LS10143-001SK-E
Control Panel Installation
4-10
4.5
RA-2000 Remote Annunciator Installation
The optional Model RA-2000 Remote Annunciator, shown in Figure 4-11. The RA-2000 can be surface or flush
mounted. It is available in gray color as RA-2000GRAY.
Figure 4-11 Model RA-2000 Remote Annunciator, Front View
RA-2000 installation involves the following steps:
1.
Make sure power is off at the panel.
2.
Mount the RA-2000 in the desired location (see Section 4.5.1).
3.
Connect the RA-2000 to the panel (see Section 4.5.2).
4.
Use the DIP switches on the back of the RA-2000 to assign an SBUS ID# to the RA-2000 (see Section
4.13.1).
5.
The RA-2000 module must be added to the system through programming. JumpStart will add the module
automatically (see Section 8.1). You can also add it manually (see Section 9.2.2). Select a name, if desired
(see Section 9.2.1.2).
4.5.1
Mounting the RA-2000
4.5.1.1 Flush Mounting
This section of the manual describes flush mounting.
Follow these steps to flush mount the RA-2000