event Number 1 8 option for ECS INPUT Only available when an ECS VCM or ECS NVCM is installed in the system Non Latching ECS TAMPER Latching Non Latching ECS SUPER VISORY Latching Non Latching CO DETECT SWITC...

Page 158: ... then press ENTER 11 Press ENTER to edit point name See Appendix B Or Press right arrow key to skip point name edit 12 Repeat Steps 1 through 11 for all circuits RELAY OUTPUT PT Select Group Output point a general use relay type Use for applications requiring a relay such as fan shutdown elevator recall and so on AUX RESET Use for auxiliary power resettable applications See Section 4 15 5 3 for a ...

Page 159: ... ECS INPUT User also has ECS Event Number 1 8 option for ECS INPUT Only available when a ECS VCM or ECS NVCM is installed in the system ECS TAMPER ECS SUPERVISORY A SWITCH Same as B SWITCH B DETECT 2 WIRE SMOKE Used for Class B 2 wire detectors 4 WIRE SMOKE Used for Class B 4 wire detectors CO 4 WIRE DET Used for Class B 4 wire CO detectors CO 4 WIRE SUP DET Latching or Non latching used for Class...

Page 160: ...s ENTER to edit point name See Appendix B Or Press right arrow key to skip point name edit 9 Repeat Steps 1 through 8 for all output points 10 To use 5880 as Input point Enter point number 41 48 See Figure 9 5 on page 17 Then press ENTER 11 Press the up or down arrow key to select type switch or unused then press ENTER 12 Press the up or down arrow key to select the desired function See Figure 9 7...

Page 161: ...ogram module points 1 Enter the installer code The panel will automatically go to the main menu 2 Select 7 for Panel Programming 3 Press 4 to enter point menu 4 Press the up or down arrow key to select the desired module Refer to Section 8 5 for available choices Then press ENTER Figure 9 7 Programming Points Screen for the ECS AMP Module 5 Enter the point number then press ENTER Points 5 8 on ECS...

Page 162: ...r to Section 8 5 for available choices Then press ENTER Figure 9 8 Programming Points Screen for the ECS VCM ECS NVCM or ECS RVM Modules 5 Enter the point number Press ENTER 6 Press the up or down arrow key to select the type switch or unused Press ENTER 7 Press the up or down arrow key to select the desired Function See Table 9 7 Press ENTER 8 Press ENTER to edit point name See Appendix B or Pres...

Page 163: ...ERVISORY WATERFLOW FIRE SUPERVISORY FIRE TAMPER DETECTOR FIRE DRILL SILENCE RESET P A S ACK ZONE AUX1 ZONE AUX2 SYSTEM AUX1 SYSTEM AUX2 MANUAL RELEASE INTERLOCK STATUS POINT ECS INPUT User also has ECS Event Number 1 8 option for ECS INPUT ECS TAMPER and ECS SUPERVISORY functions in both 5880 and ECS VCM ECS RVM choices Only available when an ECS VCM is installed in the system to the ECS VCM ECS R...

Page 164: ...xt menu select 1 for Communication Options ECS VCM ECS RVM ECS NVCM UNUSED SWITCH MANUAL PULL Refer to comments column of Table 9 4 for description of these options Latch or Non latching feature only appears for WATERFLOW FIRE SUPERVISORY FIRE TAMPER ZONE AUX1 ZONE AUX2 SYSTEM AUX1 SYSTEM AUX2 ECS INPUT ECS TAMPER and ECS SUPERVISORY WATERFLOW FIRE SUPERVISORY FIRE TAMPER FIRE DRILL SILENCE RESET ...

Page 165: ...and AMPM is not selectable 9 6 1 2 Phone Lines To access the phone lines screen 1 Enter the installer code The panel will automatically go to the main menu 2 Select 7 for Panel Programming 3 Select 5 for System Options 4 From the next menu select 1 for Communication Options 5 Select 2 for the phone Lines 6 Select Phone Line to be edited 1 or 2 by pressing the up or down arrow key then press ENTER ...

Page 166: ...ed See Figure 9 9 for location of this field on the phone lines screen When the phone line monitor has been enabled for a phone line a trouble condition will occur if the line is not connected If a phone line will not be used it must be disabled 12 Select Y monitor line or N don t monitor line by pressing the up or down arrow key then press ENTER Answering Machine Bypass This option is used in con...

Page 167: ...rom the next menu select 1 for Communication Options 5 Select 3 for Edit Ethernet Figure 9 10 Edit Ethernet Message 9 6 1 4 AlarmNet Timers 1 Enter the installer code The panel will automatically go to the main menu 2 Select 7 for Panel Programming 3 Select 5 for System Options 4 From the next menu select 1 for Communication Options 5 Select 4 for AlarmNet Timers 6 The available options for AlarmN...

Page 168: ...ect 5 for Phone Line Gains 6 The available options default Dialing Gain Low 9 DB Attenuation Normal 6 DB Attenuation High 3 DB Attenuation Reporting Gain Low 9 DB Attenuation Normal 6 DB Attenuation High 3 DB Attenuation 9 6 2 Daytime Nighttime Sensitivity If you need to change the time that sensitivity levels take effect that is the time that Day and Night begin follow these steps 1 Enter the ins...

Page 169: ...Edit the holiday schedules you wish to change or add holidays as needed in the programmable holiday loca tions Figure 9 13 Edit Holidays Screen 6 Enter the month of the holiday then press ENTER Enter the day of the month for the holiday then press ENTER 7 Repeat steps 6 for any remaining holidays you wish to program 9 6 4 Time Options Through this programming option you can set the water flow dela...

Page 170: ...ion To program low AC report delay follow these steps Note Steps continued from step 7 of Section 9 6 4 2 8 Enter the number of hours 0 30 before a low AC report will be sent to the central station then press ENTER 9 6 4 4 Change AC Line Frequency The panel s AC line frequency is selectable for 50 60 Hz or Internal AC Frequency feature dictates how the control panel will calculate time based on th...

Page 171: ...on between Y Yes or N No 6 Press right arrow key or ENTER to make your selection and move to the next programming option 9 6 5 2 Auto Display Events When this feature is programmed Y Yes the highest priority event of the system in control will automatically display on the control panel and remote annunciators after there has been no activity on any system touch pad for two minutes 7 Press the up o...

Page 172: ...ssage that displays on the panel LCD when the system is normal that is when no alarms or troubles exist and the system menus are not in use A custom banner of up to 40 characters can be created This will automatically be centered when shown If a custom message is not created the system will use the internal banner You cannot change the internal banner To customize the banner display message 1 Ente...

Page 173: ...store the panel back to factory defaults All programming will be lost 1 Enter the installer code The panel will automatically go to the main menu 2 Select 7 for Panel Programming 3 Select 7 for Restore Defaults 4 Press the up or down arrow key to select YES or NO from the warning screen Then press ENTER 9 9 Voice Options Through this programming menu you can modify the messages programmed into an ...

Page 174: ... Options 3 Select 1 for VCM Maintenance 9 9 2 Voice Settings 1 Select 7 for Panel Programming 2 Select 8 for Voice Options 3 Select 2 for Voice Settings 9 9 2 1 Enable Dual Channel System This option allows you to select whether dual channel is enabled in the system For dual channel capabilities the system must only contain dual channel voice hardware 1 Press the up or down arrow key to select YES...

Page 175: ... menus Please read this entire section carefully before operating the panel Note See Section 6 2 5 for information on how to modify user access code profiles 10 1 Default User and Installer Codes Installer Code Factory programmed as 123456 Multi site Installer Code Factory programmed as 654321 10 2 Annunciator Description Figure 10 1 shows the annunciator that is part of the control panel board as...

Page 176: ...ressing the arrow keys 10 3 Menu System The control panel is easy to operate from the Main Menu To view the Main Menu press the ENTER or right arrow key on the control panel or remote annunciator The Main Menu will appear as shown in Section 10 3 1 Select the desired option You will be prompted for as access code if required The control panel supports up to 20 access codes The profile for each acc...

Page 177: ...row key to move through the list of groups Press ENTER to select the group high lighted 10 4 2 3 Disable Enable Zone Points 1 Press 5 to Disable Zone Points press 6 to Enable Zone Points 4 Set Time Date Set time and date for the system 5 Network Diagnostics Ping Panel Data Network Status and Voice Network Status 6 Network Programming Access Learn Network Edit Network Names Edit Panel ID Computer A...

Page 178: ...h panel stores up to 1000 of its own events When viewing Event History in the panel the newest 500 events from every panel in the site will be displayed When using HFSS Honeywell Fire Software Suite all 1000 events from every panel in the network will be uploaded On multi site displays pressing ENTER or right arrow brings you directly into View Event History and allows you to view the Event Histor...

Page 179: ...ine 3 Enter the time period you wish the NAC circuit to be active for each alarm 06 to 180 second if you select this option central station reporting will be disabled while the test is in progress Select 4 for Walk Test with Report The LCD will display WALK TEST STOPPED on Line 1 and ENTER start test on Line 3 Enter the time period you wish the NAC circuit to be active for each alarm 06 to 180 sec...

Page 180: ...n restored will un silence every 4 or 24 hours depending on user selection see section 9 6 4 6 until the detector is restored Note Multi Site displays do not allow for silencing multiple sites Pressing SILENCE will only locally silence the PZT built into the annunciator To silence a site enter a multi site access password select a site and then press SILENCE Note For ECS systems pressing silence a...

Page 181: ...iance When a Calibration Trouble condition occurs the central station receives a detector trouble report 373 Zone for Contact ID format FT Zone in SIA format To check sensitivity for an individual detector follow the steps below 1 From the Main Menu press 2 for Point Functions 2 Press 2 for Point Status 3 Select the module where the point you want to check is located 4 Enter the number of the poin...

Page 182: ...RFP 2100 Firmware Update Utility can be downloaded from the Farenhyt Web Site Once a panel has been updated using the Firmware Update Utility you can use Send Receive firmware updates to propagate the firmware to the other panels in the network 1 Press 2 to send a firmware update or press 3 to receive a firmware update from the System Information menu Available panels are listed in the menu 2 Use ...

Page 183: ...group programming menus and in HFSS Honeywell Fire Software Suite In these places the option is called Allow System Override and defaults to YES It is also possible to not reactivate the output groups every 30 seconds when System Override is active on a per system basis This option is programmable in HFSS There are times when you would not want to allow System Override for an output group For exam...

Page 184: ...ull is mapped to Voice Group 1 as an Alert 1 mapping and Zone 2 Manual Pull is mapped to Voice Group 1 as a normal mapping If Zone 1 and Zone 2 Manual Pull events are active Voice Group 1 will annunciate the Fire Alarm message defined in the Voice Settings for the panel s assigned site Event priority is considered here based on the Event Priority Table If an output group is mapped both directly an...

Page 185: ...Status event priority Note All fire emergency and system troubles are prioritized into the Trouble event priority 10 6 Operation Mode Behavior The control panel can be in one or more of seven conditions at any given moment Normal Alarm Prealarm Supervisory Trouble Silenced and Reset Table 10 2 describes the behavior of the panel in each of these modes When looking at the LCD the screen will displa...

Page 186: ...ed The system seizes control and will the central station The on board annunciator will sound loud steady beeps to distinguish Alarm signals For Fire Alarm the sequence is a loud steady beep Any notification devices attached to the system will also sound For ECS Alarm the sequence is four seconds on one second off GENERAL ALARM LED is on The LCD displays a screen similar to this one Press the down...

Page 187: ...seizes control and will the central station The on board annunciator sounds a loud pulsing beep in the sequence of second on eight seconds off SYSTEM TROUBLE LED is on The LCD displays a screen similar to this one Press down arrow to view the fire trouble A screen similar to this one displays Press SILENCE to silence the annunciator Once the trouble condition has been fixed the system will restore...

Page 188: ...st be entered and then a site must be selected from the site selection menu Once this is done you will have access to the idle screen of that site and the annunciator will temporarily act like a single site annunciator 4 A multi site annunciator will sound the highest priority tone from the sites it is assigned to Note A multi site display is created in Module programming in the edit properties me...

Page 189: ...lert output group for all releasing zones NAC 98 002 is assigned to Output Group 3 Output Group 4 is created Output Group 4 will be defaulted as Interlock Release Alarm output group for all releasing zones NAC circuit 98 003 is assigned to Output Group 4 Note The installer must define which input points will be used for detectors manual release switches or inter lock pressure switches Note For man...

Page 190: ...user that the initial stages required for a release condition are present Also refer to Table 10 4 Conditions required for a Detector Alarm and Interlock Release Alarm Output Activation If two or more addressable detectors or a manual release switch activate the Detector Alarm and Interlock Viking 11591 24 VDC 417 11595 24 VDC 417 11592NC 24 VDC 416 16360 24VDC 500 Important Only addressable detec...

Page 191: ...Conditions Required for a Interlock Release Alarm Output Activation Any release requires the activation of an interlock switch and either a manual release switch or 2 activated addressable detectors When these conditions are met the Interlock Release Alarm and Detector Alarm outputs will activate and the Interlock Release Alert outputs will deactivate Table 10 4 Single Interlock Zone Operation Inp...

Page 192: ...cro can hold 50 events Manual Release Station X X X X X X X X Interlock Pressure Switch X X X X X X X X Normal Interlock Release Alert Interlock Release Alert Interlock Release Alert and Detector Alarm Interlock Release Alert and Detector Alarm Interlock Release Alert and Detector Alarm Interlock Release Alert and Detector Alarm Interlock Release Alert and Detector Alarm Interlock Release Alert an...

Page 193: ...started the session can be canceled at any time by access ing the F Key Recording menu and selecting Abort F KEY Recording option 2 The panel will return to the idle screen 10 9 3 Erasing an F Key Macro 1 If an F Key macro has already been recorded you can erase it by accessing the F Key Recording menu and selecting the Erase F KEY Macro option 2 The panel will return to the idle screen 10 9 4 Usi...

Page 194: ...ons are not pre determined and allow the user to make system functionality decisions when the event is actually happening This requires the activation of Manual ECS State which bypasses ECS Point Activations See section 11 2 3 11 2 LOC Functionality An LOC Local Operating Console consists of either the ECS series panel ECS VCM Voice Control Module or ECS NVCM Network Voice Control Module and the A...

Page 195: ...tivated at an LOC See section 11 2 3 3 The green ECS Message LEDs will activate for the LOC that activated the ECS Message 11 2 1 5 Select Keys The Select Keys are used to toggle which output areas are active 1 If Message Mode is active see Section 11 2 3 the Select Keys will activate output which areas for the active message to be played in also activates the red Select Key LED Note For LOC activ...

Page 196: ...of the ECS VCM ECS NVCM or ECS RVM an LOC priority of low normal or high LOCs with a higher priority are always able to gain control from a lower priority LOC 11 2 2 2 LOC Lockout When LOCs are programmed to the same priority the setting LOC lockout applies LOC lockout will not allow an LOC to gain ECS Control from the LOC with ECS Control until one of three things happen 1 The LOC lockout timer e...

Page 197: ...en reflects this when viewing the system for status Any outputs that were activated by the ECS Alarm programmed points are deactivated until Manual ECS state is exited Only an ECS Reset can exit the Manual ECS State If a user gains ECS Control at an LOC and does not activate an ECS message the system will automatically generate an ECS Supervisory indicating such This prevents an LOC from being in ...

Page 198: ...ct Keys to activate or deactivate which output areas the message will be played This will activate or deactivate the green and red LEDs next to the ECS Message Keys and the red LEDs next to the Select Keys 11 2 6 Custom ECS Event Custom ECS events allows the user to generate an ECS event and speak a custom message using the microphone Once the user is done speaking the message the tone and any ass...

Page 199: ...at the LOC still has ECS control 11 2 9 Relinquish ECS Control Relinquishing ECS Control is accomplished by pressing the ECS Control Key from within Message Mode A screen will be displayed to ensure the user wants to relinquish ECS Control ECS Control will be automatically relinquished after a time out on this screen When ECS Control is relinquished the system stays in the Manual ECS State ECS Con...

Page 200: ...t for Emergency 2 Point Alarm are both active the system will play message 1 through groups 1 2 and 3 Once Manual ECS State is active points in Alarm state switch to an Active state When the points are changed to the Active state they do not activate any system mapping or turn any outputs on Any points that are activated while in Manual ECS are also placed into the Active state and are not allowed...

Page 201: ...utput voltage To edit an existing module 1 Enter the installer code The panel will automatically go to the main menu 2 Select 7 for Program Menu 3 Press 1 to enter module menu 4 Press 1 to edit a module 5 Use the up or down arrow key to select the module you wish to edit 6 Press the right arrow key or ENTER to move to next selection 11 6 LOC Programming LOC Priority is a programmable option for th...

Page 202: ...1 to edit a module 5 Use the up or down arrow key to select the module you wish to edit 6 Press the right arrow key or ENTER to move to next selection 11 6 2 1 LOC Priority Each device is assigned a Priority level Low Normal or High This is modified by editing the LOC s ECS VCM ECS NVCM or ECS RVM module By default the ECS VCM or ECS NVCM has a high LOC priority The ECS RVM is defaulted to normal ...

Page 203: ...ire page is NOT allowed An LOC must gain ECS Control in order to do any live voice 11 7 4 Emergency Page An emergency page can occur when 1 Only the emergency system is active and the user has gained ECS Control 2 Both fire and the emergency systems are active and the highest priority active emergency event is pro grammed to be of higher priority than the highest priority active fire event and the...

Page 204: ...ages can be a maximum of one minute When in the record mode the ECS VCM or ECS NVCM keys will function as follows While in the Local Record mode Select Keys 1 15 will be used to reference message slots 1 15 The associated READY TO TALK LED Key Function ECS Message Key 1 Select message slot to record to ECS Message Key 3 Start and stop recording from Aux Audio Input ECS Message Key 8 Erase user mes...

Page 205: ... recorded messages into an ECS message location Follow these steps to record a user message using Aux Audio Input Note Refer to section 9 for detailed programming information 1 Wire a speaker cable with 1 8 mini plug to the Aux AUDIO GND and IN terminals Refer to Figure 11 5 Figure 11 5 Aux Audio Connection for Recording 2 Plug the mini plug into the Line Out Headphone jack on a PC or laptop See F...

Page 206: ...th Aux Audio Input Example The user wants to record into memory slot 2 via the Aux Audio Input channel Upon entering the Local Recording mode via the keypad menu the VCM will light the Select Key green LEDs 1 15 for each occupied message slot If a message already exists in message slot 2 it must first be erased Press ECS Message Key 8 then press Select Key 2 see Section Figure 11 8 3 on page 15 Wh...

Page 207: ...k PTT button on the microphone and speak your message 8 Release the PTT button on the microphone to save your message The Select Key green LED for this loca tion will turn on 9 To playback the recorded message press the Select Key 1 15 that was just recorded to 10 If you are not satisfied with the recorded message erase it see Section 11 8 3 and then repeat steps 1 through 7 Recording with Microph...

Page 208: ...oximity to them 6 Press ECS Message Key 8 on the VCM press the Select Key 1 15 that you wish to erase The Select Key red LED will stay on until the erase is done When erased the Select Key green LED by corresponding to the message slot you erased will go off 11 8 4 Using HFSS Voice Message Load Software The HFSS Voice Message Load Software is a software support utility that is used to download rec...

Page 209: ...ion see ECS Series installation manual P N 151455 The network paging source panel is the panel in the network that the microphone network paging audio is originating from One panel in the network can be the source panel at a time A network paging destination panel is a panel in the network that is receiving the network paging Many panels can be selected as a destination panel for the network pagin...

Page 210: ...ion or network paging activation 2 To use network paging Cue the microphone and press the Select Switch es that correspond to the panel s desired to receive network paging Only one panel can source network paging at a time The first panel to activate net work paging is the source until that panel discontinues use of network paging 3 The panel that is the Network Paging source will continue to play...

Page 211: ...rt SIA and Contact ID Table 12 2 Reporting Formats Table SIA Reporting Format Contact ID Reporting Format SIA pi Modifier SIA IFP 2100 ECS Event Description Module ID If Any SIA Event Codes Parameter Fixed Length Format NN panel ID XX SBUS ID ZZZ Zone PPPP Point GGG Group E Emergency RRRR Receiver Qualifier Event Code Group Contact System Events Note System Events are reported when either Report b...

Page 212: ...ping Inhibited Restoral FJ 2004 FJNN002004 3 570 00 004 Fire Reset OR 0 ORNN000000 1 401 00 000 Fire System Overridden FS 0 FSNN000000 1 245 00 000 Fire System Override Restore FR 0 FRNN000000 3 245 00 000 Ground fault condition trouble YP Exp ID YPNNXX0000 1 310 Exp ID 000 Ground fault condition trouble restore YQ Exp ID YQNNXX0000 3 310 Exp ID 000 Initial power up RR 0 RRNN000000 1 305 00 000 Lo...

Page 213: ... Remote programming aborted or ended with errors RU 0 RUNN000000 1 413 00 000 Remote programming ended nor mally RS 0 RSNN000000 1 412 00 000 Repeater ground fault trouble EM 0103 EMNN000103 1 334 Panel ID 103 Repeater ground fault trouble re store EN 0103 ENNN000103 3 334 Panel ID 103 Repeater missing trouble EM 0100 EMNN000100 1 334 Panel ID 100 Repeater missing trouble restore EN 0100 ENNN00010...

Page 214: ...0 000 Zone Events Note Zone events are reported only when Report by Zone is selected Auxiliary power trouble FT 0000 FTNN000000 1 320 00 000 Auxiliary power trouble restore FJ 0000 FJNN000000 3 320 00 000 CO Detector Alarm GA Zone GANN000ZZZ 1 162 00 Zone CO Detector Alarm Restore GH Zone GHNN000ZZZ 3 162 00 Zone CO Detector Supervisory Alarm GS Zone GSNN000ZZZ 1 200 00 Zone CO Detector Supervisor...

Page 215: ... 115 00 Zone Manual pull switch trouble FT Zone FTNN000ZZZ 1 373 00 Zone Manual pull switch trouble restore FJ Zone FJNN000ZZZ 3 373 00 Zone Notification output trouble FT Group 1000 FTNN001GGG 1 320 00 Group Notification output trouble restore FJ Group 1000 FJNN001GGG 3 320 00 Group Positive Alarm Sequence ac knowledge switch trouble FT Zone FTNN000ZZZ 1 373 00 Zone Positive Alarm Sequence ac kno...

Page 216: ...d AUX2 switch trou ble restore UJ 2000 UJNN002000 3 373 02 000 Voice Aux ECS 1 Alarm UA 3 UANN003000 1 171 00 000 Voice Aux ECS 1 Alarm Restore UH 3 UHNN003000 3 171 00 000 Voice Aux ECS 2 Alarm UA 4 UANN004000 1 172 00 000 Voice Aux ECS 2 Alarm Restore UH 4 UHNN004000 3 172 00 000 Voice Aux ECS 3 Alarm UA 5 UANN005000 1 173 00 000 Voice Aux ECS 3 Alarm Restore UH 5 UHNN005000 3 173 00 000 Voice A...

Page 217: ...iary power enabled pi Exp ID FU Point FUNNXXPPPP 3 571 Exp ID Point Auxiliary power Trouble pi Exp ID FT Point FTNNXXPPPP 1 320 Exp ID Point Auxiliary power trouble restore pi Exp ID FJ Point FJNNXXPPPP 3 320 Exp ID Point Background Music Switch is Trouble pi Exp ID UT Point UTNNXXPPPP 1 379 Exp ID Point Background Music Switch is Trouble Restored pi Exp ID UJ Point UJNNXXPPPP 3 379 Exp ID Point B...

Page 218: ...CS Alarm Point Trouble Re store pi Exp ID QJ Point QJNNXXPPPP 3 242 Exp ID Point ECS Alarm Point Disabled pi Exp ID QB Point QBNNXXPPPP 1 243 Exp ID Point ECS Alarm Point Enabled pi Exp ID QU Point QUNNXXPPPP 3 243 Exp ID Point ECS Supervisory Tamper Alarm pi Exp ID QS Point QSNNXXPPPP 1 241 Exp ID Point ECS Supervisory Tamper Alarm Restore pi Exp ID QR Point QRNNXXPPPP 3 241 Exp ID Point ECS Supe...

Page 219: ...PP 3 110 Exp ID Point Interlock switch disabled pi Exp ID FB Point FBNNXXPPPP 1 571 Exp ID Point Interlock switch enabled pi Exp ID FU Point FUNNXXPPPP 3 571 Exp ID Point Interlock switch trouble Water Release Zone pi Exp ID FT Point FTNNXXPPPP 1 373 Exp ID Point Interlock switch trouble restore Water Release Zone pi Exp ID FJ Point FJNNXXPPPP 3 373 Exp ID Point LOC Mic Activated ECS Alarm pi Exp ...

Page 220: ...FB Point FBNNXXPPPP 1 571 Exp ID Point Positive Alarm Sequence ac knowledge switch enabled pi Exp ID FU Point FUNNXXPPPP 3 571 Exp ID Point Positive Alarm Sequence ac knowledge switch trouble pi Exp ID FT Point FTNNXXPPPP 1 373 Exp ID Point Positive Alarm Sequence ac knowledge switch trouble restore pi Exp ID FJ Point FJNNXXPPPP 3 373 Exp ID Point Status Point Trouble pi Exp ID UT Point UTNNXXPPPP...

Page 221: ...d pi Exp ID UB Point UBNNXXPPPP 1 571 Exp ID Point System based AUX2 switch en abled pi Exp ID UU Point UUNNXXPPPP 3 571 Exp ID Point System based AUX2 switch trouble pi Exp ID UT Point UTNNXXPPPP 1 373 Exp ID Point System based AUX2 switch trouble restore pi Exp ID UJ Point UJNNXXPPPP 3 373 Exp ID Point Voice Aux ECS 1 Point Alarm pi Exp ID UA 3PPP PPP Point UANNXX3PPP 1 171 Exp ID Point Voice Au...

Page 222: ...NNXXPPPP 1 379 Exp ID Point Voice Aux Status 2 Switch is Trouble Restored pi Exp ID UJ Point UJNNXXPPPP 3 379 Exp ID Point Voice Aux Status 2 Switch is Disabled pi Exp ID UB Point UBNNXXPPPP 1 580 Exp ID Point Voice Aux Status 2 Switch is Enabled pi Exp ID UU Point UUNNXXPPPP 3 580 Exp ID Point Water flow switch alarm pi Exp ID SA Point SANNXXPPPP 1 113 Exp ID Point Water flow switch alarm restore...

Page 223: ...restore pi Exp ID UH Point UHNNXXPPPP 3 140 Exp ID Point Zone based AUX2 switch dis abled pi Exp ID UB Point UBNNXXPPPP 1 571 Exp ID Point Zone based AUX2 switch en abled pi Exp ID UU Point UUNNXXPPPP 3 571 Exp ID Point Zone based AUX2 switch trouble pi Exp ID UT Point UTNNXXPPPP 1 373 Exp ID Point Zone based AUX2 switch trouble restore pi Exp ID UJ Point UJNNXXPPPP 3 373 Exp ID Point System based...

Page 224: ...t IFP 2100 ECS Panels PI Modifier Reporting Examples Event Report Zone Point Panel ID Module Zone ZZZZ Point ZZZZ Fields Sent SIA Event Data Fire Alarm Zone Zone n a n a97 15 n a EE ZZ FA15 Fire Alarm Zone Zone n a n a 05 n a EE Z FA5 Fire Alarm Point Point n a 01 n a 123 EE ZZ EE ZZZ pi01 FA123 Fire Alarm Point Point n a 33 n a 203 EE ZZ EE ZZZ pi11 FA203 Expander Trouble n a n a 11 n a n a EE ZZ...

Page 225: ... Point Panel ID PP Module MM Zone ZZZZ Point ZZZZ Fields Sent SIA Event Data Fire Alarm Zone Zone 32 n a 15 n a EE PP MM ZZZZ FA32000015 Fire Alarm Zone Zone 32 n a 05 n a EE PP MM ZZZZ FA32000005 Fire Alarm Point Point 32 01 n a 123 EE PP MM ZZZZ FA32010123 Fire Alarm Point Point 21 33 n a 203 EE PP MM ZZZZ FA21330203 Expander Trouble n a 15 11 n a n a EE PP MM ZZZZ ET15110000 Auto Test n a 32 n ...

Page 226: ...terminals labeled SLC IN Make sure SLC devices have been addressed properly following the procedure described in Section 7 9 if using SD devices or Section 7 7 if using IDP or SK devices Make sure correct polarity has been observed for SLC device wiring See Section 7 8 if using SD devices or Section 7 7 for IDP or SK devices SLC devices are not being recognized trouble message Missing displays on ...

Page 227: ...15XL has not been added to the system through programming JumpStart will add any 5815XLs connected to the panel 5815XLs can be added manually see Section 9 2 2 Check that the correct ID for the 5815XL module has been set through the DIP switches Assign ID 1 to the first 5815XL and ID 2 to the second 5815XL See Section 4 13 1 for complete details If the wiring between the 5815XL and the panel is co...

Page 228: ... used to locate a device on a SLC loop Follow these steps to locate a particular SLC device 1 Select 2 for Point Functions from the Main Menu 2 Select 4 for SLC Single Device Locator A message similar to the one shown in Figure 13 1 will display Figure 13 1 Shut Down Warning 3 Press ENTER to accept or left arrow to Exit If left arrow is chosen you will exit back to the Point Function menu If ENTER...

Page 229: ...ill start flashing 6 Press the left arrow key to exit SLC Multiple Device Locator Note Once you exit the system will resume normal operation 13 5 3 I O Point Control This feature allows you to toggle any output on or off and trip any input device This can be useful to test a point s output mapping I O Point Control shall only be allowed to be accessed if enabled by the user profile Follow these st...

Page 230: ...ow Trip Low Restore Flexput Notification Circuits X I O 8 0 0 O 0 0 X I O 7 0 0 O 0 0 X I O 6 0 0 O 0 0 X I O 5 0 0 O 0 0 X I O 4 0 0 O 0 0 X I O 3 0 0 O 0 0 X I O 2 0 0 O 0 0 X I O 1 0 0 O 0 0 SBUS Communication B SBUS1 OUT 0 0 A 0 0 SBUS Power 0 0 0 0 SBUS Communication B SBUS1 IN 0 0 A 0 0 SBUS Power 0 0 0 0 SBUS Communication B SBUS2 OUT 0 0 A 0 0 SBUS Power 0 0 0 0 SBUS Communication B SBUS 2...

Page 231: ... Module Addr Zone Group Description On board 1 On board 31 On board 2 On board 32 On board 3 On board 33 On board 4 On board 34 On board 5 On board 35 On board 6 On board 36 On board 7 On board 37 On board 8 On board 38 On board 9 On board 39 On board 10 On board 40 On board 11 On board 41 On board 12 On board 42 On board 13 On board 43 On board 14 On board 44 On board 15 On board 45 On board 16 O...

Page 232: ... board 79 On board 123 On board 80 On board 124 On board 81 On board 125 On board 82 On board 126 On board 83 On board 127 On board 84 On board 128 On board 85 On board 129 On board 86 On board 130 On board 87 On board 131 On board 88 On board 132 On board 89 On board 133 On board 90 On board 134 On board 91 On board 135 On board 92 On board 136 On board 93 On board 137 On board 94 On board 138 On...

Page 233: ...oard 147 On board 154 On board 148 On board 155 On board 149 On board 156 On board 150 On board 157 On board 151 On board 158 On board 152 On board 159 On board 153 Table 14 2 Installation Record of Devices Installed on 5815XL Module Addr Zone Group Description Module Addr Zone Group Description Table 14 1 Installation Record of Onboard Devices Module Addr Zone Group Description Module Addr Zone G...

Page 234: ...LS10143 001SK E Installation Records 14 4 Table 14 2 Installation Record of Devices Installed on 5815XL Module Addr Zone Group Description Module Addr Zone Group Description ...

Page 235: ...tallation Manual LS10143 001SK E 14 5 14 2 Conventional Output Point Record This chart can be used to keep track of how conventional output points circuits have been configured Point Circuit Group Description 1 2 3 4 5 6 7 8 ...

Page 236: ...ich can be synchronized indicate the type of SYNC available in the columns marked Audio and Visual Table A 1 Compatible Notification Appliances Manufacturer Model Audio Visual Type AMSECO SH24W 153075 X X Horn Strobe SAD24 153075 X Strobe SAD24 75110 X Strobe SL24W 75110 X Strobe SL24C 3075110 X Strobe SLB24 75 X Strobe RSD24 153075 X Strobe RSD24 75110 X Strobe SH24W 75110 X X Horn Strobe SH24W 3...

Page 237: ...P24110 FC X X Horn Strobe P24110W FC X X Horn Strobe P24110K FC X X Horn Strobe S2430W FC X Strobe S2430K FC X Strobe S2475 FC X Strobe S2475W FC X Strobe S2475K FC X Strobe S24110 FC X Strobe S24110W FC X Strobe S24110K FC X Strobe Federal Signal 450 X Horn VALS X X Horn Strobe Gentex GEC 24 15 X X Horn Strobe GEC 24 30 X X Horn Strobe GEC 24 60 X X Horn Strobe GEC 24 75 X X Horn Strobe GEC 24 17...

Page 238: ...Strobe GESR 24 X Multi Candella Strobe GEH 24 X Horn ST24 30 X Strobe ST24 60 X Strobe ST24 75 X Strobe ST24 110 X Strobe ST24 1575 X Strobe WGEC24 75W X X Weatherproof Horn Strobe WGES24 75W X Weatherproof Strobe WGMS 24 X X X Horn Strobe GEC 24 110 X X Horn Strobe GEC 24 15 75 X X Horn Strobe System Sensor CHR X Chime CHW X Chime CHSR X X 2 Wire Chime Strobe CHSW X X 2 Wire Chime Strobe HR X X H...

Page 239: ... X 2 Wire Horn Strobe High Candela PC2RHK X X 2 Wire Horn Strobe High Candela P4R X X 4 Wire Horn Strobe PC4R X X 4 Wire Horn Strobe P4RH X X 4 Wire Horn Strobe High Candela P4W X X 4 Wire Horn Strobe PC4W X X 4 Wire Horn Strobe P4WH X X 4 Wire Horn Strobe High Candela PC4WH X X 4 Wire Horn Strobe High Candela P4RK X X 4 Wire Horn Strobe PC4RK X X 4 Wire Horn Strobe P4RHK X X 4 Wire Horn Strobe Hi...

Page 240: ...e SRHK X Strobe High Candela SCRHK X Strobe High Candela SRL SRL P SRL SP X Strobe Red Wall 4x4 SWL SWL P SWL ALERT SWL CLR ALERT X Strobe White Wall 4x4 SCRL X Strobe Red Ceil 4x4 SCWL X Strobe White Ceil 4x4 SCWL CLR ALERT X Strobe WHT Ceil CLR Lens 4x4 SGRL X Strobe Red Wall 2x4 SGWL X Strobe White Wall 2x4 P2RH LF X X 2 Wire Low Frequency Sounder Strobe P2WH LF X X 2 Wire Low Frequency Sounder...

Page 241: ...4MCW X X Horn Strobe AS 24MCWH X X Horn Strobe ASWP 2475W X X Horn Strobe Weatherproof ASWP 2475C X X Horn Strobe Weatherproof ASWP 24MCWH X X Horn Strobe ASWP 24MCCH X X Horn Strobe CH 70 X Chime CH 90 X Chime CH70 241575W X Chime Strobe CH70 24MCW X Chime Strobe CH70 24MCWH X Chime Strobe CH90 24MCC X Chime Strobe CH90 24MCCH X Chime Strobe HS 24 X Horn HS4 241575W X X Horn Strobe HS4 24MCW X X ...

Page 242: ...e NS 24MCW X X Horn Strobe NS 24MCC X X Horn Strobe NS 24MCCH X X Horn Strobe ZNS MCW X X Horn Strobe ZNS MCWH X X Horn Strobe ZNS 24MCC X X Horn Strobe ZNS 24MCCH X X Horn Strobe RSS 121575W X Strobe RSS 241575W X Strobe RSS 24MCC X Strobe RSS 24MCCR X Strobe RSS 24MCCH X Strobe RSS 24MCCHR X Strobe RSS 24MCW X Strobe RSS 24MCWH X Strobe RSSP 121575W X Strobe RSSP 241575W X Strobe RSSR 2415W X St...

Page 243: ...aximum Wheelock cont RSSR 24MCC X Multi Candela Strobe RSSWPA 2475W X Strobe Weatherproof RSSWPA 24MCCH X Strobe Weatherproof RSSWPG 24MCCH X Strobe Weatherproof RSSWPR 24MCCH X Strobe Weatherproof RSSWP 2475W X Strobe Weatherproof RSSWP 2475C X Strobe Weatherproof RSSWP 24MCWH X Strobe Weatherproof ZRS MCWH X Strobe ZRS 24MCC X Strobe ZRS 24MCCH X Strobe MB G6 24 Motor Bell MB G10 24 Motor Bell M...

Page 244: ... 325 55000 325 55000 326 55000 326 55000 327 55000 327 55000 328 55000 328 Hochiki SLR 24 HD 3 HSC 220R HB 72 NS6 220 OR NS4 220 HB 3 15 loop SLR 24H SLR 24V SLR 835 HD 3 14 loop SLR 835H HD 5 System Sensor 1400 A N A 16 loop 1451 B401B A N A 16 loop 2100 A N A 20 loop 2100T A N A 20 loop 2151 B401 A N A 16 loop 2151T B401 A N A 16 loop 2400 A N A 16 loop 2400TH A N A 16 loop 2451 B401B A N A 16 l...

Page 245: ...l Supervisory Relay 15 45 System Sensor 2312 24TB Photoelectric 0 12 50 System Sensor 2412 12 volt Photoelectric 0 12 77 System Sensor 2412AT 12 volt Photoelectric 0 12 58 System Sensor 2412TH 12 volt Photoelectric 0 12 77 System Sensor 2424 Photoelectric 0 10 41 System Sensor 2424TH Photoelectric 0 10 41 System Sensor 2451 Photoelectric 0 10 39 System Sensor 2451TH with B402B Base Photoelectric 0...

Page 246: ...DH154A Flush Mount 96 Edwards DH158A Surface Mount 96 Rixon Firemark FM 980 Floor Mount single 68 Rixon Firemark FM 996 Surface Wiring 68 Rixon Firemark FM 998 Concealed Wiring 68 Manufacturer Model Current mA Air Products Controls LTD MR 101 C MR 201 C PAM 1 PAM 2 PAM SD 15 35 15 15 15 System Sensor A77 716B PR 1 PR 2 PR 3 EOLR 1 R 10T R 14T R 20T R 24T R 10E R 14E R 20E R 24E 20 15 30 30 30 23 2...

Page 247: ...hite SPSW P Wall High Fidelity Speaker Strobe Plain Red SPSWH Wall High Fidelity Speaker Strobe High Candela White SPSWH P Wall High Fidelity Speaker Strobe High Candela Plain Red SPRL Wall High Fidelity Speaker Red SPWL Wall High Fidelity Speaker White SPCRL Ceiling High Fidelity Speaker Red SPCWL Ceiling High Fidelity Speaker White SPSCRL Ceiling High Fidelity Speaker Strobe Red SPSCWL Ceiling H...

Page 248: ...llation Manual LS10143 001SK E 13 A 7 Compatible 520Hz Low Frequency Bases Table A 7 Low Frequency Bases Model Number Description B200S LF Low Frequency Intelligent Sounder Base B200SR LF Low Frequency Intelligent Sounder Base ...

Page 249: ...s the available characters and their associated numeric designator When programming 1 Use the Up or Down arrow key to scroll to the mode wanted 2 Press the number shown in Table B 1 until the character wanted is shown 3 Arrow left and right for position and press enter to accept Table B 1 Character Table Lower Case Letters abc 1 def 2 ghi 3 jkl 4 mno 5 pqr 6 stu 7 vwx 8 yz 9 Spc 0 Upper Case Lette...

Page 250: ...ode to lower case letters Press 3 until i appears 3 Press 6 until r appears 4 Press 2 until e appears 5 Press 0 to space then continue to next word using the same process 6 Press ENTER to accept Note After three seconds of no change letter will automatically be accepted Also pressing next number will au tomatically accept previous choice Figure B 1 Edit Name Example ...

Page 251: ...ECS Installation Manual LS10143 001SK E 1 Appendix C Cadence Patterns The cadence patterns shown in Appendix C are available for use with the control panel Figure C 1 Cadence Patterns Available with the Control Panel ...

Page 252: ...pulated based on panel number and audited to allow only the 4 appropriate receivers See Section 6 2 6 3 Table D 1 Receiver panel relationship Panel Available receiver numbers 1 1 2 3 4 2 5 6 7 8 3 9 10 11 12 4 13 14 15 16 5 17 18 19 20 6 21 22 23 24 7 25 26 27 28 8 29 30 31 32 9 33 34 35 36 10 37 38 39 40 11 41 42 43 44 12 45 46 47 48 13 49 50 51 52 14 53 54 55 56 15 57 58 59 60 16 61 62 63 64 17 ...

Page 253: ...igure networks and firewalls Assess security risks Develop a Disaster and Recovery Plan Develop a Backup and Recovery Strategy Install configure and keep anti virus software updated on all computers which access the panel Keep operating system updated on all computers which access the panel Deliver all required system information upon delivery to the system owner Train end users on security mainte...

Page 254: ...NTIES EITHER EXPRESSED OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This ...

Page 255: ...ct System Tests 3 Enter code if prompted then press 1 to select Fire Drill 4 Press ENTER to start the fire drill and Press ENTER to end the fire drill Check Detector Sensitivity 1 Follow steps 1 through 5 for viewing a point s status 2 Press the right arrow to view detector sensitivity Set Time and Date 1 Enter the installer code The panel will automatically go to the main menu 2 Press 4 to select...

Page 256: ...Cut Along the Dotted Line ...

Page 257: ...Hold the DRILL button and then enter a code if prompted OR 1 Enter the installer code The panel will automatically go to the main menu 2 Press 1 to select System Tests 3 Enter code if prompted then press 1 to select Fire Drill 4 Press ENTER to start the fire drill and Press ENTER to end the fire drill Set Time and Date 1 Enter the installer code The panel will automatically go to the main menu 2 P...

Page 258: ...Cut Along the Dotted Line ...

Page 259: ... to output the page ECS Control LED Green Blink When this LED is blinking someone has requested control of the ECS System On LOC has ECS Control and the user is able to make changes to the ECS Off LOC does not have ECS Control ECS Message LED Red On The corresponding ECS event was activated by an ECS device Off The corresponding ECS event was not activated from this LOC Green On The corresponding ...

Page 260: ...Cut Along the Dotted Line ...

Page 261: ...another LOC has ECS Control the display will be similar to the one shown Press 1 to request control The LOC with ECS Control will then be able to allow or deny the request Gain ECS Control as ECS Super User at an LOC only one ECS Super User is allowed ECS Control in the system at a time From the idle screen enter an ECS Super User access code and then press the ECS Control Key If ECS Control as Su...

Page 262: ...Cut Along the Dotted Line ...

Page 263: ......

Page 264: ...Honeywell Farenhyt 12 Clintonville Road Northford CT 06472 1610 203 484 7161 Fax 203 484 7118 www farenhyt com Farenhyt Series ...

Reviews: